1426-M5E-CNT

Rockwell Automation, Inc. 1426-M5E-CNT

Powermonitor 5000 Base Quality Meter

Технические характеристики

Build America, Buy AmericaNo
Repair Options AvailableNo
General Features – Accuracy0.20%
General Features – Alarmtrue
General Features – ApplicationPower Management/Quality m
General Features – CommunicationsControlNet and EtherNet/IP
General Features – Frequency Rating40-75Hz
General Features – InterfaceWebpage
Напряжение питания600VLL AC
General Features – Output4 Digital Relays
Data Handling – Alarm logtrue
Environmental Operating Conditions – Altitude2000 m, max
Power / Electrical Characteristics – Ampere metertrue
Measurement / Parameters – Apparent energy (kVAh)true
Measurement / Parameters – Apparent power demand (kVA)true
Measurement / Parameters – Apparent power (kVA)true
Power / Electrical Characteristics – Blind power metertrue
Relays / Control Outputs – Break values(Inductive load) 3A @ 120V AC, 50/60 Hz, RMS, maximum
General Features – CIP energy objecttrue
General Features – Configurable via webpagetrue
General Features – Configuration lock switchWhen enabled, this switch helps prevent changes in configuration that can affect revenue accuracy.
Communication / Interfaces – ControlNettrue
General Features – Control power and ground wiring terminals• 120...240V AC @ 50/60Hz, or 120...240V DC • 24V DC
Inputoutput Specifications – Control power12VA @ 24V DC
Inputs / Outputs Io – Control relayANSI C37.90 trip duty: 2005
Напряжение питания22.8...25.2V DC @ 24V DC
Напряжение питания85...264V AC, 47…63 Hz Or 106…275V DC
Measurement / Parameters – Crest factorV-V, V-N, and I, per phase: Yes
Measurement / Parameters – Current consumptiontrue
Measurement / Parameters – Current per phase and totaltrue
Inputoutput Specifications – Current sense inputs: I1, I2, I3Accuracy: ±0.1% @ 25°C 50/60 Hz unity power factor
Inputs / Outputs Io – Current sense inputs: I1, I2, I3, I4Starting current : 5 mA
General Features – Current sensing wiring terminalsNominal input current 5 A, Use current transformers (CTs) to connect to power system
Measurement / Parameters – Current unbalancetrue
Data Handling – Data logtrue
Measurement / Parameters – Demand, ampstrue
General Features – Demand functions• ANSI C12.20 -2010 class 0.2 clause 5.5.4 • EN 62053-22 -2003 class 0.2 accuracy clause 8
Measurement / Parameters – Demand power factortrue
Dimension – Depth178 mm
Power / Electrical Characteristics – DescriptionPowerMonitor 5000 M5 unit with native ethernet and optional controlnet network communication
General Features – Device status indicators• Device status - OFF: No control power - Flashing GREEN/RED: Self-test - Flashing GREEN: Power monitor has not been configured - GREEN: Power monitor is running - Flashing RED: Power monitor has detected a recoverable minor fault - RED: Power monitor has detected a non-recoverable major fault
Environmental Operating Conditions – Dielectric withstandUL61010, EN61010
Measurement / Parameters – Displacement power factor per phase and totaltrue
Power / Electrical Characteristics – Effective power measurement devicetrue
General Features – Energy functions• ANSI C12.20 -2010 class 0.2 clause 5.5.4 • EN 62053-22 -2003 class 0.2 accuracy clause 8
Data Handling – Energy logtrue
Communication / Interfaces – EtherNet/IPtrue
General Features – Ethernet network port - standard RJ45 jack with status indicatorsEthernet port hardware is included on all models. these protocols and functions are supported: • EtherNet/IP™ network • HTML web page for configuration and data access ethernet indicators • LNK indicator - Solid GREEN: IP link established - Off: No link established • ACT indicator - Flashing YELLOW: Data present on ethernet port - Off: no data activity present
Data Handling – Event logtrue
Measurement / Parameters – FrequencyNominal: 60 Hz
Power / Electrical Characteristics – Frequency metertrue
General Features – Height132 mm
Environmental Operating Conditions – Humidity5...95% noncondensing
Relays / Control Outputs – IC rating classUL 508, CSA 22.2 @ DC: Q300
General Features – IEEE 1588 precision time protocoltrue
Environmental Operating Conditions – Installation locationIndoor use only
General Features – K-factortrue
Inputs / Outputs Io – KYZ outputSolid-state KYZ: 80mA @ 240V AC/V DC
Data Handling – Load factor logtrue
Relays / Control Outputs – Load switching100mA @ 5V AC, 50/60 Hz, RMS, minimum
Relays / Control Outputs – Make values(Inductive load) 30A @ 120V AC, 50/60 Hz, RMS, maximum
General Features – Metering update ratesOne update per line cycle, 1024 sAles per cycle per channel
Data Handling – Minimum/maximum logtrue
Relays / Control Outputs – Motor load switching1/3HP @ 125V AC, 50/60 Hz, RMS, maximum
General Features – Network demand synchronizationtrue
General Features – Network status indicators• Network status (Native Ethernet port) - OFF: No control power - Flashing GREEN/RED: Self-test - Flashing GREEN: No CIP connection - Solid GREEN: CIP connection established - Flashing RED: CIP connection timed out - Solid RED: Duplicate IP address detected
General Features – Network time synchronizationtrue
Environmental Operating Conditions – Operating temperature-20 to 70 °C
General Features – Optional communication portDeviceNet and ControlNet networks • Module status - OFF: No control power - Flashing GREEN/RED: Self-test - Flashing GREEN: Power monitor has not been configured - GREEN: Power monitor is running - Flashing RED: Power monitor has detected a recoverable minor fault - RED: Power monitor has detected a non-recoverable major fault • Network status - OFF: No control power - Flashing GREEN/RED: Self-test - Flashing GREEN: No CIP connection - Solid GREEN: CIP connection established - Flashing RED: CIP connection timed out - Solid RED: Duplicate address detected
General Features – Power•Power status - OFF: no control power - GREEN: control power is present
General Features – Power functions• ANSI C12.20 -2010 class 0.2 clause 5.5.4 • EN 62053-22 -2003 class 0.2 accuracy clause 8
Measurement / Parameters – Projected amps demandtrue
Measurement / Parameters – Projected kVA demandtrue
Measurement / Parameters – Projected kVAR demandtrue
Measurement / Parameters – Projected kW demandtrue
Power / Electrical Characteristics – Pulse countertrue
General Features – Pulse (digital) output (relay and KYZ)true
Measurement / Parameters – Reactive energy (kVARh)true
Measurement / Parameters – Reactive power demand (kVAR)true
Measurement / Parameters – Reactive power (kVAR)true
Measurement / Parameters – Real energy (kWh)true
Measurement / Parameters – Real power demand (kW)true
Measurement / Parameters – Real power (kW)true
Relays / Control Outputs – Resistive load switching10A @ 24V DC, maximum
General Features – Revenue accuracytrue
General Features – Sag and swell detectiontrue
General Features – Securitytrue
Data Handling – Setpoint logtrue
General Features – Setpoint programmingtrue
Environmental Operating Conditions – Shock50 G, nonoperating
General Features – Status input, KYZ output, and control relay wiring terminals• Four internally powered (24V DC) status inputs • Status input 2 can be used for demand period synchronization • KYZ DPDT solid-state relay for signaling use • Three DPDT control relays
General Features – Status inputstrue
Environmental Operating Conditions – Storage temperature-40 to 85 °C
Measurement / Parameters – Symmetrical component analysistrue
Data Handling – Time of use logtrue
General Features – Total harmonic distortion (THD)true
Measurement / Parameters – True power factor per phase and totaltrue
General Features – USB device portThe USB device port is a USB Mini-B receptacle that accepts standard USB Mini-B plugs, for connection to a host device, such as a notebook computer.
General Features – USB host portUSB standard A receptacle. Not used in this model.
General Features – VGConnect to power system earth ground only, This connection is a functional ground.
Environmental Operating Conditions – Vibration2 G
General Features – Virtual wiring correctiontrue
General Features – Virtual wiring correction indicatorIndicates that a virtual wiring correction command has been applied to resolve wiring errors without rewiring
Напряжение питанияtrue
Напряжение питанияInput impedance: 5M Ω minimum
Напряжение питания• Direct connect to up to 690V AC 3-phase line to line • Maximum nominal line to ground voltage 690 • Use potential transformers (PTs) for higher voltages • Neutral voltage and ground voltage connections
Напряжение питанияtrue
Power / Electrical Characteristics – Voltmetertrue
General Features – Web pagetrue
General Features – Width185 mm
General Features – Wiring diagnosticstrue
Получить предложение по этой позиции