3RT1056-2AM36

Siemens AG 3RT1056-2AM36

SIRIUS 3RT contactors, 3-pole, up to 250 kW

Технические характеристики

product brand nameSIRIUS
product designationPower contactor
product type designation3RT1
General technical data – size of contactorS6
General technical data – ● function module for communicationNo
General technical data – ● auxiliary switchYes
General technical data – ● at AC in hot operating state39 W
General technical data – ● at AC in hot operating state per pole13 W
General technical data – ● without load current share typical5.2 W
General technical data – type of calculation of power loss current-dependentquadratic
General technical data – ● of main circuit with degree of pollution 3 rated value1 000 V
General technical data – ● of auxiliary circuit with degree of pollution 3 rated value500 V
General technical data – ● of main circuit rated value8 kV
General technical data – ● of auxiliary circuit rated value6 kV
Напряжение питания690 V
General technical data – ● at AC8,5 g / 5 ms, 4,2 g / 10 ms
General technical data – ● at DC8,5 g / 5 ms, 4,2 g / 10 ms
General technical data – ● at AC (2)13,4 g / 5 ms, 6,5 g / 10 ms
General technical data – ● at DC (2)13,4 g / 5 ms, 6,5 g / 10 ms
General technical data – ● of contactor typical10 000 000
General technical data – ● of the contactor with added electronically optimized auxiliary switch block typical5 000 000
General technical data – ● of the contactor with added auxiliary switch block typical10 000 000
General technical data – reference code according to IEC 81346-2Q
General technical data – Substance Prohibitance (day/month/year)05/01/2012
General technical data – SVHC substance nameLead CAS-No. 7439-92-1
Масса3.2 kg
Ambient conditions – installation altitude at height above sea level maximum2 000 m
Ambient conditions – ● during operation-25 ... +60 °C
Ambient conditions – ● during storage-55 ... +80 °C
Ambient conditions – relative humidity minimum10 %
Ambient conditions – relative humidity at 55 °C according to IEC 60068-2-30 maximum95 %
Main circuit – number of poles for main current circuit3
Main circuit – number of NO contacts for main contacts3
Main circuit – number of NC contacts for main contacts0
Main circuit – ● at AC-3 rated value maximum1 000 V
Main circuit – ● at AC-3e rated value maximum1 000 V
Рабочая температура215 A
Рабочая температура215 A
Рабочая температура185 A
Рабочая температура100 A
Рабочая температура100 A
Main circuit – — at 400 V rated value185 A
Main circuit – — at 500 V rated value185 A
Main circuit – — at 690 V rated value170 A
Main circuit – — at 1000 V rated value65 A
Main circuit – — at 400 V rated value (2)185 A
Main circuit – — at 500 V rated value (2)185 A
Main circuit – — at 690 V rated value (2)170 A
Main circuit – — at 1000 V rated value (2)65 A
Main circuit – ● at AC-4 at 400 V rated value160 A
Main circuit – ● at AC-5a up to 690 V rated value189 A
Main circuit – ● at AC-5b up to 400 V rated value153 A
Main circuit – — up to 230 V for current peak value n=20 rated value157 A
Main circuit – — up to 400 V for current peak value n=20 rated value157 A
Main circuit – — up to 500 V for current peak value n=20 rated value157 A
Main circuit – — up to 690 V for current peak value n=20 rated value157 A
Main circuit – — up to 1000 V for current peak value n=20 rated value65 A
Main circuit – — up to 230 V for current peak value n=30 rated value105 A
Main circuit – — up to 400 V for current peak value n=30 rated value105 A
Main circuit – — up to 500 V for current peak value n=30 rated value105 A
Main circuit – — up to 690 V for current peak value n=30 rated value105 A
Main circuit – — up to 1000 V for current peak value n=30 rated value65 A
Main circuit – minimum cross-section in main circuit at maximum AC-1 rated value95 mm²
Main circuit – ● at 400 V rated value81 A
Main circuit – ● at 690 V rated value65 A
Main circuit – — at 24 V rated value160 A
Main circuit – — at 60 V rated value160 A
Main circuit – — at 110 V rated value18 A
Main circuit – — at 220 V rated value3.4 A
Main circuit – — at 440 V rated value0.8 A
Main circuit – — at 600 V rated value0.5 A
Main circuit – — at 24 V rated value (2)160 A
Main circuit – — at 60 V rated value (2)160 A
Main circuit – — at 110 V rated value (2)160 A
Main circuit – — at 220 V rated value (2)20 A
Main circuit – — at 440 V rated value (2)3.2 A
Main circuit – — at 600 V rated value (2)1.6 A
Main circuit – — at 24 V rated value (3)160 A
Main circuit – — at 60 V rated value (3)160 A
Main circuit – — at 110 V rated value (3)160 A
Main circuit – — at 220 V rated value (3)160 A
Main circuit – — at 440 V rated value (3)11.5 A
Main circuit – — at 600 V rated value (3)4 A
Main circuit – — at 24 V rated value (4)160 A
Main circuit – — at 60 V rated value (4)7.5 A
Main circuit – — at 220 V rated value (4)0.6 A
Main circuit – — at 440 V rated value (4)0.17 A
Main circuit – — at 600 V rated value (4)0.12 A
Main circuit – — at 24 V rated value (5)160 A
Main circuit – — at 60 V rated value (5)160 A
Main circuit – — at 110 V rated value (4)160 A
Main circuit – — at 220 V rated value (5)2.5 A
Main circuit – — at 440 V rated value (5)0.65 A
Main circuit – — at 600 V rated value (5)0.37 A
Main circuit – — at 24 V rated value (6)160 A
Main circuit – — at 60 V rated value (6)160 A
Main circuit – — at 110 V rated value (5)160 A
Main circuit – — at 220 V rated value (6)160 A
Main circuit – — at 440 V rated value (6)1.4 A
Main circuit – — at 600 V rated value (6)0.75 A
Main circuit – — at 230 V rated value55 kW
Main circuit – — at 400 V rated value (3)90 kW
Main circuit – — at 500 V rated value (3)132 kW
Main circuit – — at 690 V rated value (3)160 kW
Main circuit – — at 1000 V rated value (3)90 kW
Main circuit – — at 230 V rated value (2)55 kW
Main circuit – — at 400 V rated value (4)90 kW
Main circuit – — at 500 V rated value (4)132 kW
Main circuit – — at 690 V rated value (4)160 kW
Main circuit – — at 1000 V rated value (4)90 kW
Main circuit – ● at 400 V rated value (2)45 kW
Main circuit – ● at 690 V rated value (2)65 kW
Main circuit – ● up to 230 V for current peak value n=20 rated value60 kVA
Main circuit – ● up to 400 V for current peak value n=20 rated value100 kVA
Main circuit – ● up to 500 V for current peak value n=20 rated value130 kVA
Main circuit – ● up to 690 V for current peak value n=20 rated value180 kVA
Main circuit – ● up to 1000 V for current peak value n=20 rated value110 kVA
Main circuit – ● up to 230 V for current peak value n=30 rated value40 kVA
Main circuit – ● up to 400 V for current peak value n=30 rated value70 kVA
Main circuit – ● up to 500 V for current peak value n=30 rated value90 kVA
Main circuit – ● up to 690 V for current peak value n=30 rated value120 kVA
Main circuit – ● up to 1000 V for current peak value n=30 rated value110 kVA
Main circuit – ● limited to 1 s switching at zero current maximum2 900 A; Use minimum cross-section acc. to AC-1 rated value
Main circuit – ● limited to 5 s switching at zero current maximum2 084 A; Use minimum cross-section acc. to AC-1 rated value
Main circuit – ● limited to 10 s switching at zero current maximum1 480 A; Use minimum cross-section acc. to AC-1 rated value
Main circuit – ● limited to 30 s switching at zero current maximum968 A; Use minimum cross-section acc. to AC-1 rated value
Main circuit – ● limited to 60 s switching at zero current maximum801 A; Use minimum cross-section acc. to AC-1 rated value
Main circuit – ● at AC2 000 1/h
Main circuit – ● at DC2 000 1/h
Main circuit – ● at AC-1 maximum800 1/h
Main circuit – ● at AC-2 maximum300 1/h
Main circuit – ● at AC-3 maximum750 1/h
Main circuit – — maximum750 1/h
Main circuit – ● at AC-4 maximum130 1/h
Напряжение питанияAC/DC
Control circuit/ Control – ● at 50 Hz rated value200 ... 220 V
Control circuit/ Control – ● at 60 Hz rated value200 ... 220 V
Напряжение питания200 ... 220 V
Control circuit/ Control – ● initial value0.8
Control circuit/ Control – ● full-scale value1.1
Control circuit/ Control – ● at 50 Hz0.8 ... 1.1
Control circuit/ Control – ● at 60 Hz0.8 ... 1.1
Control circuit/ Control – design of the surge suppressorwith varistor
Control circuit/ Control – — at 50 Hz250 V·A
Control circuit/ Control – — at 60 Hz250 V·A
Control circuit/ Control – — at 60 Hz (2)300 V·A
Control circuit/ Control – — at 50 Hz (2)300 V·A
Control circuit/ Control – ● at 50 Hz (2)300 V·A
Control circuit/ Control – ● at 60 Hz (2)300 V·A
Control circuit/ Control – ● at 50 Hz (3)0.9
Control circuit/ Control – ● at 60 Hz (3)0.9
Напряжение питания4.3 V·A
Напряжение питания5.2 V·A
Control circuit/ Control – — at 50 Hz (3)4.8 V·A
Control circuit/ Control – — at 60 Hz (3)4.8 V·A
Control circuit/ Control – — at 50 Hz (4)5.8 V·A
Control circuit/ Control – — at 60 Hz (4)5.8 V·A
Control circuit/ Control – ● at 50 Hz (4)0.8
Control circuit/ Control – ● at 60 Hz (4)0.8
Control circuit/ Control – closing power of magnet coil at DC360 W
Control circuit/ Control – holding power of magnet coil at DC5.2 W
Control circuit/ Control – ● at AC20 ... 95 ms
Control circuit/ Control – ● at DC20 ... 95 ms
Control circuit/ Control – ● at AC (2)40 ... 60 ms
Control circuit/ Control – ● at DC (2)40 ... 60 ms
Control circuit/ Control – arcing time10 ... 15 ms
Control circuit/ Control – control version of the switch operating mechanismStandard A1 - A2
Auxiliary circuit – number of NC contacts for auxiliary contacts instantaneous contact2
Auxiliary circuit – number of NO contacts for auxiliary contacts instantaneous contact2
Auxiliary circuit – operational current at AC-12 maximum10 A
Auxiliary circuit – ● at 230 V rated value6 A
Auxiliary circuit – ● at 400 V rated value3 A
Auxiliary circuit – ● at 500 V rated value2 A
Auxiliary circuit – ● at 690 V rated value1 A
Auxiliary circuit – ● at 24 V rated value10 A
Auxiliary circuit – ● at 48 V rated value6 A
Auxiliary circuit – ● at 60 V rated value6 A
Auxiliary circuit – ● at 110 V rated value3 A
Auxiliary circuit – ● at 125 V rated value2 A
Auxiliary circuit – ● at 220 V rated value1 A
Auxiliary circuit – ● at 600 V rated value0.15 A
Auxiliary circuit – ● at 24 V rated value (2)10 A
Auxiliary circuit – ● at 48 V rated value (2)2 A
Auxiliary circuit – ● at 60 V rated value (2)2 A
Auxiliary circuit – ● at 110 V rated value (2)1 A
Auxiliary circuit – ● at 125 V rated value (2)0.9 A
Auxiliary circuit – ● at 220 V rated value (2)0.3 A
Auxiliary circuit – ● at 600 V rated value (2)0.1 A
Auxiliary circuit – contact reliability of auxiliary contacts1 faulty switching per 100 million (17 V, 1 mA)
UL/CSA ratings – ● at 480 V rated value180 A
UL/CSA ratings – ● at 600 V rated value192 A
UL/CSA ratings – — at 230 V rated value30 hp
UL/CSA ratings – — at 200/208 V rated value60 hp
UL/CSA ratings – — at 220/230 V rated value75 hp
UL/CSA ratings – — at 460/480 V rated value150 hp
UL/CSA ratings – — at 575/600 V rated value200 hp
UL/CSA ratings – contact rating of auxiliary contacts according to ULA600 / Q600
Short-circuit protection – design of the miniature circuit breaker for short-circuit protection of the auxiliary circuit up to 230 VC characteristic: 10 A; 0.4 kA
Short-circuit protection – — with type of coordination 1 requiredgG: 355 A (690 V, 100 kA)
Short-circuit protection – — with type of coordination 2 requiredgG: 315 A (690 V, 100 kA), aM: 200 A (690 V, 50 kA), BS88: 315 A (415 V, 50 kA)
Short-circuit protection – ● for short-circuit protection of the auxiliary switch requiredgG: 10 A (500 V, 1 kA)
Installation/ mounting/ dimensions – mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Installation/ mounting/ dimensions – fastening method side-by-side mountingYes
Installation/ mounting/ dimensions – fastening methodscrew fixing
Installation/ mounting/ dimensions – height172 mm
Installation/ mounting/ dimensions – width120 mm
Installation/ mounting/ dimensions – depth170 mm
Installation/ mounting/ dimensions – — forwards20 mm
Installation/ mounting/ dimensions – — upwards10 mm
Installation/ mounting/ dimensions – — downwards10 mm
Installation/ mounting/ dimensions – — at the side0 mm
Installation/ mounting/ dimensions – — forwards (2)20 mm
Installation/ mounting/ dimensions – — upwards (2)10 mm
Installation/ mounting/ dimensions – — at the side (2)10 mm
Installation/ mounting/ dimensions – — downwards (2)10 mm
Installation/ mounting/ dimensions – — forwards (3)20 mm
Installation/ mounting/ dimensions – — upwards (3)10 mm
Installation/ mounting/ dimensions – — downwards (3)10 mm
Installation/ mounting/ dimensions – — at the side (3)10 mm
Connections/ Terminals – ● for main current circuitConnection bar
Connections/ Terminals – ● for auxiliary and control circuitspring-loaded terminals
Connections/ Terminals – ● at contactor for auxiliary contactsSpring-type terminals
Connections/ Terminals – ● of magnet coilSpring-loaded terminal
Connections/ Terminals – width of connection bar17 mm
Connections/ Terminals – thickness of connection bar3 mm
Connections/ Terminals – diameter of holes9 mm
Connections/ Terminals – number of holes1
Connections/ Terminals – ● for AWG cables for main contacts4 ... 250 kcmil
Connections/ Terminals – ● stranded25 ... 120 mm²
Connections/ Terminals – ● solid or stranded0.25 ... 2.5 mm²
Connections/ Terminals – ● finely stranded with core end processing0.25 ... 1.5 mm²
Connections/ Terminals – ● finely stranded without core end processing0.25 ... 2.5 mm²
Connections/ Terminals – — solid2x (0.25 ... 2.5 mm²)
Connections/ Terminals – — solid or stranded2x (0,25 ... 2,5 mm²)
Connections/ Terminals – — finely stranded with core end processing2x (0.25 ... 1.5 mm²)
Connections/ Terminals – — finely stranded without core end processing2x (0.25 ... 2.5 mm²)
Connections/ Terminals – ● for AWG cables for auxiliary contacts2x (24 ... 14)
Connections/ Terminals – AWG number as coded connectable conductor cross section for auxiliary contacts24 ... 14
Safety related data – ● mirror contact according to IEC 60947-4-1Yes
Safety related data – ● positively driven operation according to IEC 60947-5-1No
Safety related data – ● suitable for safety functionYes
Safety related data – suitability for use safety-related switching OFFYes
Safety related data – service life maximum20 a
Safety related data – test wear-related service life necessaryYes
Safety related data – ● with low demand rate according to SN 3192040 %
Safety related data – ● with high demand rate according to SN 3192073 %
Safety related data – B10 value with high demand rate according to SN 319201 000 000
Safety related data – failure rate [FIT] with low demand rate according to SN 31920100 FIT
Safety related data – device type according to ISO 13849-13
Safety related data – overdimensioning according to ISO 13849-2 necessaryYes
Safety related data – safety device type according to IEC 61508-2Type A
Safety related data – protection class IP on the front according to IEC 60529IP00; IP20 with box terminal/cover
Safety related data – touch protection on the front according to IEC 60529finger-safe, for vertical contact from the front with box terminal/cover
Сертификация17 kg
Сертификация0.901 kg
Сертификация363 kg
Сертификация-2.28 kg
Сертификация379 kg
Получить предложение по этой позиции