Pepperl+Fuchs SE NCN4-V3-N0-0,8M
Inductive sensor
Категории:
Технические характеристики
| Switching function | Normally closed (NC) |
|---|---|
| Output type | NAMUR |
| Rated operating distance | 4 mm |
| Installation | non-flush |
| Assured operating distance | 0 ... 3.24 mm |
| Reduction factor rAl | 0.3 |
| Reduction factor rCu | 0.2 |
| Reduction factor r304 | 0.7 |
| Напряжение питания | 8.2 V (Riapprox. 1 kΩ) |
| Switching frequency | 0 ... 2000 Hz |
| Hysteresis | typ. 5 % |
| Current consumption - Measuring plate not detected | ≥ 3 mA |
| Current consumption - Measuring plate detected | ≤ 1 mA |
| Switching state indicator | LED, yellow |
| MTTFd | 1735 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Standard conformity - NAMUR | EN 60947-5-6:2000IEC 60947-5-6:1999 |
| Standard conformity - Electromagnetic compatibility | NE 21:2007 |
| Standard conformity - Standards | EN IEC 60947-5-2 |
| IECEx approval - Equipment protection level Ga | IECEx PTB 11.0021X |
| IECEx approval - Equipment protection level Gb | IECEx PTB 11.0021X |
| IECEx approval - Equipment protection level Da | IECEx PTB 11.0021X |
| IECEx approval - Equipment protection level Mb | IECEx PTB 11.0021X |
| ATEX approval - Equipment protection level Ga | PTB 00 ATEX 2032 X |
| ATEX approval - Equipment protection level Gb | PTB 00 ATEX 2032 X |
| ATEX approval - Equipment protection level Da | PTB 00 ATEX 2032 X |
| UL approval | cULus ListedLoad Type: ResistiveCircuitry: Class 2 Power SourceEnclosure Type Rating: Type 1Supply/Switching Voltage: 8.2 V DC |
| ATEX approval - Ordinary Location | E87056 |
| ATEX approval - Hazardous Location | E501628 |
| ATEX approval - Control drawing | 116-0451 |
| CML approval | on request |
| ANZEx | 19.3001X |
| Рабочая температура | -25 ... 100 °C (-13 ... 212 °F) |
| Connection type | cable |
| Материал | PBT |
| Sensing face | PBT |
| Degree of protection | IP67 |
| Cable - Cable diameter | 2.6 mm ± 0.2 mm |
| Cable - Bending radius | > 10 x cable diameter |
| Материал | PVC |
| Cable - Core cross section | 0.14 mm2 |
| Cable - Length | 0.8 m |
| Tightening torque, fastening screws | ≤ 0.4 Nm |
| Dimensions - Height | 10.2 mm |
| Dimensions - Width | 27.8 mm |
| Dimensions - Length | 16 mm |
| Use in the hazardous area | see instruction manuals |