Mitsubishi Electric Corporation (Factory Automation / FA Systems Group) FX5-CCLGN-MS
FX5-CCLGN-MS
Технические характеристики
| Applicable Controller | MX Controller MX-F model *1 |
|---|---|
| Applicable CPU module | FX5UJ CPU module: Ver. 1.040 or later FX5U CPU module: Ver. 1.210 or later FX5UC CPU module*: Ver. 1.210 or later * FX5-CNV-IFC or FX5-C1PS-5V is required to connect to the FX5UC CPU module. |
| GX Works3 | FX5UJ CPU module: Ver. 1.090U or later FX5U CPU module: Ver. 1.065T or later FX5UC CPU module: Ver. 1.065T or later |
| Number of occupied I/O points | 8 points |
| Масса | Approx. 0.3 kg |
| Communication method | Time sharing method |
| Communication speed | ・1 Gbps ・100Mbps* * This setting can be used for the firmware version "1.010" or later. |
| Network topology | Line topology, star topology (Coexistence of line topology and star topology is also possible.) |
| Station type | Manager or local station |
| Station number | ・Manager station: 0 ・Local station: 1 to 120 |
| Number of connectable modules | One module can be connected to the CPU module for each station type. ・Manager station: 1 ・Local station: 1 |
| When used as a manager station | 61 |
| When used as a local station | 121 |
| RX | 16 K points (16384 points, 2 K bytes) |
| RY | 16 K points (16384 points, 2 K bytes) |
| RWr | 8 K points (8192 points, 16 K bytes) |
| RWw | 8 K points (8192 points, 16 K bytes) |
| Maximum number of link points per station > Manager station > RX | 8 K points (8192 points, 1 K bytes) The maximum number of points for all link devices may not be used simultaneously depending on the number of device stations, or the number of points and assignments of the link devices that are set in the "Network Configuration Settings" of the "Basic Settings". |
| Maximum number of link points per station > Manager station > RY | 8 K points (8192 points, 1 K bytes) The maximum number of points for all link devices may not be used simultaneously depending on the number of device stations, or the number of points and assignments of the link devices that are set in the "Network Configuration Settings" of the "Basic Settings". |
| Maximum number of link points per station > Manager station > RWr | 4 K points (4096 points, 8 K bytes) The maximum number of points for all link devices may not be used simultaneously depending on the number of device stations, or the number of points and assignments of the link devices that are set in the "Network Configuration Settings" of the "Basic Settings". |
| Maximum number of link points per station > Manager station > RWw | 4 K points (4096 points, 8 K bytes) The maximum number of points for all link devices may not be used simultaneously depending on the number of device stations, or the number of points and assignments of the link devices that are set in the "Network Configuration Settings" of the "Basic Settings". |
| Maximum number of link points per station > Local station > RX | 16 K points (16384 points, 2 K bytes) The maximum number of points for all link devices may not be used simultaneously depending on the number of device stations, or the number of points and assignments of the link devices that are set in the "Network Configuration Settings" of the "Basic Settings". |
| Maximum number of link points per station > Local station > RY | 16 K points (16384 points, 2 K bytes) The maximum number of points for all link devices may not be used simultaneously depending on the number of device stations, or the number of points and assignments of the link devices that are set in the "Network Configuration Settings" of the "Basic Settings". |
| Maximum number of link points per station > Local station > RWr | 8 K points (8192 points, 16 K bytes) The maximum number of points for all link devices may not be used simultaneously depending on the number of device stations, or the number of points and assignments of the link devices that are set in the "Network Configuration Settings" of the "Basic Settings". |
| Maximum number of link points per station > Local station > RWw | 8 K points (8192 points, 16 K bytes) The maximum number of points for all link devices may not be used simultaneously depending on the number of device stations, or the number of points and assignments of the link devices that are set in the "Network Configuration Settings" of the "Basic Settings". |
| Minimum synchronization cycle | 250.00 μs |
| Connection cable | Ethernet cable which satisfies standard: Category 5e or higher, straight cable (double shielded, STP) |
| Line topology | 12000 m (when 121 stations are connected) |
| Others | Depends on the system configuration. |
| Maximum station-to-station distance | 100 m |
| CC-Link IE TSN Class | B |
| Network number setting range | 1 to 239 |
| Transient transmission capacity | 1920 bytes |
| CC-Link IE TSN Protocol version | ・2.0* ・1.0 * This setting can be used for the firmware version "1.010" or later. |
| Data transmission speed | ・1Gbps ・100Mbps* * This setting can be used for the firmware version "1.010" or later. |
| 1000BASE-T | Full-duplex |
| 100BASE-TX | Full-duplex* * This setting can be used for the firmware version "1.010" or later. |
| Interface | RJ45 connector (Auto MDI/MDI-X) |
| Maximum frame size | 1518 bytes |
| Maximum segment length | 100 m* * For maximum segment length (length between switching hubs), consult the manufacturer of the switching hub used. |
| Number of cascade connections | Consult the manufacturer of the switching hub used. |
| IP version | IPv4 |
| Connection with MELSOFT products | 8 connections* * In the case of one connection per device, up to eight devices can be connected. |
| Connection to SLMP-compatible devices | 8 connections* * In the case of one connection per device, up to eight devices can be connected. |
| Напряжение питания | 24 V DC +20%, -15% |
| Allowable instantaneous power failure time | Operation continues for an instantaneous power failure of 1ms or less. |
| Current consumption | 220 mA |
| Рабочая температура | Operating ambient temperature -20 to 55℃* * When using the FX5-CCLGN-MS manufactured in December 2020 or earlier, the operating ambient temperature is -20 to 50℃. |
| Between all external terminals and ground terminal of CPU module | 500 V AC for one minute |
| Insulation resistance > Between all external terminals and ground terminal of CPU module | 10 MΩ or higher by 500 V DC insulation resistance tester |
| Category (site listing) | MELSEC iQ-F |