Mitsubishi Electric Corporation (Factory Automation / FA Systems Group) Q06PHCPU
Q06PHCPU
Технические характеристики
| Control method | Stored program cyclic operation |
|---|---|
| I/O control mode | Refresh mode (The direct access input/output is available by specifying the direct access input/output (DX, DY).) |
| Sequence control language | Relay symbol language, logic symbolic language, MELSAP3 (SFC), MELSAP-L, function block and structured text (ST) |
| Process control language | FBD for process control |
| LD X0 | 34 ns |
| MOV D0 D1 | 102 ns |
| Constant scan | 0.5...2000 ms (setting is available in increments of 0.5 ms by parameter) |
| Program capacity | 60K steps (240K bytes) |
| Program memory (drive 0) | 240K bytes |
| Memory card (RAM) (drive 1) | Size of the installed memory card (2M bytes max.) |
| Memory card (ROM) (drive 2) | Size of the installed memory card (Flash card: 4M bytes max., ATA card: 32M bytes max.) |
| Standard RAM (drive 3) | 128K bytes |
| Standard ROM (drive 4) | 240K bytes |
| QCPU standard memory | 8K bytes |
| Program memory | 60 |
| Memory card (RAM) | 287 (when the Q2MEM-2MBS is used) |
| Flash card | 288 |
| ATA card | 512 |
| Standard RAM | 3 |
| Standard ROM | 60 |
| Initial setting | 512 parameters |
| Refresh | 256 parameters |
| Number of I/O device points | 8192 points (X/Y0...1FFF) |
| Number of I/O points | 4096 points (X/Y0...FFF) |
| Internal relay (M) | 8192 points (M0...8191) by default (changeable) |
| Latch relay (L) | 8192 points (L0...8191) by default (changeable) |
| Link relay (B) | 8192 points (B0...1FFF) by default (changeable) |
| Timer (T) | 2048 points (T0...2047) by default (changeable) (Low-speed and high-speed timers available) Low-speed or high-speed is specified by an instruction. The measurement unit is set by parameter. (Low-speed timer: 1...1000 ms (in increments of 1 ms), default: 100 ms) (High-speed timer: 0.1...100.0 ms (in increments of 0.1 ms), default: 10.0 ms) |
| Retentive timer (ST) | 0 points by default (changeable) (Low-speed and high-speed retentive timers available) Low-speed or high-speed is specified by an instruction. The measurement unit is set by parameter. (Low-speed retentive timer: 1...1000 ms (in increments of 1 ms), default: 100 ms) (High-speed retentive timer: 0.1...100.0 ms (in increments of 0.1 ms), default: 10.0 ms) |
| Counter (C) | Normal counter: 1024 points (C0...1023) by default (changeable) Interrupt counter: 256 points max. (0 points by default, setting by parameters) |
| Data register (D) | 12288 points (D0...12287) by default (changeable) |
| Link register (W) | 8192 points (W0...1FFF) by default (changeable) |
| Annunciator (F) | 2048 points (F0...2047) by default (changeable) |
| Edge relay (V) | 2048 points (V0...2047) by default (changeable) |
| No. of device points > File register (R) > Standard RAM | 32768 points (R0...32767) (Maximum 65536 points are available by switching blocks.) |
| SRAM card (1M byte) | 32768 points (R0...32767) (Maximum 517120 points are available by switching blocks.) |
| SRAM card (2M bytes) | 32768 points (R0...32767) (Maximum 1041408 points are available by switching blocks.) |
| Flash card (2M bytes) | 32768 points (R0...32767) (Maximum 1041408 points are available by switching blocks.) |
| Flash card (4M bytes) | 32768 points (R0...32767) (Maximum 1042432 points are available by switching blocks.) |
| No. of device points > File register (ZR) > Standard RAM | 65536 points (ZR0...65535) (Blocks do not need to be switched.) |
| No. of device points > File register (ZR) > SRAM card (1M byte) | 517120 points (ZR0...517119) (Blocks do not need to be switched.) |
| No. of device points > File register (ZR) > SRAM card (2M bytes) | 1041408 points (ZR0...1041407) (Blocks do not need to be switched.) |
| No. of device points > File register (ZR) > Flash card (2M bytes) | 1041408 points (ZR0...1041407) (Blocks do not need to be switched.) |
| No. of device points > File register (ZR) > Flash card (4M bytes) | 1042432 points (ZR0...1042431) (Blocks do not need to be switched.) |
| Link special relay (SB) | 2048 points (SB0...7FF) (The number of device points is fixed.) |
| Link special register (SW) | 2048 points (SW0...7FF) (The number of device points is fixed.) |
| Step relay (S) | 8192 points (S0...8191) (The number of device points is fixed.) |
| Index register (Z) | 16 points (Z0...15) (The number of device points is fixed.) |
| Pointer (P) | 4096 points (P0...4095) (The number of device points is fixed.) (The local pointer range and the common pointer range can be set by parameter.) |
| Interrupt pointer (I) | 256 points (I0...255) (The number of device points is fixed.) (The fixed scan interval for the system interrupt pointer I28 to 31 can be set by parameter.) 0.5...1000.0 ms (in increments of 0.5 ms) Default I28: 100 ms, I29: 40 ms, I30: 20 ms, I31: 10 ms |
| Special relay (SM) | 2048 points (SM0...2047) (The number of device points is fixed.) |
| Special register (SD) | 2048 points (SD0...2047) (The number of device points is fixed.) |
| Function input (FX) | 16 points (FX0...F) (The number of device points is fixed.) |
| Function output (FY) | 16 points (FY0...F) (The number of device points is fixed.) |
| Function register (FD) | 5 points (FD0...4) (The number of device points is fixed.) |
| Link direct device | Device that directly accesses the link device of a network module Specification format: J□□\X□□, J□□\Y□□, J□□\SB□□, J□□\W□□, J□□\SW□□ |
| Intelligent function module device | Device that directly accesses the buffer memory of an intelligent function module Specified form: U...\G... |
| Latch (data retention during power failure) range | 8192 points (L0...8191) by default (The latch range can be set for the devices, B, F, V, T, ST, C, D, and W.) |
| RUN/PAUSE contact | One contact can be set up in X0 to X1FFF for each of RUN and PAUSE. |
| Clock function | Year, month, date, hour, minute, second, and day of week (automatic leap year detection) Accuracy: -3.18...+5.25 s (TYP. +2.12 s)/d at 0 ˚C Accuracy: -3.93...+5.25 s (TYP. +1.90 s)/d at 25 ˚C Accuracy: -14.69...+3.53 s (TYP. -3.67 s)/d at 55 ˚C |
| Allowable momentary power failure time | The time differs depending on the power supply module used. |
| Internal current consumption (5 V DC) | 0.64 A |
| Height | 98 mm |
| Width | 27.4 mm |
| Depth | 89.3 mm |
| Масса | 0.20 kg |
| Рабочая температура | 0...55 ˚C |
| Storage ambient temperature | -25...75 ˚C |
| Operating ambient humidity | 5...95 %RH, non-condensing |
| Storage ambient humidity | 5...95 %RH, non-condensing |
| Under intermittent vibration | Frequency: 5...8.4 Hz, Half amplitude: 3.5 mm Frequency: 8.4...150 Hz, Constant acceleration: 9.8 m/s 2 Sweep count: 10 times each in X, Y, Z directions |
| Under continuous vibration | Frequency: 5...8.4 Hz, Half amplitude: 1.75 mm Frequency: 8.4...150 Hz, Constant acceleration: 4.9 m/s 2 |
| Shock resistance | Compliant with JIS B 3502 and IEC 61131-2 (147 m/s 2 , 3 times each in 3 directions X, Y, Z) |
| Operating atmosphere | No corrosive gases |
| Operating altitude | 0...2000 m |
| Installation location | Inside a control panel |
| Напряжение питания | II or less |
| Pollution degree | 2 or less |
| Equipment class | Class I |
| Category (site listing) | Process CPU |