Технические характеристики

Control methodStored program cyclic operation
I/O control modeRefresh mode (The direct access input/output is available by specifying the direct access input/output (DX, DY).)
Sequence control languageRelay symbol language, logic symbolic language, MELSAP3 (SFC), MELSAP-L, function block and structured text (ST)
Process control languageFBD for process control
LD X034 ns
MOV D0 D1102 ns
Tracking execution time (increased scantime)Device memory 48k words: 10ms Device memory 100k words: 15ms
Constant scan0.5...2000 ms (setting is available in increments of 0.5 ms by parameter)
Program capacity252K steps (1008K bytes)
Program memory (drive 0)1008K bytes
Memory card (RAM) (drive 1)Size of the installed memory card (2M bytes max.)
Memory card (ROM) (drive 2)Size of the installed memory card (Flash card: 4M bytes max., ATA card: 32M bytes max.)
Standard RAM (drive 3)256K bytes
Standard ROM (drive 4)1008K bytes
Program memory252
Memory card (RAM)287 (when the Q2MEM-2MBS is used)
Flash card288
ATA card512
Standard RAM3
Standard ROM252
Initial setting512 parameters
Refresh256 parameters
Number of I/O device points8192 points (X/Y0...1FFF)
Number of I/O points4096 points (X/Y0...FFF)
Internal relay (M)8192 points (M0...8191) by default (changeable)
Latch relay (L)8192 points (L0...8191) by default (changeable)
Link relay (B)8192 points (B0...1FFF) by default (changeable)
Timer (T)2048 points (T0...2047) by default (changeable) (Low-speed and high-speed timers available) Low-speed or high-speed is specified by an instruction. The measurement unit is set by parameter. (Low-speed timer: 1...1000 ms (in increments of 1 ms), default: 100 ms) (High-speed timer: 0.1...100.0 ms (in increments of 0.1 ms), default: 10.0 ms)
Retentive timer (ST)0 points by default (changeable) (Low-speed and high-speed retentive timers available) Low-speed or high-speed is specified by an instruction. The measurement unit is set by parameter. (Low-speed retentive timer: 1...1000 ms (in increments of 1 ms), default: 100 ms) (High-speed retentive timer: 0.1...100.0 ms (in increments of 0.1 ms), default: 10.0 ms)
Counter (C)Normal counter: 1024 points (C0...1023) by default (changeable) Interrupt counter: 256 points max. (0 points by default, setting by parameters)
Data register (D)12288 points (D0...12287) by default (changeable)
Link register (W)8192 points (W0...1FFF) by default (changeable)
Annunciator (F)2048 points (F0...2047) by default (changeable)
Edge relay (V)2048 points (V0...2047) by default (changeable)
No. of device points > File register (R) > Standard RAM32768 points (R0...32767) (Maximum 131072 points are available by switching blocks.)
SRAM card (1M byte)32768 points (R0...32767) (Maximum 517120 points are available by switching blocks.)
SRAM card (2M bytes)32768 points (R0...32767) (Maximum 1041408 points are available by switching blocks.)
Flash card (2M bytes)32768 points (R0...32767) (Maximum 1041408 points are available by switching blocks.)
Flash card (4M bytes)32768 points (R0...32767) (Maximum 1042432 points are available by switching blocks.)
No. of device points > File register (ZR) > Standard RAM131072 points (ZR0...131071) (Blocks do not need to be switched.)
No. of device points > File register (ZR) > SRAM card (1M byte)517120 points (ZR0...517119) (Blocks do not need to be switched.)
No. of device points > File register (ZR) > SRAM card (2M bytes)1041408 points (ZR0...1041407) (Blocks do not need to be switched.)
No. of device points > File register (ZR) > Flash card (2M bytes)1041408 points (ZR0...1041407) (Blocks do not need to be switched.)
No. of device points > File register (ZR) > Flash card (4M bytes)1042432 points (ZR0...1042431) (Blocks do not need to be switched.)
Link special relay (SB)2048 points (SB0...7FF) (The number of device points is fixed.)
Link special register (SW)2048 points (SW0...7FF) (The number of device points is fixed.)
Step relay (S)8192 points (S0...8191) (The number of device points is fixed.)
Index register (Z)16 points (Z0...15) (The number of device points is fixed.)
Pointer (P)4096 points (P0...4095) (The number of device points is fixed.) (The local pointer range and the common pointer range can be set by parameter.)
Interrupt pointer (I)256 points (I0...255) (The number of device points is fixed.) (The fixed scan interval for the system interrupt pointer I28 to 31 can be set by parameter.) 0.5...1000.0 ms (in increments of 0.5 ms) Default I28: 100 ms, I29: 40 ms, I30: 20 ms, I31: 10 ms
Special relay (SM)2048 points (SM0...2047) (The number of device points is fixed.)
Special register (SD)2048 points (SD0...2047) (The number of device points is fixed.)
Function input (FX)16 points (FX0...F) (The number of device points is fixed.)
Function output (FY)16 points (FY0...F) (The number of device points is fixed.)
Function register (FD)5 points (FD0...4) (The number of device points is fixed.)
No. of device tracking wordsMaximum 100 k words
Link direct deviceDevice that directly accesses the link device of a network module Specification format: J□□\X□□, J□□\Y□□, J□□\SB□□, J□□\W□□, J□□\SW□□
Intelligent function module deviceDevice that directly accesses the buffer memory of an intelligent function module Specified form: U...\G...
Latch (data retention during power failure) range8192 points (L0...8191) by default (The latch range can be set for the devices, B, F, V, T, ST, C, D, and W.)
RUN/PAUSE contactOne contact can be set up in X0 to X1FFF for each of RUN and PAUSE.
Clock functionYear, month, date, hour, minute, second, and day of week (automatic leap year detection) Accuracy: -3.20...+5.27 s (TYP. +2.07 s)/d at 0 ˚C Accuracy: -2.77...+5.27 s (TYP. +2.22 s)/d at 25 ˚C Accuracy: -12.14...+3.65 s (TYP. -2.89 s)/d at 55 ˚C
Allowable momentary power failure timeThe time differs depending on the power supply module used.
Internal current consumption (5 V DC)0.89 A
Height98 mm
Width55.2 mm
Depth89.3 mm
Масса0.30 kg
Рабочая температура0...55 ˚C
Storage ambient temperature-25...75 ˚C
Operating ambient humidity5...95 %RH, non-condensing
Storage ambient humidity5...95 %RH, non-condensing
Under intermittent vibrationFrequency: 5...8.4 Hz, Half amplitude: 3.5 mm Frequency: 8.4...150 Hz, Constant acceleration: 9.8 m/s 2 Sweep count: 10 times each in X, Y, Z directions
Under continuous vibrationFrequency: 5...8.4 Hz, Half amplitude: 1.75 mm Frequency: 8.4...150 Hz, Constant acceleration: 4.9 m/s 2
Shock resistanceCompliant with JIS B 3502 and IEC 61131-2 (147 m/s 2 , 3 times each in 3 directions X, Y, Z)
Operating atmosphereNo corrosive gases
Operating altitude0...2000 m
Installation locationInside a control panel
Напряжение питанияII or less
Pollution degree2 or less
Equipment classClass I
Category (site listing)Redundant CPU