Реле управления
SI

Siemens AG 3RH2131-1AV00

Контакторное реле Siemens 3RH2131-1AV00, серия 3RH2. Подбор по артикулу, поставка под заказ: цену и срок уточняйте через запрос на поставку.

  • Бренд: Siemens AG
  • Артикул (MPN): 3RH2131-1AV00
  • Серия: 3RH2 Series
  • Статус производства: Не определён

Категории:

Технические характеристики

Data sheet designationcontactor relay, 3 NO + 1 NC, 400 V AC, 50/60 Hz, screw terminal, frame size S00
product brand nameSIRIUS
product designationAuxiliary contactor
product type designation3RH2
General technical data / size of contactorS00
Напряжение питания6 kV
General technical data / shock resistance at rectangular impulse / at AC7,3 g / 5 ms, 4,7 g / 10 ms
General technical data / shock resistance with sine pulse / at AC11,4 g / 5 ms, 7,3 g / 10 ms
General technical data / mechanical service life (operating cycles) / of contactor typical30 000 000
General technical data / mechanical service life (operating cycles) / of the contactor with added electronically optimized5 000 000
General technical data / mechanical service life (operating cycles) / of the contactor with added auxiliary switch block typical10 000 000
General technical data / reference code according to IEC 81346-2K
General technical data / Substance Prohibitance (day/month/year)10/01/2009
Масса0.22 kg
Ambient conditions / installation altitude at height above sea level maximum2 000 m
Рабочая температура-25 ... +60 °C
Ambient conditions / ambient temperature / during storage-55 ... +80 °C
Main circuit / no-load switching frequency / at AC10 000 1/h
Main circuit / no-load switching frequency / at DC10 000 1/h
Напряжение питанияAC
Напряжение питания400 V
Напряжение питания400 V
Control circuit/ Control / magnet coil at AC / at 60 Hz0.85 ... 1.1
Control circuit/ Control / apparent pick-up power of magnet coil at AC37 V·A
Control circuit/ Control / inductive power factor with closing power of the coil0.8
Control circuit/ Control / apparent holding power of magnet coil at AC5.7 V·A
Control circuit/ Control / inductive power factor with the holding power of the coil0.25
Control circuit/ Control / closing delay / at AC8 ... 33 ms
Control circuit/ Control / opening delay / at AC4 ... 15 ms
Control circuit/ Control / arcing time10 ... 15 ms
Auxiliary circuit / number of NC contacts for auxiliary contacts1
Auxiliary circuit / instantaneous contact1
Auxiliary circuit / number of NO contacts for auxiliary contacts3
Auxiliary circuit / instantaneous contact #23
Auxiliary circuit / identification number and letter for switching elements31 E
Auxiliary circuit / operational current at AC-12 maximum10 A
Auxiliary circuit / operational current at AC-15 / at 230 V rated value10 A
Auxiliary circuit / operational current at AC-15 / at 400 V rated value3 A
Auxiliary circuit / operational current at AC-15 / at 500 V rated value2 A
Auxiliary circuit / operational current at AC-15 / at 690 V rated value1 A
Auxiliary circuit / operational current at 1 current path at DC-12 / at 24 V rated value10 A
Auxiliary circuit / operational current at 1 current path at DC-12 / at 60 V rated value6 A
Auxiliary circuit / operational current at 1 current path at DC-12 / at 110 V rated value3 A
Auxiliary circuit / operational current at 1 current path at DC-12 / at 220 V rated value1 A
Auxiliary circuit / operational current at 1 current path at DC-12 / at 440 V rated value0.3 A
Auxiliary circuit / operational current at 1 current path at DC-12 / at 600 V rated value0.15 A
Auxiliary circuit / operational current with 2 current paths in series at DC-12 / at 24 V rated value10 A
Auxiliary circuit / operational current with 2 current paths in series at DC-12 / at 60 V rated value10 A
Auxiliary circuit / operational current with 2 current paths in series at DC-12 / at 110 V rated value4 A
Auxiliary circuit / operational current with 2 current paths in series at DC-12 / at 220 V rated value2 A
Auxiliary circuit / operational current with 2 current paths in series at DC-12 / at 440 V rated value1.3 A
Auxiliary circuit / operational current with 2 current paths in series at DC-12 / at 600 V rated value0.65 A
Auxiliary circuit / operational current with 3 current paths in series at DC-12 / at 24 V rated value10 A
Auxiliary circuit / operational current with 3 current paths in series at DC-12 / at 60 V rated value10 A
Auxiliary circuit / operational current with 3 current paths in series at DC-12 / at 110 V rated value10 A
Auxiliary circuit / operational current with 3 current paths in series at DC-12 / at 220 V rated value3.6 A
Auxiliary circuit / operational current with 3 current paths in series at DC-12 / at 440 V rated value2.5 A
Auxiliary circuit / operational current with 3 current paths in series at DC-12 / at 600 V rated value1.8 A
Auxiliary circuit / operating frequency at DC-12 maximum1 000 1/h
Auxiliary circuit / operational current at 1 current path at DC-13 / at 24 V rated value10 A
Auxiliary circuit / operational current at 1 current path at DC-13 / at 60 V rated value2 A
Auxiliary circuit / operational current at 1 current path at DC-13 / at 110 V rated value1 A
Auxiliary circuit / operational current at 1 current path at DC-13 / at 220 V rated value0.3 A
Auxiliary circuit / operational current at 1 current path at DC-13 / at 440 V rated value0.14 A
Auxiliary circuit / operational current at 1 current path at DC-13 / at 600 V rated value0.1 A
Auxiliary circuit / operational current with 2 current paths in series at DC-13 / at 24 V rated value10 A
Auxiliary circuit / operational current with 2 current paths in series at DC-13 / at 60 V rated value3.5 A
Auxiliary circuit / operational current with 2 current paths in series at DC-13 / at 110 V rated value1.3 A
Auxiliary circuit / operational current with 2 current paths in series at DC-13 / at 220 V rated value0.9 A
Auxiliary circuit / operational current with 2 current paths in series at DC-13 / at 440 V rated value0.2 A
Auxiliary circuit / operational current with 2 current paths in series at DC-13 / at 600 V rated value0.1 A
Auxiliary circuit / operational current with 3 current paths in series at DC-13 / at 24 V rated value10 A
Auxiliary circuit / operational current with 3 current paths in series at DC-13 / at 60 V rated value4.7 A
Auxiliary circuit / operational current with 3 current paths in series at DC-13 / at 110 V rated value3 A
Auxiliary circuit / operational current with 3 current paths in series at DC-13 / at 220 V rated value1.2 A
Auxiliary circuit / operational current with 3 current paths in series at DC-13 / at 440 V rated value0.5 A
Auxiliary circuit / operational current with 3 current paths in series at DC-13 / at 600 V rated value0.26 A
Auxiliary circuit / operating frequency at DC-13 maximum1 000 1/h
Auxiliary circuit / contact reliability of auxiliary contacts1 faulty switching per 100 million (17 V, 1 mA)
UL/CSA ratings / contact rating of auxiliary contacts according to ULA600 / Q600
Installation/ mounting/ dimensions / width45 mm
Installation/ mounting/ dimensions / depth73 mm
Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / forwards10 mm
Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / upwards10 mm
Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / downwards10 mm
Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / at the side0 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts / forwards10 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts / upwards10 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts / at the side6 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts / downwards10 mm
Installation/ mounting/ dimensions / required spacing / for live parts / forwards10 mm
Installation/ mounting/ dimensions / required spacing / for live parts / upwards10 mm
Installation/ mounting/ dimensions / required spacing / for live parts / downwards10 mm
Installation/ mounting/ dimensions / required spacing / for live parts / at the side6 mm
Connections/ Terminals / type of electrical connection for auxiliary and control circuitscrew-type terminals
Connections/ Terminals / type of connectable conductor cross-sections / for auxiliary contacts / solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Connections/ Terminals / type of connectable conductor cross-sections / for auxiliary contacts / finely stranded with core end processing2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Connections/ Terminals / type of connectable conductor cross-sections / for AWG cables for auxiliary contacts2x (20 ... 16), 2x (18 ... 14), 2x 12
Safety related data / product function / positively driven operation according to IEC 60947-5-Yes
Safety related data / product function / suitable for safety functionYes
Safety related data / suitability for use safety-related switching OFFYes
Safety related data / service life maximum20 a
Safety related data / proportion of dangerous failures / with low demand rate according to SN 3192040 %
Safety related data / proportion of dangerous failures / with high demand rate according to SN 3192073 %
Сертификация1.15 kg
Сертификация48.2 kg
Сертификация-0.139 kg
Получить предложение по этой позиции