R32PCPU

Mitsubishi Electric Corporation (Factory Automation / FA Systems Group) R32PCPU

R32PCPU

Технические характеристики

Operation control methodStored program cyclic operation
I/O control modeRefresh mode (The direct access input/output is available by specifying the direct access input/output (DX, DY).)
LD instruction0.98 ns
MOV instruction1.96 ns
IF1.96 ns
CASE1.96 ns
FOR1.96 ns
Program capacity320K steps (1280K bytes)
Program memory1280K bytes
SD memory cardDiffers depending on the SD memory card used. (SD/SDHC memory card: 32G bytes maximum)
Device/label memory2316K bytes
Area for programs40K bytes
Area for function blocks256K bytes
Data memory20M bytes
CPU buffer memory1072K bytes (536K words) (including the fixed scan communication area (24K words))
Refresh memory2048K bytes
Maximum number of storable files > Program memory252
Device/label memory (file storage area)324 (with or without an extended SRAM cassette)
Maximum number of storable files > Data memory512
Maximum number of storable files > SD memory card• NZ1MEM-2GBSD: 256 • NZ1MEM-4GBSD, NZ1MEM-8GBSD, NZ1MEM-16GBSD: 32767
Number of storable folders > Data memory512
Number of storable folders > SD memory card• NZ1MEM-2GBSD: 256 • NZ1MEM-4GBSD, NZ1MEM-8GBSD, NZ1MEM-16GBSD: 32767
USB portUSB2.0 High Speed (miniB)×1
Ethernet port10BASE-T/100BASE-TX×1
Clock functionYear, month, date, hour, minute, second, and day of week (automatic leap year adjustment) Accuracy: -1.00...+1.00 s/d at 0...55 ˚C
Allowable momentary power failure timeThe time differs depending on the power supply module used.
Internal current consumption (5 V DC)0.76 A
Height106 mm (base unit mounting side: 98 mm)
Width27.8 mm
Depth110 mm
Масса0.20 kg
Programming languageLadder diagram (LD), sequential function chart (SFC), structured text (ST), function block diagram (FBD/LD)
Programming supporting functionFunction block (FB), label programming (system/local/global)
Standard programInitial execution type, scan execution type, fixed scan execution type, event execution type, standby type
Program operation > Type of interrupt > Standard programInternal timer interrupt (I28 to I31), high-speed internal timer interrupt 1 (I49), high-speed internal timer interrupt 2 (I48), interrupt by modules, inter-module synchronous interrupt (I44), multiple CPU synchronous interrupt (I45)
General program252
FB file128
Constant scan0.2...2000 ms (in 0.1 ms increments)
Interrupt using the internal timer (I28...I31)0.5...1000 ms (in 0.5 ms increments)
High-speed internal timer interrupt 1 (I49)0.05...1000 ms (in 0.05 ms increments)
High-speed internal timer interrupt 2 (I48)0.05...1000 ms (in 0.05 ms increments)
Inter-module synchronous interrupt (I44)0.1...10.00 ms (in 0.05 ms increments)
Multiple CPU synchronous interrupt (I45)0.1...10.00 ms (in 0.05 ms increments)
Low-speed timer1...1000 ms (Default: 100 ms)
High-speed timer0.01...100 ms (Default: 10 ms)
Long timer0.001...1000 ms (Default: 0.001 ms)
Number of I/O points4096 points
Input (X)12288 points (fixed)
Output (Y)12288 points (fixed)
Internal relay (M)12288 points (user-changeable)
Latch relay (L)8192 points (user-changeable)
Link relay (B)8192 points (user-changeable)
Link special relay (SB)2048 points (user-changeable)
Annunciator (F)2048 points (user-changeable)
Edge relay (V)2048 points (user-changeable)
Step relay (S)0 points (user-changeable)
Timer (T)1024 points (user-changeable)
Long timer (LT)1024 points (user-changeable)
Retentive timer (ST)0 points (user-changeable)
Long retentive timer (LST)0 points (user-changeable)
Counter (C)512 points (user-changeable)
Long counter (LC)512 points (user-changeable)
Data register (D)18432 points (user-changeable)
Link register (W)8192 points (user-changeable)
Link special register (SW)2048 points (user-changeable)
Special relay (SM)4096 points (fixed)
Special register (SD)4096 points (fixed)
Function input (FX)16 points (fixed)
Function output (FY)16 points (fixed)
Function register (FD)5 points × 4 words (fixed)
File register (R/ZR)0 points (user-changeable)
Index register (Z)20 points (user-changeable, up to 24 points)
Long index register (LZ)2 points (user-changeable, up to 12 points)
Pointer (P) (global/local)8192 points (user-changeable, up to 16384 points)
Interrupt pointer (I)1024 points (fixed)
Link input (J☐\X☐)16384 points maximum
Link output (J☐\Y☐)16384 points maximum
Link relay (J☐\B☐)32768 points maximum
Link register (J☐\W☐)131072 points maximum
Link special relay (J☐\SB☐)512 points maximum
Link special register (J☐\SW☐)512 points maximum
Intelligent function module device (U☐\G☐)268435456 points maximum
Buffer memory (U3E☐\G☐)524288 points
Fixed scan communication area in the buffer memory (U3E☐\HG☐)12288 points maximum
Refresh data register (RD)524288 points (1048576 points maximum)
Nesting (N)15 points
SFC block device (BL)320 points
SFC transition device (TR)0 points (Can be used for device comments only)
Data transmission speed100/10 Mbps
Communication mode100BASE-TX: Full-duplex/half-duplex 10BASE-T: Full-duplex/half-duplex
InterfaceRJ45 (AUTO MDI/MDI-X)
Transmission methodBase band
Maximum frame size1518 bytes
Jumbo frameNot available
Maximum segment length100 m (length between hub and node)
IP versionIPv4
Number of simultaneously open connections16 connections (connections usable on a program)
Socket communications5K words × 16
Рабочая температура0...55 ˚C (When an extended temperature range base unit is not used) 0...60 ˚C (When an extended temperature range base unit is used)
Storage ambient temperature-25...75 ˚C
Operating ambient humidity5...95 %RH, non-condensing
Storage ambient humidity5...95 %RH, non-condensing
Under intermittent vibrationFrequency: 5...8.4 Hz, Half amplitude: 3.5 mm Frequency: 8.4...150 Hz, Constant acceleration: 9.8 m/s 2 Sweep count: 10 times each in X, Y, and Z directions
Under continuous vibrationFrequency: 5...8.4 Hz, Half amplitude: 1.75 mm Frequency: 8.4...150 Hz, Constant acceleration: 4.9 m/s 2
IEC 61131-2: 2007/JIS B 3502: 2011Three shocks in each direction per axis, on 3 mutually perpendicular axes (total of 18 shocks)
Operating atmosphereNo corrosive gases, flammable gases, less conductive dust
Operating altitude0...2000 m
Installation locationInside a control panel
Напряжение питанияII or less
Pollution degree2 or less
Category (site listing)Process CPU
Получить предложение по этой позиции