Технические характеристики

Control methodStored program cyclic operation
I/O control modeRefresh mode (The direct access input/output is available by specifying the direct access input/output (DX, DY).)
Sequence control languageRelay symbol language, logic symbolic language, MELSAP3 (SFC), MELSAP-L, function block and structured text (ST)
LD X0200 ns
MOV D0 D1700 ns
Constant scan1...2000 ms (setting is available in increments of 1 ms by parameter)
Program capacity8K steps (32K bytes)
Program memory (drive 0)58K bytes
Standard ROM (drive 4)58K bytes
Program memory6
Standard ROM6
Initial setting512 parameters
Refresh256 parameters
Number of I/O device points2048 points (X/Y0...7FF)
Number of I/O points256 points (X/Y0...FF)
Internal relay (M)8192 points (M0...8191) by default (changeable)
Latch relay (L)2048 points (L0...2047) by default (changeable)
Link relay (B)2048 points (B0...7FF) by default (changeable)
Timer (T)512 points (T0...511) by default (changeable) (Low-speed and high-speed timers available) Low-speed or high-speed is specified by an instruction. The measurement unit is set by parameter. (Low-speed timer: 1...1000 ms (in increments of 1 ms), default: 100 ms) (High-speed timer: 0.1...100.0 ms (in increments of 0.1 ms), default: 10.0 ms)
Retentive timer (ST)0 points by default (changeable) (Low-speed and high-speed retentive timers available) Low-speed or high-speed is specified by an instruction. The measurement unit is set by parameter. (Low-speed retentive timer: 1...1000 ms (in increments of 1 ms), default: 100 ms) (High-speed retentive timer: 0.1...100.0 ms (in increments of 0.1 ms), default: 10.0 ms)
Counter (C)Normal counter: 512 points (C0...511) by default (changeable) Interrupt counter: 128 points max. (0 points by default, setting by parameters)
Data register (D)11136 points (D0...11135) by default (changeable)
Link register (W)2048 points (W0...7FF) by default (changeable)
Annunciator (F)1024 points (F0...1023) by default (changeable)
Edge relay (V)1024 points (V0...1023) by default (changeable)
Link special relay (SB)1024 points (SB0...3FF) (The number of device points is fixed.)
Link special register (SW)1024 points (SW0...3FF) (The number of device points is fixed.)
Step relay (S)2048 points (S0...127/block) (The number of device points is fixed.)
Index register (Z)10 points (Z0...9) (The number of device points is fixed.)
Pointer (P)300 points (P0...299) (The number of device points is fixed.)
Interrupt pointer (I)128 points (I0...127) (The number of device points is fixed.) (The fixed scan interval for the system interrupt pointer I28 to 31 can be set by parameter.) 2...1000 ms (in increments of 1 ms) Default I28: 100 ms, I29: 40 ms, I30: 20 ms, I31: 10 ms
Special relay (SM)1024 points (SM0...1023) (The number of device points is fixed.)
Special register (SD)1024 points (SD0...1023) (The number of device points is fixed.)
Function input (FX)16 points (FX0...F) (The number of device points is fixed.)
Function output (FY)16 points (FY0...F) (The number of device points is fixed.)
Function register (FD)5 points (FD0...4) (The number of device points is fixed.)
Link direct deviceDevice that directly accesses the link device of a network module Specification format: J□□\X□□, J□□\Y□□, J□□\SB□□, J□□\W□□, J□□\SW□□
Intelligent function module deviceDevice that directly accesses the buffer memory of an intelligent function module Specified form: U...\G...
Latch (data retention during power failure) range2048 points (L0...2047) by default (The latch range can be set for the devices, B, F, V, T, ST, C, D, and W.)
RUN/PAUSE contactOne contact can be set up in X0 to X7FF for each of RUN and PAUSE.
Clock functionYear, month, date, hour, minute, second, and day of week (automatic leap year detection) Accuracy: -3.20...+5.27 s (TYP. +1.98 s)/d at 0 ˚C Accuracy: -2.57...+5.27 s (TYP. +2.22 s)/d at 25 ˚C Accuracy: -11.68...+3.65 s (TYP. -2.64 s)/d at 55 ˚C
Allowable momentary power failure timeWithin 20 ms (100 V AC or more)
Internal current consumption (5 V DC)0.26 A
Height98 mm
Width245 mm
Depth98 mm
Масса0.66 kg
Напряжение питания100...240 V AC (-15 %...+10 %)
Input frequency50/60 Hz ±5 %
Напряжение питанияWithin 5 %
Maximum input apparent power105 VA
Inrush current40 A, within 8 ms
5 V DC3 A
Overcurrent protection > 5 V DC3.3 A or more
Напряжение питания5.5...6.5 V
Efficiency65 % or more
Напряжение питанияBetween the input and LG batched terminal and the output and FG batched terminal, 2300 V AC per minute (altitude 0...2000 m)
Insulation resistanceInput and LG batched, output and FG batched, batch input-LG, batch output-FG: 10 MΩ or higher by 500 VDC insulation resistance tester
Operation indicationLED indication (The POWER LED of the CPU part: Normal: On (green), Error: Off)
FuseBuilt-in (user-unchangeable)
Contact output sectionNone
External interfaceTerminal block (M3.5 screw)
Number of mountable I/O modules5
Applicable moduleMELSEC-Q series modules
Рабочая температура0...55 ˚C
Storage ambient temperature-25...75 ˚C
Operating ambient humidity5...95 %RH, non-condensing
Storage ambient humidity5...95 %RH, non-condensing
Under intermittent vibrationFrequency: 5...8.4 Hz, Half amplitude: 3.5 mm Frequency: 8.4...150 Hz, Constant acceleration: 9.8 m/s 2 Sweep count: 10 times each in X, Y, Z directions
Under continuous vibrationFrequency: 5...8.4 Hz, Half amplitude: 1.75 mm Frequency: 8.4...150 Hz, Constant acceleration: 4.9 m/s 2
Shock resistanceCompliant with JIS B 3502 and IEC 61131-2 (147 m/s 2 , 3 times each in 3 directions X, Y, Z)
Operating atmosphereNo corrosive gases
Operating altitude0...2000 m
Installation locationInside a control panel
Напряжение питанияII or less
Pollution degree2 or less
Equipment classClass I
Category (site listing)Programmable controller CPU
Получить предложение по этой позиции