Siemens AG 3RA2115-0EA16-2BB4
SIRIUS 3RA2 load feeders
Технические характеристики
| product brand name | SIRIUS |
|---|---|
| product designation | Direct (on-line) starter |
| design of the product | for DIN-rail or screw mounting |
| product type designation | 3RA21 |
| ● of the supplied contactor | 3RT2016-1BB42 |
| ● of the supplied circuit-breakers | 3RV2011-0EA15 |
| ● of the supplied link module | 3RA1921-1DA00 |
| General technical data – size of the circuit-breaker | S00 |
| General technical data – size of load feeder | S00 |
| General technical data – ● at AC in hot operating state per pole | 2.1 W |
| General technical data – ● without load current share typical | 4 W |
| General technical data – type of calculation of power loss current-dependent | quadratic |
| Напряжение питания | 690 V |
| Напряжение питания | 6 kV |
| General technical data – degree of protection NEMA rating | other |
| General technical data – shock resistance according to IEC 60068-2-27 | 6 g / 11 ms |
| General technical data – mechanical service life (operating cycles) of contactor typical | 30 000 000 |
| General technical data – type of coordination | 2 |
| General technical data – reference code according to IEC 81346-2:2019 | Q |
| Масса | 0.538 kg |
| Ambient conditions – ● during operation | -20 ... +60 °C |
| Ambient conditions – ● during storage | -50 ... +80 °C |
| Ambient conditions – ● during transport | -50 ... +80 °C |
| Ambient conditions – temperature compensation | -20 ... +60 °C |
| Ambient conditions – relative humidity during operation | 10 ... 95 % |
| Main circuit – number of poles for main current circuit | 3 |
| Main circuit – design of the switching contact | electromechanical |
| Main circuit – adjustable current response value current of the current-dependent overload release | 0.28 ... 0.4 A |
| Main circuit – ● rated value | 690 V |
| Main circuit – ● at AC-3 rated value maximum | 690 V |
| Main circuit – ● at AC-3e rated value maximum | 690 V |
| Main circuit – operating frequency rated value | 50 ... 60 Hz |
| Main circuit – ● at AC-3 at 400 V rated value | 0.4 A |
| Main circuit – ● at AC-3e at 400 V rated value | 0.4 A |
| Main circuit – — at 400 V rated value | 90 W |
| Main circuit – — at 400 V rated value (2) | 90 W |
| Напряжение питания | DC |
| Напряжение питания | 24 V |
| Control circuit/ Control – holding power of magnet coil at DC | 4 W |
| Auxiliary circuit – product extension auxiliary switch | Yes |
| Auxiliary circuit – number of NC contacts for auxiliary contacts | 1 |
| Auxiliary circuit – number of NO contacts for auxiliary contacts | 1 |
| Protective and monitoring functions – trip class | CLASS 10 |
| Protective and monitoring functions – design of the overload release | thermal (bimetallic) |
| Protective and monitoring functions – response value current of instantaneous short-circuit trip unit | 5.2 A |
| UL/CSA ratings – ● at 480 V rated value | 0.4 A |
| UL/CSA ratings – ● at 600 V rated value | 0.4 A |
| Short-circuit protection – product function short circuit protection | Yes |
| Short-circuit protection – design of the short-circuit trip | magnetic |
| Short-circuit protection – ● at 400 V according to IEC 60947-4-1 rated value | 150 000 A |
| Installation/ mounting/ dimensions – mounting position | vertical |
| Installation/ mounting/ dimensions – fastening method | screw and snap-on mounting onto 35 mm DIN rail |
| Installation/ mounting/ dimensions – height | 167 mm |
| Installation/ mounting/ dimensions – width | 45 mm |
| Installation/ mounting/ dimensions – depth | 97 mm |
| Installation/ mounting/ dimensions – — forwards | 20 mm |
| Installation/ mounting/ dimensions – — backwards | 0 mm |
| Installation/ mounting/ dimensions – — upwards | 50 mm |
| Installation/ mounting/ dimensions – — at the side | 20 mm |
| Installation/ mounting/ dimensions – — downwards | 10 mm |
| Installation/ mounting/ dimensions – — forwards (2) | 20 mm |
| Installation/ mounting/ dimensions – — backwards (2) | 0 mm |
| Installation/ mounting/ dimensions – — upwards (2) | 50 mm |
| Installation/ mounting/ dimensions – — downwards (2) | 10 mm |
| Installation/ mounting/ dimensions – — at the side (2) | 20 mm |
| Connections/ Terminals – ● for main current circuit | screw-type terminals |
| Connections/ Terminals – ● for auxiliary and control circuit | screw-type terminals |
| Safety related data – product function suitable for safety function | Yes |
| Safety related data – touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front |
| Communication/ Protocol – ● PROFINET IO protocol | No |
| Communication/ Protocol – ● PROFIsafe protocol | No |
| Communication/ Protocol – protocol is supported AS-Interface protocol | No |