Rockwell Automation, Inc. 191E-ANEJ3-CB25B
1.6-2.5 A Economy Rev Starter W/Ckt-Bkr
Технические характеристики
| Build America, Buy America | No |
|---|---|
| Repair Options Available | No |
| Power / Electrical Characteristics – Circuit breaker auxiliary and trip contacts for 140M | Internal 140M auxiliary contact 1 NO |
| Construction – Circuit breaker frame size | 140M-C2E, high break |
| Напряжение питания | 24V DC with electronic coil |
| Power / Electrical Characteristics – Contactor size | 100-C09 |
| Contruction – Depth | 83.5 mm |
| Power / Electrical Characteristics – Fuse or circuit breaker per NEC, max | 450 A @ D-frame with 100-C/104-C contactors |
| Contruction – Height | 178 mm |
| Power / Electrical Characteristics – Hp ratings as a UL508/CSA motor controller in group motor installations | 3/4…1.5Hp @ 460V AC, 60 Hz (with D-frame, 100-C/104-C contactors) |
| Power / Electrical Characteristics – Hp ratings as a UL508/CSA self-protected Type E combination motor controller | 3/4…1.5Hp @ 460V AC, 60 Hz (with D-frame, 100-C/104-C contactors) |
| Power / Electrical Characteristics – Hp ratings as a UL508/CSA Type F combination motor controller | 3/4…2Hp @ 575V AC, 60 Hz (with C-frame, 100-K/104-K mini contactors) |
| Power / Electrical Characteristics – kW ratings as a IEC for standard motor, 1500 rpm, max | 1.8 kW @ 690V AC @ 50Hz D-frame with bulletin 100-C/104-C contactors |
| Power / Electrical Characteristics – Modifications, accessories | 140M auxiliary contact, side mount, 2 NC |
| Power / Electrical Characteristics – Number of auxiliary contacts as normally closed contact | 1 |
| Power / Electrical Characteristics – Number of auxiliary contacts as normally open contact | 1 |
| Power / Electrical Characteristics – Overload release current setting | 1.6 A |
| Mechanical – Rail mounting possible | true |
| Напряжение питания | 24 V |
| Power / Electrical Characteristics – Short-circuit current as a IEC (Type 1 coordination), max | 8kA @ 690V AC, C-frame with bulletin 100-K/104-K mini contactors |
| Power / Electrical Characteristics – Short-circuit current as a IEC (Type 2 coordination), max | 8kA @ 690V AC, C-frame with bulletin 100-C/104-C contactors |
| Power / Electrical Characteristics – Short-circuit current as a UL508/CSA motor controller in group motor installations (Type 1 coordination), max | 65kA @ 480V AC, D-frame with 100-C/104-C contactors |
| Power / Electrical Characteristics – Short-circuit current as a UL508/CSA motor controller in group motor installations (Type 2 coordination), max | 65kA @ 480V AC, D-frame with 100-C/104-C contactors |
| Power / Electrical Characteristics – Short-circuit current as a UL508/CSA self-protected Type E combination motor controller, max | 65 kA @ 480Y/277V AC, D-frame with bulletin 100-C/104-C contactors |
| Power / Electrical Characteristics – Short-circuit current as a UL508/CSA Type F combination motor controller (Type 1 coordination), max | 65 kA @ 480Y/277V AC, D-frame with bulletin 100-C/104-C contactors |
| Power / Electrical Characteristics – Short-circuit current as a UL508/CSA Type F combination motor controller (Type 2 coordination), max | 65 kA @ 480Y/277V AC, D-frame with bulletin 100-C/104-C contactors |
| Power / Electrical Characteristics – Style | Open type |
| Power / Electrical Characteristics – Type of electrical connection for auxiliary- and control current circuit | Screw connection |
| Power / Electrical Characteristics – Type of electrical connection of main circuit | Screw connection |
| Power / Electrical Characteristics – Type of motor starter | Reversing starter |
| Напряжение питания | DC |
| Contruction – Width | 99 mm |
| Power / Electrical Characteristics – With short-circuit release | true |