SI
Siemens AG 3RH2131-2VB40
Контакторное реле Siemens 3RH2131-2VB40, серия 3RH2. Подбор по артикулу, поставка под заказ: цену и срок уточняйте через запрос на поставку.
Категории:
Технические характеристики
| Data sheet designation | coupling contactor relay, 3 NO + 1 NC, 24 V DC, 0.85-1.85*Us, with integrated diode, spring-loaded terminal, frame size S00 |
|---|---|
| product brand name | SIRIUS |
| product designation | Coupling relay for switching auxiliary circuits |
| product type designation | 3RH2 |
| General technical data / size of contactor | S00 |
| Напряжение питания | 6 kV |
| General technical data / shock resistance at rectangular impulse / at DC | 10 g / 5 ms, 5 g / 10 ms |
| General technical data / shock resistance with sine pulse / at DC | 15 g / 5 ms, 8 g / 10 ms |
| General technical data / mechanical service life (operating cycles) / of contactor typical | 30 000 000 |
| General technical data / reference code according to IEC 81346-2 | K |
| General technical data / Substance Prohibitance (day/month/year) | 10/01/2009 |
| General technical data / SVHC substance name | Lead CAS-No. 7439-92-1 |
| Масса | 305.102 g |
| Ambient conditions / installation altitude at height above sea level maximum | 2 000 m |
| Рабочая температура | -25 ... +50 °C |
| Ambient conditions / ambient temperature / during storage | -55 ... +80 °C |
| Main circuit / no-load switching frequency / at AC | 10 000 1/h |
| Main circuit / no-load switching frequency / at DC | 10 000 1/h |
| Control circuit/ Control / magnet coil at DC / full-scale value | 1.85 |
| Control circuit/ Control / design of the surge suppressor | diode |
| Control circuit/ Control / closing power of magnet coil at DC | 1.6 W |
| Control circuit/ Control / holding power of magnet coil at DC | 1.6 W |
| Control circuit/ Control / closing delay / at DC | 25 ... 120 ms |
| Control circuit/ Control / opening delay / at DC | 20 ... 80 ms |
| Control circuit/ Control / arcing time | 10 ... 15 ms |
| Auxiliary circuit / number of NC contacts for auxiliary contacts | 1 |
| Auxiliary circuit / instantaneous contact | 1 |
| Auxiliary circuit / number of NO contacts for auxiliary contacts | 3 |
| Auxiliary circuit / instantaneous contact #2 | 3 |
| Auxiliary circuit / identification number and letter for switching elements | 31 E |
| Auxiliary circuit / operational current at AC-12 maximum | 10 A |
| Auxiliary circuit / operational current at AC-15 / at 230 V rated value | 10 A |
| Auxiliary circuit / operational current at AC-15 / at 400 V rated value | 3 A |
| Auxiliary circuit / operational current at AC-15 / at 500 V rated value | 2 A |
| Auxiliary circuit / operational current at AC-15 / at 690 V rated value | 1 A |
| Auxiliary circuit / operational current at 1 current path at DC-12 / at 24 V rated value | 10 A |
| Auxiliary circuit / operational current at 1 current path at DC-12 / at 60 V rated value | 6 A |
| Auxiliary circuit / operational current at 1 current path at DC-12 / at 110 V rated value | 3 A |
| Auxiliary circuit / operational current at 1 current path at DC-12 / at 220 V rated value | 1 A |
| Auxiliary circuit / operational current at 1 current path at DC-12 / at 440 V rated value | 0.3 A |
| Auxiliary circuit / operational current at 1 current path at DC-12 / at 600 V rated value | 0.15 A |
| Auxiliary circuit / operational current with 2 current paths in series at DC-12 / at 24 V rated value | 10 A |
| Auxiliary circuit / operational current with 2 current paths in series at DC-12 / at 60 V rated value | 10 A |
| Auxiliary circuit / operational current with 2 current paths in series at DC-12 / at 110 V rated value | 4 A |
| Auxiliary circuit / operational current with 2 current paths in series at DC-12 / at 220 V rated value | 2 A |
| Auxiliary circuit / operational current with 2 current paths in series at DC-12 / at 440 V rated value | 1.3 A |
| Auxiliary circuit / operational current with 2 current paths in series at DC-12 / at 600 V rated value | 0.65 A |
| Auxiliary circuit / operational current with 3 current paths in series at DC-12 / at 24 V rated value | 10 A |
| Auxiliary circuit / operational current with 3 current paths in series at DC-12 / at 60 V rated value | 10 A |
| Auxiliary circuit / operational current with 3 current paths in series at DC-12 / at 110 V rated value | 10 A |
| Auxiliary circuit / operational current with 3 current paths in series at DC-12 / at 220 V rated value | 3.6 A |
| Auxiliary circuit / operational current with 3 current paths in series at DC-12 / at 440 V rated value | 2.5 A |
| Auxiliary circuit / operational current with 3 current paths in series at DC-12 / at 600 V rated value | 1.8 A |
| Auxiliary circuit / operating frequency at DC-12 maximum | 1 000 1/h |
| Auxiliary circuit / operational current at 1 current path at DC-13 / at 24 V rated value | 10 A |
| Auxiliary circuit / operational current at 1 current path at DC-13 / at 60 V rated value | 2 A |
| Auxiliary circuit / operational current at 1 current path at DC-13 / at 110 V rated value | 1 A |
| Auxiliary circuit / operational current at 1 current path at DC-13 / at 220 V rated value | 0.3 A |
| Auxiliary circuit / operational current at 1 current path at DC-13 / at 440 V rated value | 0.14 A |
| Auxiliary circuit / operational current at 1 current path at DC-13 / at 600 V rated value | 0.1 A |
| Auxiliary circuit / operational current with 2 current paths in series at DC-13 / at 24 V rated value | 10 A |
| Auxiliary circuit / operational current with 2 current paths in series at DC-13 / at 60 V rated value | 3.5 A |
| Auxiliary circuit / operational current with 2 current paths in series at DC-13 / at 110 V rated value | 1.3 A |
| Auxiliary circuit / operational current with 2 current paths in series at DC-13 / at 220 V rated value | 0.9 A |
| Auxiliary circuit / operational current with 2 current paths in series at DC-13 / at 440 V rated value | 0.2 A |
| Auxiliary circuit / operational current with 2 current paths in series at DC-13 / at 600 V rated value | 0.1 A |
| Auxiliary circuit / operational current with 3 current paths in series at DC-13 / at 24 V rated value | 10 A |
| Auxiliary circuit / operational current with 3 current paths in series at DC-13 / at 60 V rated value | 4.7 A |
| Auxiliary circuit / operational current with 3 current paths in series at DC-13 / at 110 V rated value | 3 A |
| Auxiliary circuit / operational current with 3 current paths in series at DC-13 / at 220 V rated value | 1.2 A |
| Auxiliary circuit / operational current with 3 current paths in series at DC-13 / at 440 V rated value | 0.5 A |
| Auxiliary circuit / operational current with 3 current paths in series at DC-13 / at 600 V rated value | 0.26 A |
| Auxiliary circuit / operating frequency at DC-13 maximum | 1 000 1/h |
| Auxiliary circuit / contact reliability of auxiliary contacts | 1 faulty switching per 100 million (17 V, 1 mA) |
| UL/CSA ratings / contact rating of auxiliary contacts according to UL | A600 / Q600 |
| Installation/ mounting/ dimensions / width | 45 mm |
| Installation/ mounting/ dimensions / depth | 73 mm |
| Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / forwards | 10 mm |
| Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / upwards | 10 mm |
| Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / downwards | 10 mm |
| Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / at the side | 0 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts / forwards | 10 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts / upwards | 10 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts / at the side | 6 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts / downwards | 10 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts / forwards | 10 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts / upwards | 10 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts / downwards | 10 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts / at the side | 6 mm |
| Connections/ Terminals / type of electrical connection for auxiliary and control circuit | spring-loaded terminals |
| Connections/ Terminals / type of connectable conductor cross-sections / for auxiliary contacts / solid or stranded | 2x (0,5 ... 4 mm²) |
| Connections/ Terminals / type of connectable conductor cross-sections / for auxiliary contacts / finely stranded with core end processing | 2x (0.5 ... 2.5 mm²) |
| Connections/ Terminals / type of connectable conductor cross-sections / for auxiliary contacts / finely stranded without core end processing | 2x (0.5 ... 2.5 mm²) |
| Connections/ Terminals / type of connectable conductor cross-sections / for AWG cables for auxiliary contacts | 2x (20 ... 12) |
| Safety related data / product function / positively driven operation according to IEC 60947-5- | Yes |
| Safety related data / product function / suitable for safety function | Yes |
| Safety related data / suitability for use safety-related switching OFF | Yes |
| Safety related data / service life maximum | 20 a |
| Safety related data / proportion of dangerous failures / with low demand rate according to SN 31920 | 40 % |
| Safety related data / proportion of dangerous failures / with high demand rate according to SN 31920 | 73 % |
| Сертификация | 1.3 kg |
| Сертификация | 132 kg |
| Сертификация | -0.227 kg |