1420-V2A-485

Rockwell Automation, Inc. 1420-V2A-485

Powermonitor 500 Serial Power Meter

Технические характеристики

Build America, Buy AmericaNo
Repair Options AvailableNo
General Features – AccuracyVoltage, nominal: 400V AC LN, 600V AC LL @ 25 °C ±5 °C, R.H. ≤ 60% @ 48...62Hz
General Features – Alarmtrue
General Features – CommunicationsRS-485
General Features – Frequency Rating45-65Hz
General Features – InterfaceBuilt-in LCD
General Features – Output2 Digital Relays
Communication / Interfaces – Addresses247, selectable by using the front key-pad or through the software
Power / Electrical Characteristics – Ampere metertrue
Inputs / Outputs Io – Analog output (0 to 20 mA)true
General Features – An optional pair of 0 to 20 mA analog outputstrue
Measurement / Parameters – Apparent power consumption (kVAh)true
Measurement / Parameters – Apparent power (kVA)true
Power / Electrical Characteristics – Blind power metertrue
Environmental Operating Conditions – BurstOn current and voltage measuring inputs circuit: 4 kV
Standard Compliance – Cable cross-section area2.5 mm2 AWG) max, Screw tightening torque: 0.4 N•m min/0.8 N•m max, Suggested screw tightening torque: 0.5 N•m
General Features – Class• Class 1 (kWh) according to EN62053-21, • Class B (kWh) according to EN50470-3, • Class 2 (kVARh) according to EN62053-23
General Features – Configurable alarmstrue
General Features – Configurable via software tooltrue
General Features – configurable virtual alarmsUp to four
Inputs / Outputs Io – ConfigurationBy using the front keypad
Standard Compliance – ConnectionsScrew-type
Inputoutput Specifications – Control powerRange: 100 to 240V AC (48 to 62 Hz)
Inputoutput Specifications – Coupling typeWith CTs
Measurement / Parameters – Crest factor≤3 (15 A max peak)
General Specifications – Current all modelsFrom 0.01 to 0.25 A: ±(1.0% of reading (RDG) + 2 digits From 0.25 to 6 A: ±(0.5% RDG +2 digits)
Measurement / Parameters – Currenttrue
Inputoutput Specifications – Current overloads6 A, at 50/60 Hz, Continuous
Inputoutput Specifications – Current range (by CT)5 A nominal (6 A maximum)
Inputs / Outputs Io – Current sensingNominal: 5 A
General Specifications – Current sensing modelInominal: 5 A, Imaximum: 6A
Inputoutput Specifications – Current typeGalvanic insulation with built-in CTs
Communication / Interfaces – Data communication rateSelectable: 9.6, 19.2, 38.4, 115.2 Kbps
Communication / Interfaces – Data dynamic (reading only)System and phase variables
Communication / Interfaces – Data formatOne start bit, eight data bit, no/even/odd parity, 1 stop bit
Communication / Interfaces – Data static (reading and writing only)All configuration param
Measurement / Parameters – Demand (kVA)true
Measurement / Parameters – Demand (kVAR)true
Measurement / Parameters – Demand (kW)true
Measurement / Parameters – Demand power factortrue
Housing Din – Depth behind panelMaximum @ 81.7 mm (3.2 in.)
Environmental Operating Conditions – Dielectric strength4 kV AC rms for 1 min
Housing Din – Dimensions (WxHxD)Module holder: 96 x 96 x 50 mm (3.78 x 3.78 x 1.97 in.), Digital and analog output type modules: 89.5 x 63 x 16 mm (3.52 x 2.48 x 0.63 in.), Serial and Ethernet Communication type modules: 89.5 x 63 x 20 mm (3.52 x 2.48 x 0.79 in.)
Communication / Interfaces – Driver input capability1/5 unit load. Max 160 transceivers on the same bus
Power / Electrical Characteristics – Effective power measurement devicetrue
Environmental Operating Conditions – Electrostatic discharge15 kV air discharge
Environmental Operating Conditions – EMCAccording to EN62052-11
Inputoutput Specifications – Energy additional errorsAccording to EN62053-21 ANSI C12.1, influence quantities Class B according to EN50470-3, EN62053-23
General Features – Energy measurements (imported/exported)kWh and kVARh
General Features – Energy value displayTen digits and the plus/minus sign
Measurement / Parameters – FrequencyHz: Yes
Power / Electrical Characteristics – Frequency metertrue
General Features – Front protection degreeIP65, NEMA 4X, NEMA 12
General Features – HeightFront dimensions: 96 mm
Environmental Operating Conditions – Immunity to conducted disturbances10V/m from 150 KHz to 80 MHz
Environmental Operating Conditions – Immunity to radiated electromagnetic fieldsTest without any current: 30V/m from 80 to 2000 MHz
Inputoutput Specifications – Input impedance5(6)A, < 0.2VA
Environmental Operating Conditions – Installation categoryCat. III (IEC60664, EN60664)
General Specifications – Line-line RMSMaximum @ 277 to 830V AC
Напряжение питанияIn the range Vnom: ±(1.0% RDG +1 digit)
General Specifications – Line-neutral RMSMaximum @ 160 to 480V AC
Напряжение питанияIn the range Vnom: ±(0.5% RDG +1 digit)
Inputs / Outputs Io – Load≤ 600 Ω
МатериалABS, self-extinguishing: UL 94 V-0
General Features – Metering values displayFour rows with 4 digits
Inputoutput Specifications – MethodTrue RMS measurements of distorted wave forms
Housing Din – MountingPanel mounting
Environmental Operating Conditions – Noise rejection CMRR100 dB, 48 to 62 Hz
Inputs / Outputs Io – Number of outputs2
Environmental Operating Conditions – Operating temperature-25 to +40 °C (-13 to +104 °F) (R.H. from 0…90% noncondensing @ 40 °C) according to EN62053-21, EN50470-1 and EN62053- 23
General Features – Optional serial RS-232/RS-485 communication supporting Modbus RTUtrue
Housing Din – Pollution degree2
Measurement / Parameters – Power factorPF: Yes
Communication / Interfaces – ProtocolModbus RTU
Power / Electrical Characteristics – Pulse countertrue
Environmental Operating Conditions – Radio frequency suppressionAccording to CISPR 22
Inputs / Outputs Io – RangeMaximum @ 0 to 20 mA
Inputoutput Specifications – Rated inputsSystem type: 1, 2, or 3-phase
Measurement / Parameters – Reactive energy (kVARh)Class 2 according to EN62053-23, ANSI C12.1
Measurement / Parameters – Reactive power consumption (kVARh)true
Measurement / Parameters – Reactive power (kVAR)true
General Specifications – Real and apparent powerFrom 0.05 to 0.25 A, PF 1: ±(2% RDG +1 digit) From 0.25 to 6A, PF 0.5L, PF1, PF 0.8C: ±(1.0% RDG+1 digit)
Measurement / Parameters – Real energy (kWh)Class 1 according to EN62053-21, ANSI C12.1 Class B according to EN50470-3
Measurement / Parameters – Real power consumption (kWh)true
Measurement / Parameters – Real power (kW)true
General Features – Real-time clock functiontrue
Время отклика≤ 400 ms typical (filter excluded)
General Features – Revenue grade energy measurementsPer ANSI C12.1 Class 1.0, ANSI C12.1
Inputs / Outputs Io – Ripple≤ 1% (according to IEC 60688-1, EN 60688-1)
Communication / Interfaces – RS-485 (Modbus RTU)true
Communication / Interfaces – RS-485 typeMultidrop, bidirectional (static and dynamic variables)
General Features – Run hours counter8+2 digits
Inputoutput Specifications – Sampling rate3840 sAles/s at 60 Hz, 3200 sAles/s at 50 Hz
Inputs / Outputs Io – Scaling factorProgmable within the whole range of retransmission, it allows the retransmission management of all values from 0 to 20 mA DC
Housing Din – Screw terminalsIP20
Inputs / Outputs Io – Signal retransmissionThe signal output can be connected to any instantaneous variable
General Features – Single phase variablesV(L-L), V(L-N), A(L), An (calculated), VA, W, VAR, power factor
General Specifications – Start up current5
Environmental Operating Conditions – Storage temperature-30 to +70 °C (-22 to +158 °F) (R.H.P178 < 90% noncondensing @ 40 °C) according to EN62053-21, EN50470-1 and EN62053- 23
Environmental Operating Conditions – SurgeOn current and voltage measuring inputs circuit: 4 kV, on ‘L’ auxiliary power supply input: 1 kV
General Features – System and single phase average and maximum variablestrue
Inputoutput Specifications – Temperature drift≤ 200 ppm/°C
General Features – Three-phase (system) variablesV(L-L), V(L-N), A, VA, W, VAR, power factor, frequency
Inputs / Outputs Io – Total temperature drift≤ 500 ppm/°C
General Features – Universal power supply120/240V AC 50/60 Hz or 120/240V DC
Напряжение питания400/600V LL
Напряжение питанияtrue
Напряжение питания2 × Vnom (where Vnom is the nominal voltage of the module), for 500 ms
Напряжение питанияtrue
Напряжение питанияNominal: 400V AC LN, 600V AC LL Range: 160 to 480V AC LN RMS, 277 to 830V AC LL RMS
Power / Electrical Characteristics – Voltmetertrue
МассаApprox 400 g (0.88 lb) (packing included)
General Features – WidthFront dimensions: 96 mm
Получить предложение по этой позиции