Siemens AG 3RT1075-6AP36
SIRIUS 3RT contactors, 3-pole, up to 250 kW
Технические характеристики
| product brand name | SIRIUS |
|---|---|
| product designation | Power contactor |
| product type designation | 3RT1 |
| General technical data – size of contactor | S12 |
| General technical data – ● function module for communication | No |
| General technical data – ● auxiliary switch | Yes |
| General technical data – ● at AC in hot operating state | 105 W |
| General technical data – ● at AC in hot operating state per pole | 35 W |
| General technical data – ● without load current share typical | 10 W |
| General technical data – type of calculation of power loss current-dependent | quadratic |
| General technical data – ● of main circuit with degree of pollution 3 rated value | 1 000 V |
| General technical data – ● of auxiliary circuit with degree of pollution 3 rated value | 500 V |
| General technical data – ● of main circuit rated value | 8 kV |
| General technical data – ● of auxiliary circuit rated value | 6 kV |
| Напряжение питания | 690 V |
| General technical data – ● at AC | 8,5 g / 5 ms, 4,2 g / 10 ms |
| General technical data – ● at DC | 8,5 g / 5 ms, 4,2 g / 10 ms |
| General technical data – ● at AC (2) | 13,4 g / 5 ms, 6,5 g / 10 ms |
| General technical data – ● at DC (2) | 13,4 g / 5 ms, 6,5 g / 10 ms |
| General technical data – ● of contactor typical | 10 000 000 |
| General technical data – ● of the contactor with added electronically optimized auxiliary switch block typical | 5 000 000 |
| General technical data – ● of the contactor with added auxiliary switch block typical | 10 000 000 |
| General technical data – reference code according to IEC 81346-2 | Q |
| General technical data – Substance Prohibitance (day/month/year) | 05/01/2012 |
| General technical data – SVHC substance name | Lead CAS-No. 7439-92-1 |
| Масса | 10.162 kg |
| Ambient conditions – installation altitude at height above sea level maximum | 2 000 m |
| Ambient conditions – ● during operation | -25 ... +60 °C |
| Ambient conditions – ● during storage | -55 ... +80 °C |
| Ambient conditions – relative humidity minimum | 10 % |
| Ambient conditions – relative humidity at 55 °C according to IEC 60068-2-30 maximum | 95 % |
| Main circuit – number of poles for main current circuit | 3 |
| Main circuit – number of NO contacts for main contacts | 3 |
| Main circuit – number of NC contacts for main contacts | 0 |
| Main circuit – ● at AC-3 rated value maximum | 1 000 V |
| Main circuit – ● at AC-3e rated value maximum | 1 000 V |
| Рабочая температура | 430 A |
| Рабочая температура | 430 A |
| Рабочая температура | 400 A |
| Рабочая температура | 200 A |
| Рабочая температура | 200 A |
| Main circuit – — at 400 V rated value | 400 A |
| Main circuit – — at 500 V rated value | 400 A |
| Main circuit – — at 690 V rated value | 400 A |
| Main circuit – — at 1000 V rated value | 180 A |
| Main circuit – — at 400 V rated value (2) | 400 A |
| Main circuit – — at 500 V rated value (2) | 400 A |
| Main circuit – — at 690 V rated value (2) | 400 A |
| Main circuit – — at 1000 V rated value (2) | 180 A |
| Main circuit – ● at AC-4 at 400 V rated value | 350 A |
| Main circuit – ● at AC-5a up to 690 V rated value | 378 A |
| Main circuit – ● at AC-5b up to 400 V rated value | 332 A |
| Main circuit – — up to 230 V for current peak value n=20 rated value | 395 A |
| Main circuit – — up to 400 V for current peak value n=20 rated value | 395 A |
| Main circuit – — up to 500 V for current peak value n=20 rated value | 395 A |
| Main circuit – — up to 690 V for current peak value n=20 rated value | 395 A |
| Main circuit – — up to 1000 V for current peak value n=20 rated value | 180 A |
| Main circuit – — up to 230 V for current peak value n=30 rated value | 264 A |
| Main circuit – — up to 400 V for current peak value n=30 rated value | 264 A |
| Main circuit – — up to 500 V for current peak value n=30 rated value | 264 A |
| Main circuit – — up to 690 V for current peak value n=30 rated value | 264 A |
| Main circuit – — up to 1000 V for current peak value n=30 rated value | 180 A |
| Main circuit – minimum cross-section in main circuit at maximum AC-1 rated value | 300 mm² |
| Main circuit – ● at 400 V rated value | 150 A |
| Main circuit – ● at 690 V rated value | 135 A |
| Main circuit – — at 24 V rated value | 400 A |
| Main circuit – — at 60 V rated value | 330 A |
| Main circuit – — at 110 V rated value | 33 A |
| Main circuit – — at 220 V rated value | 3.8 A |
| Main circuit – — at 440 V rated value | 0.9 A |
| Main circuit – — at 600 V rated value | 0.6 A |
| Main circuit – — at 24 V rated value (2) | 400 A |
| Main circuit – — at 60 V rated value (2) | 400 A |
| Main circuit – — at 110 V rated value (2) | 400 A |
| Main circuit – — at 220 V rated value (2) | 400 A |
| Main circuit – — at 440 V rated value (2) | 4 A |
| Main circuit – — at 600 V rated value (2) | 2 A |
| Main circuit – — at 24 V rated value (3) | 400 A |
| Main circuit – — at 60 V rated value (3) | 400 A |
| Main circuit – — at 110 V rated value (3) | 400 A |
| Main circuit – — at 220 V rated value (3) | 400 A |
| Main circuit – — at 440 V rated value (3) | 11 A |
| Main circuit – — at 600 V rated value (3) | 5.2 A |
| Main circuit – — at 24 V rated value (4) | 400 A |
| Main circuit – — at 60 V rated value (4) | 11 A |
| Main circuit – — at 220 V rated value (4) | 0.6 A |
| Main circuit – — at 440 V rated value (4) | 0.18 A |
| Main circuit – — at 600 V rated value (4) | 0.125 A |
| Main circuit – — at 24 V rated value (5) | 400 A |
| Main circuit – — at 60 V rated value (5) | 400 A |
| Main circuit – — at 110 V rated value (4) | 400 A |
| Main circuit – — at 220 V rated value (5) | 2.5 A |
| Main circuit – — at 440 V rated value (5) | 0.65 A |
| Main circuit – — at 600 V rated value (5) | 0.37 A |
| Main circuit – — at 24 V rated value (6) | 400 A |
| Main circuit – — at 60 V rated value (6) | 400 A |
| Main circuit – — at 110 V rated value (5) | 400 A |
| Main circuit – — at 220 V rated value (6) | 400 A |
| Main circuit – — at 440 V rated value (6) | 1.4 A |
| Main circuit – — at 600 V rated value (6) | 0.75 A |
| Main circuit – — at 230 V rated value | 132 kW |
| Main circuit – — at 400 V rated value (3) | 200 kW |
| Main circuit – — at 500 V rated value (3) | 250 kW |
| Main circuit – — at 690 V rated value (3) | 400 kW |
| Main circuit – — at 1000 V rated value (3) | 250 kW |
| Main circuit – — at 230 V rated value (2) | 132 kW |
| Main circuit – — at 400 V rated value (4) | 200 kW |
| Main circuit – — at 500 V rated value (4) | 250 kW |
| Main circuit – — at 690 V rated value (4) | 400 kW |
| Main circuit – — at 1000 V rated value (4) | 250 kW |
| Main circuit – ● at 400 V rated value (2) | 85 kW |
| Main circuit – ● at 690 V rated value (2) | 133 kW |
| Main circuit – ● up to 230 V for current peak value n=20 rated value | 150 kVA |
| Main circuit – ● up to 400 V for current peak value n=20 rated value | 270 kVA |
| Main circuit – ● up to 500 V for current peak value n=20 rated value | 340 kVA |
| Main circuit – ● up to 690 V for current peak value n=20 rated value | 470 kVA |
| Main circuit – ● up to 1000 V for current peak value n=20 rated value | 310 kVA |
| Main circuit – ● up to 230 V for current peak value n=30 rated value | 100 kVA |
| Main circuit – ● up to 400 V for current peak value n=30 rated value | 180 kVA |
| Main circuit – ● up to 500 V for current peak value n=30 rated value | 220 kVA |
| Main circuit – ● up to 690 V for current peak value n=30 rated value | 310 kVA |
| Main circuit – ● up to 1000 V for current peak value n=30 rated value | 310 kVA |
| Main circuit – ● limited to 1 s switching at zero current maximum | 6 600 A; Use minimum cross-section acc. to AC-1 rated value |
| Main circuit – ● limited to 5 s switching at zero current maximum | 5 761 A; Use minimum cross-section acc. to AC-1 rated value |
| Main circuit – ● limited to 10 s switching at zero current maximum | 4 143 A; Use minimum cross-section acc. to AC-1 rated value |
| Main circuit – ● limited to 30 s switching at zero current maximum | 2 635 A; Use minimum cross-section acc. to AC-1 rated value |
| Main circuit – ● limited to 60 s switching at zero current maximum | 2 088 A; Use minimum cross-section acc. to AC-1 rated value |
| Main circuit – ● at AC | 2 000 1/h |
| Main circuit – ● at DC | 2 000 1/h |
| Main circuit – ● at AC-1 maximum | 700 1/h |
| Main circuit – ● at AC-2 maximum | 200 1/h |
| Main circuit – ● at AC-3 maximum | 500 1/h |
| Main circuit – — maximum | 500 1/h |
| Main circuit – ● at AC-4 maximum | 130 1/h |
| Напряжение питания | AC/DC |
| Control circuit/ Control – ● at 50 Hz rated value | 220 ... 240 V |
| Control circuit/ Control – ● at 60 Hz rated value | 220 ... 240 V |
| Напряжение питания | 220 ... 240 V |
| Control circuit/ Control – ● initial value | 0.8 |
| Control circuit/ Control – ● full-scale value | 1.1 |
| Control circuit/ Control – ● at 50 Hz | 0.8 ... 1.1 |
| Control circuit/ Control – ● at 60 Hz | 0.8 ... 1.1 |
| Control circuit/ Control – design of the surge suppressor | with varistor |
| Control circuit/ Control – — at 50 Hz | 700 V·A |
| Control circuit/ Control – — at 60 Hz | 700 V·A |
| Control circuit/ Control – — at 60 Hz (2) | 830 V·A |
| Control circuit/ Control – — at 50 Hz (2) | 830 V·A |
| Control circuit/ Control – ● at 50 Hz (2) | 830 V·A |
| Control circuit/ Control – ● at 60 Hz (2) | 830 V·A |
| Control circuit/ Control – ● at 50 Hz (3) | 0.9 |
| Control circuit/ Control – ● at 60 Hz (3) | 0.9 |
| Напряжение питания | 8.5 V·A |
| Напряжение питания | 10 V·A |
| Control circuit/ Control – — at 50 Hz (3) | 7.6 V·A |
| Control circuit/ Control – — at 60 Hz (3) | 7.6 V·A |
| Control circuit/ Control – — at 50 Hz (4) | 9.2 V·A |
| Control circuit/ Control – — at 60 Hz (4) | 9.2 V·A |
| Control circuit/ Control – ● at 50 Hz (4) | 0.9 |
| Control circuit/ Control – ● at 60 Hz (4) | 0.9 |
| Control circuit/ Control – closing power of magnet coil at DC | 920 W |
| Control circuit/ Control – holding power of magnet coil at DC | 10 W |
| Control circuit/ Control – ● at AC | 45 ... 100 ms |
| Control circuit/ Control – ● at DC | 45 ... 100 ms |
| Control circuit/ Control – ● at AC (2) | 60 ... 100 ms |
| Control circuit/ Control – ● at DC (2) | 60 ... 100 ms |
| Control circuit/ Control – arcing time | 10 ... 15 ms |
| Control circuit/ Control – control version of the switch operating mechanism | Standard A1 - A2 |
| Auxiliary circuit – number of NC contacts for auxiliary contacts instantaneous contact | 2 |
| Auxiliary circuit – number of NO contacts for auxiliary contacts instantaneous contact | 2 |
| Auxiliary circuit – operational current at AC-12 maximum | 10 A |
| Auxiliary circuit – ● at 230 V rated value | 6 A |
| Auxiliary circuit – ● at 400 V rated value | 3 A |
| Auxiliary circuit – ● at 500 V rated value | 2 A |
| Auxiliary circuit – ● at 690 V rated value | 1 A |
| Auxiliary circuit – ● at 24 V rated value | 10 A |
| Auxiliary circuit – ● at 48 V rated value | 6 A |
| Auxiliary circuit – ● at 60 V rated value | 6 A |
| Auxiliary circuit – ● at 110 V rated value | 3 A |
| Auxiliary circuit – ● at 125 V rated value | 2 A |
| Auxiliary circuit – ● at 220 V rated value | 1 A |
| Auxiliary circuit – ● at 600 V rated value | 0.15 A |
| Auxiliary circuit – ● at 24 V rated value (2) | 10 A |
| Auxiliary circuit – ● at 48 V rated value (2) | 2 A |
| Auxiliary circuit – ● at 60 V rated value (2) | 2 A |
| Auxiliary circuit – ● at 110 V rated value (2) | 1 A |
| Auxiliary circuit – ● at 125 V rated value (2) | 0.9 A |
| Auxiliary circuit – ● at 220 V rated value (2) | 0.3 A |
| Auxiliary circuit – ● at 600 V rated value (2) | 0.1 A |
| Auxiliary circuit – contact reliability of auxiliary contacts | 1 faulty switching per 100 million (17 V, 1 mA) |
| UL/CSA ratings – ● at 480 V rated value | 361 A |
| UL/CSA ratings – ● at 600 V rated value | 382 A |
| UL/CSA ratings – — at 200/208 V rated value | 125 hp |
| UL/CSA ratings – — at 220/230 V rated value | 150 hp |
| UL/CSA ratings – — at 460/480 V rated value | 300 hp |
| UL/CSA ratings – — at 575/600 V rated value | 400 hp |
| UL/CSA ratings – contact rating of auxiliary contacts according to UL | A600 / Q600 |
| Short-circuit protection – design of the miniature circuit breaker for short-circuit protection of the auxiliary circuit up to 230 V | C characteristic: 10 A; 0.4 kA |
| Short-circuit protection – — with type of coordination 1 required | gG: 630 A (690 V, 100 kA) |
| Short-circuit protection – — with type of coordination 2 required | gG: 500 A (690 V, 100 kA), aM: 400 A (690 V, 50 kA), BS88: 450 A (415 V, 50 kA) |
| Short-circuit protection – ● for short-circuit protection of the auxiliary switch required | gG: 10 A (500 V, 1 kA) |
| Installation/ mounting/ dimensions – mounting position | with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back |
| Installation/ mounting/ dimensions – fastening method side-by-side mounting | Yes |
| Installation/ mounting/ dimensions – fastening method | screw fixing |
| Installation/ mounting/ dimensions – height | 214 mm |
| Installation/ mounting/ dimensions – width | 160 mm |
| Installation/ mounting/ dimensions – depth | 225 mm |
| Installation/ mounting/ dimensions – — forwards | 20 mm |
| Installation/ mounting/ dimensions – — upwards | 10 mm |
| Installation/ mounting/ dimensions – — downwards | 10 mm |
| Installation/ mounting/ dimensions – — at the side | 0 mm |
| Installation/ mounting/ dimensions – — forwards (2) | 20 mm |
| Installation/ mounting/ dimensions – — upwards (2) | 10 mm |
| Installation/ mounting/ dimensions – — at the side (2) | 10 mm |
| Installation/ mounting/ dimensions – — downwards (2) | 10 mm |
| Installation/ mounting/ dimensions – — forwards (3) | 20 mm |
| Installation/ mounting/ dimensions – — upwards (3) | 10 mm |
| Installation/ mounting/ dimensions – — downwards (3) | 10 mm |
| Installation/ mounting/ dimensions – — at the side (3) | 10 mm |
| Connections/ Terminals – ● for main current circuit | Connection bar |
| Connections/ Terminals – ● for auxiliary and control circuit | screw-type terminals |
| Connections/ Terminals – ● at contactor for auxiliary contacts | Screw-type terminals |
| Connections/ Terminals – ● of magnet coil | screw terminal |
| Connections/ Terminals – width of connection bar | 25 mm |
| Connections/ Terminals – thickness of connection bar | 6 mm |
| Connections/ Terminals – diameter of holes | 11 mm |
| Connections/ Terminals – number of holes | 1 |
| Connections/ Terminals – ● for AWG cables for main contacts | 2/0 ... 500 kcmil |
| Connections/ Terminals – ● stranded | 70 ... 240 mm² |
| Connections/ Terminals – ● solid or stranded | 0.5 ... 4 mm² |
| Connections/ Terminals – ● finely stranded with core end processing | 0.5 ... 2.5 mm² |
| Connections/ Terminals – — solid | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²) |
| Connections/ Terminals – — solid or stranded | 2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²) |
| Connections/ Terminals – — finely stranded with core end processing | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
| Connections/ Terminals – ● for AWG cables for auxiliary contacts | 2x (20 ... 16), 2x (18 ... 14), 1x 12 |
| Connections/ Terminals – AWG number as coded connectable conductor cross section for auxiliary contacts | 18 ... 14 |
| Safety related data – ● mirror contact according to IEC 60947-4-1 | Yes |
| Safety related data – ● positively driven operation according to IEC 60947-5-1 | No |
| Safety related data – ● suitable for safety function | Yes |
| Safety related data – suitability for use safety-related switching OFF | Yes |
| Safety related data – service life maximum | 20 a |
| Safety related data – test wear-related service life necessary | Yes |
| Safety related data – ● with low demand rate according to SN 31920 | 40 % |
| Safety related data – ● with high demand rate according to SN 31920 | 73 % |
| Safety related data – B10 value with high demand rate according to SN 31920 | 1 000 000 |
| Safety related data – failure rate [FIT] with low demand rate according to SN 31920 | 100 FIT |
| Safety related data – device type according to ISO 13849-1 | 3 |
| Safety related data – overdimensioning according to ISO 13849-2 necessary | Yes |
| Safety related data – safety device type according to IEC 61508-2 | Type A |
| Safety related data – protection class IP on the front according to IEC 60529 | IP00; IP20 with box terminal/cover |
| Safety related data – touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front with box terminal/cover |
| Сертификация | 55.8 kg |
| Сертификация | 2.54 kg |
| Сертификация | 718 kg |
| Сертификация | -7.03 kg |
| Сертификация | 769 kg |