Siemens AG 3RT1456-6SP36
SIRIUS 3RT.4 contactors for weak or non-inductive loads (AC-1), 3-pole up to 2 650 A
Категории:
Технические характеристики
| product brand name | SIRIUS |
|---|---|
| product designation | Contactor |
| product type designation | 3RT14 |
| General technical data – size of contactor | S6 |
| General technical data – ● function module for communication | No |
| General technical data – ● auxiliary switch | Yes |
| General technical data – ● at AC in hot operating state | 86.4 W |
| General technical data – ● at AC in hot operating state per pole | 28.8 W |
| General technical data – ● without load current share typical | 2.8 W |
| General technical data – type of calculation of power loss current-dependent | quadratic |
| General technical data – ● of main circuit with degree of pollution 3 rated value | 1 000 V |
| General technical data – ● of auxiliary circuit with degree of pollution 3 rated value | 500 V |
| General technical data – ● of main circuit rated value | 8 kV |
| General technical data – ● of auxiliary circuit rated value | 6 kV |
| General technical data – ● at AC | 8,5 g / 5 ms, 4,2 g / 10 ms |
| General technical data – ● at DC | 8,5 g / 5 ms, 4,2 g / 10 ms |
| General technical data – ● at AC (2) | 13,4 g / 5 ms, 6,5 g / 10 ms |
| General technical data – ● at DC (2) | 13,4 g / 5 ms, 6,5 g / 10 ms |
| General technical data – ● of contactor typical | 10 000 000 |
| General technical data – ● of the contactor with added electronically optimized auxiliary switch block typical | 5 000 000 |
| General technical data – ● of the contactor with added auxiliary switch block typical | 10 000 000 |
| General technical data – reference code according to IEC 81346-2 | Q |
| General technical data – Substance Prohibitance (day/month/year) | 03/01/2017 |
| General technical data – SVHC substance name | Lead CAS-No. 7439-92-1 Lead monoxide (lead oxide) CAS-No. 1317-36-8 2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-one CAS-No. 71868-10-5 Melamine CAS-No. 108-78-1 |
| Масса | 3.223 kg |
| Ambient conditions – installation altitude at height above sea level maximum | 2 000 m |
| Ambient conditions – ● during operation | -25 ... +60 °C |
| Ambient conditions – ● during storage | -55 ... +80 °C |
| Ambient conditions – relative humidity minimum | 10 % |
| Ambient conditions – relative humidity at 55 °C according to IEC 60068-2-30 maximum | 95 % |
| Main circuit – number of poles for main current circuit | 3 |
| Main circuit – number of NO contacts for main contacts | 3 |
| Main circuit – number of NC contacts for main contacts | 0 |
| Напряжение питания | AC |
| Рабочая температура | 275 A |
| Рабочая температура | 250 A |
| Рабочая температура | 250 A |
| Main circuit – — at 400 V rated value | 97 A |
| Main circuit – — at 690 V rated value | 97 A |
| Main circuit – minimum cross-section in main circuit at maximum AC-1 rated value | 140 mm² |
| Main circuit – — at 24 V rated value | 250 A |
| Main circuit – — at 60 V rated value | 250 A |
| Main circuit – — at 110 V rated value | 18 A |
| Main circuit – — at 220 V rated value | 3.4 A |
| Main circuit – — at 440 V rated value | 0.8 A |
| Main circuit – — at 600 V rated value | 0.5 A |
| Main circuit – — at 24 V rated value (2) | 250 A |
| Main circuit – — at 60 V rated value (2) | 250 A |
| Main circuit – — at 110 V rated value (2) | 250 A |
| Main circuit – — at 220 V rated value (2) | 20 A |
| Main circuit – — at 440 V rated value (2) | 3.2 A |
| Main circuit – — at 600 V rated value (2) | 1.6 A |
| Main circuit – — at 24 V rated value (3) | 250 A |
| Main circuit – — at 60 V rated value (3) | 250 A |
| Main circuit – — at 110 V rated value (3) | 250 A |
| Main circuit – — at 220 V rated value (3) | 250 A |
| Main circuit – — at 440 V rated value (3) | 11.5 A |
| Main circuit – — at 600 V rated value (3) | 4 A |
| Main circuit – — at 24 V rated value (4) | 250 A |
| Main circuit – — at 60 V rated value (4) | 7.5 A |
| Main circuit – — at 110 V rated value (4) | 2.5 A |
| Main circuit – — at 220 V rated value (4) | 0.6 A |
| Main circuit – — at 440 V rated value (4) | 0.17 A |
| Main circuit – — at 600 V rated value (4) | 0.12 A |
| Main circuit – — at 24 V rated value (5) | 250 A |
| Main circuit – — at 60 V rated value (5) | 250 A |
| Main circuit – — at 110 V rated value (5) | 250 A |
| Main circuit – — at 220 V rated value (5) | 2.5 A |
| Main circuit – — at 440 V rated value (5) | 0.65 A |
| Main circuit – — at 600 V rated value (5) | 0.37 A |
| Main circuit – — at 24 V rated value (6) | 250 A |
| Main circuit – — at 60 V rated value (6) | 250 A |
| Main circuit – — at 110 V rated value (6) | 250 A |
| Main circuit – — at 220 V rated value (6) | 250 A |
| Main circuit – — at 440 V rated value (6) | 1.4 A |
| Main circuit – — at 600 V rated value (6) | 0.75 A |
| Main circuit – ● at AC | 1 000 1/h |
| Main circuit – ● at DC | 1 000 1/h |
| Main circuit – ● at AC-1 maximum | 200 1/h |
| Напряжение питания | AC/DC |
| Напряжение питания | AC/DC |
| Control circuit/ Control – ● at 50 Hz rated value | 200 ... 277 V |
| Control circuit/ Control – ● at 60 Hz rated value | 200 ... 277 V |
| Напряжение питания | 200 ... 277 V |
| Control circuit/ Control – ● initial value | 0.8 |
| Control circuit/ Control – ● full-scale value | 1.1 |
| Control circuit/ Control – ● at 50 Hz | 0.8 ... 1.1 |
| Control circuit/ Control – ● at 60 Hz | 0.8 ... 1.1 |
| Control circuit/ Control – type of PLC-control input according to IEC 60947-1 | Type 1 |
| Control circuit/ Control – consumed current at PLC-control input according to IEC 60947-1 maximum | 30 mA |
| Control circuit/ Control – design of the surge suppressor | with varistor |
| Control circuit/ Control – — at 50 Hz | 190 V·A |
| Control circuit/ Control – — at 60 Hz | 190 V·A |
| Control circuit/ Control – — at 60 Hz (2) | 280 V·A |
| Control circuit/ Control – — at 50 Hz (2) | 280 V·A |
| Control circuit/ Control – ● at 50 Hz (2) | 280 V·A |
| Control circuit/ Control – ● at 50 Hz (3) | 0.8 |
| Напряжение питания | 2.1 V·A |
| Напряжение питания | 2.8 V·A |
| Control circuit/ Control – — at 50 Hz (3) | 4.3 V·A |
| Control circuit/ Control – — at 60 Hz (3) | 4.3 V·A |
| Control circuit/ Control – — at 50 Hz (4) | 5.2 V·A |
| Control circuit/ Control – — at 60 Hz (4) | 5.2 V·A |
| Control circuit/ Control – ● at 50 Hz (4) | 4.4 V·A |
| Control circuit/ Control – ● at 50 Hz (5) | 0.5 |
| Control circuit/ Control – closing power of magnet coil at DC | 320 W |
| Control circuit/ Control – holding power of magnet coil at DC | 2.8 W |
| Control circuit/ Control – ● at AC | 60 ... 75 ms |
| Control circuit/ Control – ● at DC | 60 ... 75 ms |
| Control circuit/ Control – ● at AC (2) | 115 ... 130 ms |
| Control circuit/ Control – ● at DC (2) | 115 ... 130 ms |
| Control circuit/ Control – arcing time | 10 ... 15 ms |
| Control circuit/ Control – control version of the switch operating mechanism | Fail-safe PLC input (F-PLC-IN) |
| Auxiliary circuit – number of NC contacts for auxiliary contacts | 2 |
| Auxiliary circuit – ● attachable | 4 |
| Auxiliary circuit – ● instantaneous contact | 2 |
| Auxiliary circuit – number of NO contacts for auxiliary contacts | 2 |
| Auxiliary circuit – ● attachable (2) | 4 |
| Auxiliary circuit – ● instantaneous contact (2) | 2 |
| Auxiliary circuit – operational current at AC-12 maximum | 10 A |
| Auxiliary circuit – ● at 230 V rated value | 6 A |
| Auxiliary circuit – ● at 400 V rated value | 3 A |
| Auxiliary circuit – ● at 500 V rated value | 2 A |
| Auxiliary circuit – ● at 690 V rated value | 1 A |
| Auxiliary circuit – ● at 24 V rated value | 10 A |
| Auxiliary circuit – ● at 48 V rated value | 2 A |
| Auxiliary circuit – ● at 60 V rated value | 2 A |
| Auxiliary circuit – ● at 110 V rated value | 1 A |
| Auxiliary circuit – ● at 125 V rated value | 0.9 A |
| Auxiliary circuit – ● at 220 V rated value | 0.3 A |
| Auxiliary circuit – ● at 600 V rated value | 0.1 A |
| Auxiliary circuit – contact reliability of auxiliary contacts | 1 faulty switching per 100 million (17 V, 1 mA) |
| Short-circuit protection – design of the miniature circuit breaker for short-circuit protection of the auxiliary circuit up to 230 V | C characteristic: 10 A; 0.4 kA |
| Short-circuit protection – — with type of coordination 1 required | gG: 355 A (690 V, 100 kA) |
| Short-circuit protection – — with type of coordination 2 required | gR: 350 A (690 V, 100 kA) |
| Short-circuit protection – ● for short-circuit protection of the auxiliary switch required | gG: 10 A (500 V, 1 kA) |
| Installation/ mounting/ dimensions – mounting position | with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back |
| Installation/ mounting/ dimensions – fastening method side-by-side mounting | Yes |
| Installation/ mounting/ dimensions – fastening method | screw fixing |
| Installation/ mounting/ dimensions – height | 172 mm |
| Installation/ mounting/ dimensions – width | 120 mm |
| Installation/ mounting/ dimensions – depth | 170 mm |
| Installation/ mounting/ dimensions – — forwards | 20 mm |
| Installation/ mounting/ dimensions – — upwards | 10 mm |
| Installation/ mounting/ dimensions – — downwards | 10 mm |
| Installation/ mounting/ dimensions – — at the side | 0 mm |
| Installation/ mounting/ dimensions – — forwards (2) | 20 mm |
| Installation/ mounting/ dimensions – — upwards (2) | 10 mm |
| Installation/ mounting/ dimensions – — at the side (2) | 10 mm |
| Installation/ mounting/ dimensions – — downwards (2) | 10 mm |
| Installation/ mounting/ dimensions – — forwards (3) | 20 mm |
| Installation/ mounting/ dimensions – — upwards (3) | 10 mm |
| Installation/ mounting/ dimensions – — downwards (3) | 10 mm |
| Installation/ mounting/ dimensions – — at the side (3) | 10 mm |
| Connections/ Terminals – ● for main current circuit | Connection bar |
| Connections/ Terminals – ● for auxiliary and control circuit | screw-type terminals |
| Connections/ Terminals – ● at contactor for auxiliary contacts | Screw-type terminals |
| Connections/ Terminals – ● of magnet coil | screw terminal |
| Connections/ Terminals – width of connection bar | 17 mm |
| Connections/ Terminals – thickness of connection bar | 3 mm |
| Connections/ Terminals – diameter of holes | 9 mm |
| Connections/ Terminals – number of holes | 1 |
| Connections/ Terminals – ● for AWG cables for main contacts | 4 ... 250 kcmil |
| Connections/ Terminals – ● solid or stranded | 25 ... 120 mm² |
| Connections/ Terminals – ● stranded | 25 ... 120 mm² |
| Connections/ Terminals – ● solid or stranded (2) | 0.5 ... 4 mm² |
| Connections/ Terminals – ● finely stranded with core end processing | 0.5 ... 2.5 mm² |
| Connections/ Terminals – — solid | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²) |
| Connections/ Terminals – — solid or stranded | 2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²) |
| Connections/ Terminals – — finely stranded with core end processing | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
| Connections/ Terminals – ● for AWG cables for auxiliary contacts | 2x (20 ... 16), 2x (18 ... 14), 1x 12 |
| Connections/ Terminals – AWG number as coded connectable conductor cross section for auxiliary contacts | 18 ... 14 |
| Safety related data – ● mirror contact according to IEC 60947-4-1 | Yes |
| Safety related data – ● positively driven operation according to IEC 60947-5-1 | No |
| Safety related data – ● suitable for safety function | Yes |
| Safety related data – suitability for use safety-related switching OFF | Yes |
| Safety related data – safe state | off |
| Safety related data – stop category according to IEC 60204-1 | 0 |
| Safety related data – ● with low demand rate according to SN 31920 | 40 % |
| Safety related data – ● with high demand rate according to SN 31920 | 73 % |
| Safety related data – B10 value with high demand rate according to SN 31920 | 1 000 000 |
| Safety related data – failure rate [FIT] with low demand rate according to SN 31920 | 100 FIT |
| Safety related data – Safety Integrity Level (SIL) according to IEC 62061 | SIL 2 |
| Safety related data – PFHD with high demand rate according to IEC 62061 | 4.5E-7 1/h |
| Safety related data – performance level (PL) according to ISO 13849-1 | PL c |
| Safety related data – category according to ISO 13849-1 | 2 |
| Safety related data – device type according to ISO 13849-1 | 1 |
| Safety related data – overdimensioning according to ISO 13849-2 necessary | Yes |
| Safety related data – Safety Integrity Level (SIL) according to IEC 61508 | 2 |
| Safety related data – safety device type according to IEC 61508-2 | Type B |
| Safety related data – PFHD with high demand rate according to IEC 61508 | 4.5E-7 1/h |
| Safety related data – PFDavg with low demand rate according to IEC 61508 | 0.007 |
| Safety related data – Safe failure fraction (SFF) | 93 % |
| Safety related data – hardware fault tolerance according to IEC 61508 | 0 |
| Safety related data – T1 value of service life according to IEC 61508 | 20 a |
| Safety related data – protection class IP on the front according to IEC 60529 | IP00; IP20 with box terminal/cover |
| Safety related data – touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front with box terminal/cover |