Модули ввода-вывода и промышленные шины
MO

Moxa Inc. 65M-3800H-CT-T

Модуль ввода-вывода Moxa 65M-3800H-CT-T, серия ioPAC 6500 (65M) I/O Modules. Рабочая температура: -40…75 °C. Подбор по артикулу, поставка под заказ: цену и срок уточняйте через запрос на поставку.

Категории:

Технические характеристики

Input/Output Interface / Analog Input Channels8 (HART)
Input/Output Interface / Isolation65M-3600-CT-T/65M-3610-CT-T/65M-4820-CT-T/65M-5801-CT-T: - Between signal and system: 3k VDC - Between groups: 1k VDC per min All other models: - Between signal and system: 3k VDC
Digital Inputs / I/O TypeSink (Internal/external field circuit supply for dry contact)
Digital Inputs / I/O ModeDI or event counter (channels 1 to 8, group configurable by software)
Напряжение питания24 VDC 22.8 to 25.2 VDC
Digital Inputs / Internal Field Circuit Supply Current125 mA (max.) (Only for dry contact)
Напряжение питанияOn: 11 to 30 VDC Off: 0 to 5 VDC
Напряжение питания2.35 mA ± 20% per channel
Digital Inputs / Counter FrequencySquare wave: 0 to 10 kHz
Digital Inputs / Digital Filtering Time IntervalSoftware configurable
Digital Inputs / DiagnosticsInput Wire-break Detection (current: 50 µA max., delay: 20 ms) Internal Field Circuit Supply Detection (17.5 VDC, 16 to 19 VDC)
Digital Outputs / I/O TypeSource
Digital Outputs / I/O ModeDO or pulse output (channel 1 to 8, group configurable by software)
Напряжение питания24 VDC 19.2 to 28.8 VDC
Digital Outputs / Common Power Input Current6.4 A (max.)
Digital Outputs / Load Current200 mA/channel (typ.) 500 mA/channel (max.)
Digital Outputs / Pulse Duration500 μs
Digital Outputs / ProtectionOutput Short-circuit Protection Common Power Input Over-voltage Protection Inductive Load Shutdown Voltage Protection
Digital Outputs / DiagnosticsWire Break Detection (on state, output current < 3 mA) Wire Break Detection (off state, output load impedance > 58 kilo-ohms) Output Short-Circuit Detection (output current > 0.87 A, range: 0.64 to 1.2 A) External Power Detection (17.5 VDC, 16 to 19 VDC) Failsafe Configuration (hold last/failsafe state)
Analog Inputs / I/O Mode65M-3600-CT-T: Current 65M-3610-CT-T: Voltage 65M-3800H-CT-T: HART
Analog Inputs / I/O TypeDifferential
Analog Inputs / Input Range65M-3600-CT-T: 0 to 20 mA 4 to 20 mA 65M-3610-CT-T: 0 to 10 V 1 to 5 V 65M-3800H-CT-T: 4 to 20 mA
Analog Inputs / Overload Permitted on Inputs65M-3600-CT-T: ±30 mA 65M-3610-CT-T: ±12 V 65M-3800H-CT-T: 30 mA
Analog Inputs / Internal Loop Power Supply Current2-wire connection: 500 mA (max.)
Analog Inputs / Converter Resolution16 bits
Analog Inputs / Measurement Resolution65M-3600-CT-T: 2 μA (0 to 20 mA) 1.6 μA (4 to 20 mA) 65M-3610-CT-T: 1 mV (0 to 10 V) 0.4 mV (1 to 5 V) 65M-3800H-CT-T: 1.6 μA (4 to 20 mA)
Analog Inputs / Accuracy±0.1% FSR @ 25°C ±0.3% FSR @ -40 to 75°C
Analog Inputs / Conversion Time100 ms
Analog Inputs / Rejection RatioNormal mode: > 60 dB @ 60 Hz (min.), conversion time: 100 ms Common mode: > 90 dB @ 60 Hz (min.), conversion time: 100 ms
Analog Inputs / Input Impedance65M-3800H-CT-T: 250 ohms 65M-3600-CT-T: 250 ohms 65M-3610-CT-T: 1 mega-ohms
Analog Inputs / Diagnostics65M-3800H-CT-T: Input Wire-break Input Short-circuit Input Underflow/Overflow Detection 65M-3600-CT-T: Internal Loop Power Detection (17.5 VDA, 16 to 19 VDC) Input Short-circuit Detection 65M-3600-CT-T (in 4 to 20 mA mode): Input Wire-break Detection (delay: 0.8 s) 65M-3610-CT-T: Input Wire-break Detection (delay:1.6 s max)
Analog Outputs / I/O ModeVoltage/Current
Analog Outputs / Output Range0 to 10 V 1 to 5 V 0 to 20 mA 4 to 20 mA
Analog Outputs / Converter Resolution16-bit
Analog Outputs / Output Resolution1 mV (0 to 10 V) 0.4 mV (1 to 5 V) 2 μA (0 to 20 mA) 1.6 μA (4 to 20 mA)
Analog Outputs / Accuracy±0.1% FSR @ 25°C ±0.3% FSR @ -40 to 75°C
Analog Outputs / Output Refresh Time16 ms
Analog Outputs / Output ImpedanceVoltage mode: 1 kilo-ohms (min.) Current mode: 750 ohms (max.)
Analog Outputs / DiagnosticsOutput Short-circuit Detection (voltage) Failsafe Configuration (hold last/failsafe state) Output Wire-break Detection (current)
Serial Interface / Serial StandardsRS-232, RS-422, RS-485-2w
Serial Interface / Baudrate300, 600, 1200, 1800, 2400, 4800, 9600, 19200, 38400, 57600, and 115200 bps
Serial Interface / Data Bits7, 8
Serial Interface / Stop Bits1, 2
Serial Interface / ParityNone Even Odd
Serial Interface / Flow ControlRTS/CTS, XON/XOFF
Serial Interface / Serial SignalsRS-232: TxD, RxD, RTS, CTS, GND RS-422: Tx+, Tx-, Rx+, Rx-, GND RS-485-2w: Data+, Data-, GND
Terminal Blocks / ConnectorScrew-fastened terminal block
Terminal Blocks / Dimensions42.3 x 102.38 x 80.8 mm (1.67 x 4.03 x 3.18 in)
Масса164 g (0.36 lb)
Power Consumption / System Power65M-1900-CT-T/65M-2901-CT-T: 0.068 A @ 12 VDC 65M-3610-CT-T/65M-4820-CT-T: 0.069 A @ 12 VDC 65M-3600-CT-T: 0.073 A @ 12 VDC 65M-3800H-CT-T: 0.072 A @ 12 VDC 65M-5801-CT-T: 0.143 @ 12 VDC
Power Consumption / Field Power65M-1900-CT-T: 0.019 A @ 24 VDC (without internal field circuit supply) 0.115 A @ 24 VDC (32-channel dry contact with internal field circuit supply) 65M-2901-CT-T: 0.005 A @ 24 VDC 65M-3600-CT-T: 0.053 A @ 24 VDC (without internal loop power) 0.466 A @ 24 VDC (16-channel 20 mA input with internal loop power) 65M-3610-CT-T: 0.038 A @ 24 VDC 65M-3800H-CT-T: 0.05 A (max.) @ 24 VDC (without internal l
Physical Characteristics / HousingPlastic
Physical Characteristics / Dimensions42 x 116 x 130 mm (1.65 x 4,57 x 5.12 in)
Масса262 g (0.58 lb)
Environmental Limits / Operating Temperature-40 to 75°C (-40 to 167°F) Note: Proper airflow is required in an environment with temperature > 65°C.
Environmental Limits / Storage Temperature (package included)-40 to 85°C (-40 to 185°F)
Environmental Limits / Ambient Relative Humidity5 to 95% (non-condensing)
Environmental Limits / AltitudeUp to 2000 meters Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
СертификацияEN 55032/35 EN 61000-6-2/-6-4
СертификацияCISPR 32, FCC Part 15B Class A
СертификацияIEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m IEC 61000-4-4 EFT: Power: (DC) 1 kV; Signal: 1 kV IEC 61000-4-5 Surge: Power: (DC) 0.5 kV L-N, 1 kV L/N-PE; Signal: 1 kV; IO: 0.5 kV IEC 61000-4-6 CS: Power: (DC) 10 V; Signal: 10 Vrms IEC 61000-4-8 PFMF: 30 A/m
СертификацияUL 61010-1 UL 61010-2-201
СертификацияIEC 60068-2-27 Half sine wave; acceleration: 15 g; time: 11 ms
СертификацияIEC 60068-2-6 DIN-rail mounted: 7 mm peak-peak (p-p) (2 to 8.42 Hz), 1 g (8.42 to 150 Hz) Rack mounted (with optional kit): 7 mm peak-peak (p-p) (2 to 8.42 Hz), 0.5 g (8.42 to 150 Hz)
MTBF / Time1,016,573 hrs
MTBF / StandardsTelcordia Standard SR-332
Warranty / Warranty Period5 years
Warranty / DetailsSee www.moxa.com/warranty
Получить предложение по этой позиции