| Input type | DC input (positive common type) |
|---|---|
| Number of input points | 16 points |
| Напряжение питания | 24 V DC (ripple ratio: within 5 %) (allowable voltage range: 20.4...28.8 V DC) |
| Rated input current | 6.0 mA TYP. (24 V DC) |
| Maximum number of simultaneous input points | 100 % |
| Напряжение питания | 11 V DC or more/4 mA or more |
| Напряжение питания | 5 V DC or less/1.5 mA or less |
| Input resistance | 3.3 kΩ |
| OFF to ON | 0 ms, 0.2 ms, 1 ms, 1.5 ms, 5 ms, 10 ms, 20 ms, 70 ms |
| ON to OFF | 0 ms, 0.2 ms, 1 ms, 1.5 ms, 5 ms, 10 ms, 20 ms, 70 ms |
| Input common terminal arrangement | 16 points/common (1-wire, spring clamp terminal block type) |
| Output type | Transistor output (sink type) |
| Number of output points | 16 points |
| Напряжение питания | 24 V DC (ripple ratio: within 5 %) (allowable voltage range: 20.4...28.8 V DC) |
| Maximum load current | 0.5 A/point, 4 A/common |
| Maximum inrush current | Current is limited by the overload protection function. |
| Leakage current at OFF | 0.1 mA or less |
| Напряжение питания | 0.3 V DC (TYP.) 0.5 A, 0.6 V DC (MAX.) 0.5 A |
| Время отклика | 0.1 ms or less |
| Время отклика | 0.8 ms or less (resistive load) |
| Surge suppressor | Zener diode |
| Overheat protection function | Activated in increments of 1 point. |
| Overload protection function | Limit current with overload protection at overcurrent detection: 1.5...3.5 A/point Activated in increments of 1 point. |
| Напряжение питания | 24 V DC (ripple ratio: within 5 %) (allowable voltage range: 20.4...28.8 V DC) |
| Current | 25 mA or less (TYP. 24 V DC/common), excluding external load current |
| Output common terminal arrangement | 16 points/common (1-wire, spring clamp terminal block type) |
| Напряжение питания | Between all DC external terminals and ground: 510 V AC for 1 minute |
| Insulation resistance | Between all DC external terminals and ground: 10 MΩ or higher by 500 V DC insulation resistance tester |
| Protection degree | IP2X |
| Station type | CC-Link IE TSN Communication Mode: Remote station CC-Link IE Field Network Communication Mode: Intelligent device station |
| CC-Link IE TSN Class | CC-Link IE TSN Class B CC-Link IE TSN Class A |
| CC-Link IE TSN Class B | Protocol version 2.0/1.0 |
| CC-Link IE TSN Class A | Protocol version 2.0 |
| Время отклика | 512 µs |
| Network topology | Line topology, star topology (Coexistence of line topology and star topology is possible.), and ring topology |
| Multicast filter | Available |
| RX/RY points | 32 points |
| RWr/RWw points | 4 points |
| Module power supply > Current | 110 mA or less (at 24 V DC, all points ON) |
| External interface | Communication part: RJ45 connector Module power supply part: Terminal block for module power supply and FG (two-piece spring clamp terminal block) I/O part: Two-piece spring clamp terminal block |
| Height | 54.5 mm |
| Width | 179 mm |
| Depth | 45.5 mm |
| Масса | 0.20 kg |
| Data transmission speed | 1 Gbps/100 Mbps |
| Communication mode | 1000BASE-T: Full-duplex 100BASE-TX: Full-duplex |
| Interface | RJ45 (AUTO MDI/MDI-X) |
| Maximum frame size | 1518 bytes |
| Maximum segment length | 100 m |
| Number of cascaded connections | Consult the manufacturer of the switching hub used. |
| IP version | IPv4 |
| Рабочая температура | 0...55 ˚C |
| Storage ambient temperature | -25...75 ˚C |
| Operating ambient humidity | 5...95 %RH, non-condensing |
| Storage ambient humidity | 5...95 %RH, non-condensing |
| Under intermittent vibration | Frequency: 5...8.4 Hz, Half amplitude: 3.5 mm Frequency: 8.4...150 Hz, Constant acceleration: 9.8 m/s 2 Sweep count: 10 times each in X, Y, and Z directions |
| Under continuous vibration | Frequency: 5...8.4 Hz, Half amplitude: 1.75 mm Frequency: 8.4...150 Hz, Constant acceleration: 4.9 m/s 2 |
| IEC 61131-2: 2007/JIS B 3502: 2011 | Three shocks in each direction per axis, on 3 mutually perpendicular axes (total of 18 shocks) |
| Operating atmosphere | No corrosive gases, flammable gases, less conductive dust |
| Operating altitude | 0...2000 m |
| Installation location | Inside a control panel |
| Напряжение питания | II or less |
| Pollution degree | 2 or less |
| Equipment class | Class I |
| Category (site listing) | Remote I/O |