Siemens AG 3RP2505-1AB30
Timing relays
Категории:
Технические характеристики
| product brand name | SIRIUS |
|---|---|
| product designation | timing relay |
| design of the product | 13 functions |
| product type designation | 3RP25 |
| General technical data – product feature protective coating on printed-circuit board | No |
| General technical data – ● relay output | Yes |
| General technical data – ● semi-conductor output | No |
| General technical data – product extension required remote control | No |
| General technical data – product extension optional remote control | No |
| General technical data – power loss [W] maximum | 2 W |
| Напряжение питания | 300 V |
| Напряжение питания | 2.5 kV |
| General technical data – degree of pollution | 3 |
| Напряжение питания | 4 000 V |
| General technical data – shock resistance according to IEC 60068-2-27 | 11 g / 15 ms |
| General technical data – vibration resistance according to IEC 60068-2-6 | 10 ... 55 Hz / 0.35 mm |
| General technical data – mechanical service life (operating cycles) typical | 10 000 000 |
| General technical data – electrical endurance (operating cycles) at AC-15 at 230 V typical | 100 000 |
| General technical data – adjustable time | 0.05 s ... 100 h |
| General technical data – relative setting accuracy relating to full-scale value | 5 %; +/- |
| General technical data – thermal current | 5 A |
| General technical data – ON period/maximum minimum | 35 ms |
| General technical data – recovery time | 150 ms |
| General technical data – reference code according to IEC 81346-2 | K |
| General technical data – relative repeat accuracy | 1 %; +/- |
| General technical data – influence of the surrounding temperature | 1% in the whole temperature range to the set runtime |
| General technical data – power supply influence | 1% in the whole voltage range to the set runtime |
| General technical data – Substance Prohibitance (day/month/year) | 09/12/2014 |
| General technical data – SVHC substance name | 2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-one CAS-No. 71868-10-5 Melamine CAS-No. 108-78-1 6,6'-di-tert-butyl-2,2'-methylenedi-p-cresol CAS-No. 119-47-1 |
| Масса | 0.108 kg |
| Напряжение питания | AC/DC |
| Control circuit/ Control – ● at 50 Hz rated value | 24 V |
| Control circuit/ Control – ● at 60 Hz rated value | 24 V |
| Control circuit/ Control – ● at 50 Hz rated value (2) | 24 V |
| Control circuit/ Control – ● at 60 Hz rated value (2) | 24 V |
| Напряжение питания | 50 ... 60 Hz |
| Напряжение питания | 24 V |
| Напряжение питания | 24 V |
| Control circuit/ Control – ● initial value | 0.85 |
| Control circuit/ Control – ● full-scale value | 1.1 |
| Control circuit/ Control – ● initial value (2) | 0.85 |
| Control circuit/ Control – ● full-scale value (2) | 1.1 |
| Control circuit/ Control – ● initial value (3) | 0.85 |
| Control circuit/ Control – ● full-scale value (3) | 1.1 |
| Control circuit/ Control – ● at 24 V | 2 A |
| Control circuit/ Control – ● at 24 V (2) | 1 ms |
| Switching Function – ● ON-delay | Yes |
| Switching Function – ● ON-delay/instantaneous contact | No |
| Switching Function – ● passing make contact | Yes |
| Switching Function – ● passing make contact/instantaneous contact | No |
| Switching Function – ● OFF delay | No |
| Switching Function – ● flashing symmetrically with interval start/instantaneous | No |
| Switching Function – ● flashing symmetrically with interval start | Yes |
| Switching Function – ● flashing symmetrically with pulse start/instantaneous | No |
| Switching Function – ● flashing symmetrically with pulse start | Yes |
| Switching Function – ● flashing asymmetrically with interval start | No |
| Switching Function – ● flashing asymmetrically with pulse start | No |
| Switching Function – ● star-delta circuit with delay time | No |
| Switching Function – ● star-delta circuit | No |
| Switching Function – ● additive ON-delay | Yes |
| Switching Function – ● passing break contact | Yes |
| Switching Function – ● passing break contact/instantaneous | No |
| Switching Function – ● OFF delay (2) | Yes |
| Switching Function – ● OFF delay/instantaneous | No |
| Switching Function – ● pulse delayed | Yes |
| Switching Function – ● pulse delayed/instantaneous | No |
| Switching Function – ● pulse-shaping | Yes |
| Switching Function – ● pulse-shaping/instantaneous | No |
| Switching Function – ● additive ON-delay/instantaneous | No |
| Switching Function – ● ON-delay/OFF-delay/instantaneous | No |
| Switching Function – ● passing make contact (2) | Yes |
| Switching Function – ● passing make contact/instantaneous contact (2) | No |
| Switching Function – ● retrotriggerable with deactivated control signal/instantaneous contact | No |
| Switching Function – ● retrotriggerable with switched-on control signal | Yes |
| Switching Function – ● retrotriggerable with switched-on control signal/instantaneous contact | No |
| Switching Function – ● retriggerable with deactivated control signal | Yes |
| Switching Function – design of the control terminal non-floating | Yes |
| Short-circuit protection – design of the fuse link for short-circuit protection of the auxiliary switch required | fuse gL/gG: 4 A |
| Материал | AgSnO2 |
| Auxiliary circuit – ● delayed switching | 0 |
| Auxiliary circuit – ● instantaneous contact | 0 |
| Auxiliary circuit – ● delayed switching (2) | 0 |
| Auxiliary circuit – ● instantaneous contact (2) | 0 |
| Auxiliary circuit – ● delayed switching (3) | 1 |
| Auxiliary circuit – ● instantaneous contact (3) | 0 |
| Auxiliary circuit – ● at 24 V | 3 A |
| Auxiliary circuit – ● at 250 V | 3 A |
| Auxiliary circuit – ● at 24 V (2) | 1 A |
| Auxiliary circuit – ● at 125 V | 0.2 A |
| Auxiliary circuit – ● at 250 V (2) | 0.1 A |
| Auxiliary circuit – operating frequency with 3RT2 contactor maximum | 5 000 1/h |
| Auxiliary circuit – contact reliability of auxiliary contacts | one incorrect switching operation of 100 million switching operations (17 V, 5 mA) |
| Auxiliary circuit – contact rating of auxiliary contacts according to UL | R300 / B300 |
| Auxiliary circuit – switching capacity current with inductive load | 0.01 ... 3 A |
| Inputs/ Outputs – ● at the relay outputs switchover delayed/without delay | No |
| Inputs/ Outputs – ● non-volatile | No |
| Inputs/ Outputs – ● at 24 V | 1 A |
| Inputs/ Outputs – ● at 125 V | 0.2 A |
| Electromagnetic compatibility – EMC emitted interference according to IEC 61812-1 | ambience A (industrial sector) |
| Electromagnetic compatibility – EMC immunity according to IEC 61812-1 | corresponds to degree of severity 3 |
| Electromagnetic compatibility – ● due to burst according to IEC 61000-4-4 | 2 kV network connection / 1 kV control connection |
| Electromagnetic compatibility – ● due to conductor-earth surge according to IEC 61000-4-5 | 2 kV |
| Electromagnetic compatibility – ● due to conductor-conductor surge according to IEC 61000-4-5 | 1 kV |
| Electromagnetic compatibility – field-based interference according to IEC 61000-4-3 | 10 V/m |
| Electromagnetic compatibility – electrostatic discharge according to IEC 61000-4-2 | 4 kV contact discharge / 8 kV air discharge |
| Safety related data – category according to EN 954-1 | none |
| Safety related data – protection class IP on the front according to IEC 60529 | IP20 |
| Safety related data – type of insulation | Basic insulation |
| Connections/ Terminals – product component removable terminal for auxiliary and control circuit | Yes |
| Connections/ Terminals – type of electrical connection | screw terminal |
| Connections/ Terminals – ● for auxiliary and control circuit | screw-type terminals |
| Connections/ Terminals – ● solid | 1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²) |
| Connections/ Terminals – ● finely stranded with core end processing | 1x (0.5 ... 4 mm²), 2x (0.5 ... 1.5 mm²) |
| Connections/ Terminals – ● for AWG cables solid | 1x (20 ... 12), 2x (20 ... 14) |
| Connections/ Terminals – ● solid (2) | 0.5 ... 4 mm² |
| Connections/ Terminals – ● finely stranded with core end processing (2) | 0.5 ... 4 mm² |
| Connections/ Terminals – ● solid (3) | 20 ... 12 |
| Connections/ Terminals – tightening torque | 0.6 ... 0.8 N·m |
| Connections/ Terminals – design of the thread of the connection screw | M3 |
| Installation/ mounting/ dimensions – mounting position | any |
| Installation/ mounting/ dimensions – fastening method | screw and snap-on mounting onto 35 mm DIN rail |
| Installation/ mounting/ dimensions – height | 100 mm |
| Installation/ mounting/ dimensions – width | 17.5 mm |
| Installation/ mounting/ dimensions – depth | 90 mm |
| Installation/ mounting/ dimensions – — forwards | 0 mm |
| Installation/ mounting/ dimensions – — backwards | 0 mm |
| Installation/ mounting/ dimensions – — upwards | 0 mm |
| Installation/ mounting/ dimensions – — downwards | 0 mm |
| Installation/ mounting/ dimensions – — at the side | 0 mm |
| Installation/ mounting/ dimensions – — forwards (2) | 0 mm |
| Installation/ mounting/ dimensions – — backwards (2) | 0 mm |
| Installation/ mounting/ dimensions – — upwards (2) | 0 mm |
| Installation/ mounting/ dimensions – — at the side (2) | 0 mm |
| Installation/ mounting/ dimensions – — downwards (2) | 0 mm |
| Installation/ mounting/ dimensions – — forwards (3) | 0 mm |
| Installation/ mounting/ dimensions – — backwards (3) | 0 mm |
| Installation/ mounting/ dimensions – — upwards (3) | 0 mm |
| Installation/ mounting/ dimensions – — downwards (3) | 0 mm |
| Installation/ mounting/ dimensions – — at the side (3) | 0 mm |
| Ambient conditions – installation altitude at height above sea level maximum | 2 000 m |
| Ambient conditions – ● during operation | -25 ... +60 °C |
| Ambient conditions – ● during storage | -40 ... +85 °C |
| Ambient conditions – ● during transport | -40 ... +85 °C |
| Ambient conditions – relative humidity during operation | 10 ... 95 % |