3RT1476-2XJ46-0LA2

Siemens AG 3RT1476-2XJ46-0LA2

SIRIUS 3RT contactors with extended application range, 3-pole

Технические характеристики

product brand nameSIRIUS
product designationPower contactor
design of the productWith extended operating range
product type designation3RT14
General technical data – size of contactorS12
General technical data – ● function module for communicationNo
General technical data – ● auxiliary switchYes
General technical data – ● at AC in hot operating state165 W
General technical data – ● at AC in hot operating state per pole55 W
General technical data – ● without load current share typical3.6 W
General technical data – type of calculation of power loss current-dependentquadratic
General technical data – ● of main circuit with degree of pollution 3 rated value1 000 V
General technical data – ● of auxiliary circuit with degree of pollution 3 rated value500 V
General technical data – ● of main circuit rated value8 kV
General technical data – ● of auxiliary circuit rated value6 kV
Напряжение питания690 V
General technical data – shock resistance for railway applications according to EN 61373Category 1, Class B
General technical data – ● at DC8,5 g / 5 ms, 4,2 g / 10 ms
General technical data – ● at DC (2)13,4 g / 5 ms, 6,5 g / 10 ms
General technical data – ● of contactor typical10 000 000
General technical data – ● of the contactor with added electronically optimized auxiliary switch block typical5 000 000
General technical data – ● of the contactor with added auxiliary switch block typical10 000 000
General technical data – reference code according to IEC 81346-2Q
General technical data – Substance Prohibitance (day/month/year)09/06/2016
General technical data – SVHC substance nameLead CAS-No. 7439-92-1 Lead monoxide (lead oxide) CAS-No. 1317-36-8 2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-one CAS-No. 71868-10-5 Melamine CAS-No. 108-78-1
Масса10.199 kg
Ambient conditions – installation altitude at height above sea level maximum2 000 m
Ambient conditions – ● during operation-40 ... +70 °C
Ambient conditions – ● during storage-55 ... +80 °C
Ambient conditions – relative humidity minimum10 %
Ambient conditions – relative humidity at 55 °C according to IEC 60068-2-30 maximum95 %
Main circuit – number of poles for main current circuit3
Main circuit – number of NO contacts for main contacts3
Main circuit – number of NC contacts for main contacts0
Main circuit – ● at AC-3 rated value maximum690 V
Рабочая температура690 A
Рабочая температура690 A
Рабочая температура600 A
Main circuit – ● at AC-2 at 400 V rated value170 A
Main circuit – — at 400 V rated value170 A
Main circuit – — at 500 V rated value170 A
Main circuit – — at 690 V rated value170 A
Main circuit – ● at maximum AC-1 rated value480 mm²
Main circuit – ● at maximum Ith rated value480 mm²
Main circuit – — at 24 V rated value500 A
Main circuit – — at 110 V rated value33 A
Main circuit – — at 220 V rated value3.8 A
Main circuit – — at 440 V rated value0.9 A
Main circuit – — at 600 V rated value0.6 A
Main circuit – — at 24 V rated value (2)500 A
Main circuit – — at 110 V rated value (2)500 A
Main circuit – — at 220 V rated value (2)500 A
Main circuit – — at 440 V rated value (2)4 A
Main circuit – — at 600 V rated value (2)2 A
Main circuit – — at 24 V rated value (3)500 A
Main circuit – — at 110 V rated value (3)500 A
Main circuit – — at 220 V rated value (3)500 A
Main circuit – — at 440 V rated value (3)11 A
Main circuit – — at 600 V rated value (3)5.2 A
Main circuit – — at 24 V rated value (4)500 A
Main circuit – — at 110 V rated value (4)3 A
Main circuit – — at 220 V rated value (4)0.6 A
Main circuit – — at 440 V rated value (4)0.18 A
Main circuit – — at 600 V rated value (4)0.125 A
Main circuit – — at 24 V rated value (5)500 A
Main circuit – — at 110 V rated value (5)500 A
Main circuit – — at 220 V rated value (5)2.5 A
Main circuit – — at 440 V rated value (5)0.65 A
Main circuit – — at 600 V rated value (5)0.37 A
Main circuit – — at 24 V rated value (6)500 A
Main circuit – — at 110 V rated value (6)500 A
Main circuit – — at 220 V rated value (6)500 A
Main circuit – — at 440 V rated value (6)1.4 A
Main circuit – — at 600 V rated value (6)0.75 A
Main circuit – ● at AC-2 at 400 V rated value (2)90 kW
Main circuit – — at 230 V rated value160 kW
Main circuit – — at 400 V rated value (2)90 kW
Main circuit – — at 500 V rated value (2)110 kW
Main circuit – — at 690 V rated value (2)160 kW
Main circuit – ● limited to 1 s switching at zero current maximum7 484 A; Use minimum cross-section acc. to AC-1 rated value
Main circuit – ● limited to 5 s switching at zero current maximum7 484 A; Use minimum cross-section acc. to AC-1 rated value
Main circuit – ● limited to 10 s switching at zero current maximum5 978 A; Use minimum cross-section acc. to AC-1 rated value
Main circuit – ● limited to 30 s switching at zero current maximum3 765 A; Use minimum cross-section acc. to AC-1 rated value
Main circuit – ● limited to 60 s switching at zero current maximum2 887 A; Use minimum cross-section acc. to AC-1 rated value
Main circuit – ● at DC500 1/h
Main circuit – ● at AC-1 maximum600 1/h
Main circuit – ● at DC-1 maximum250 1/h
Ratings for railway applications – ● up to 40 °C according to IEC 60077 rated value690 A
Ratings for railway applications – ● up to 70 °C according to IEC 60077 rated value520 A
Напряжение питанияDC
Напряжение питанияDC
Напряжение питания72 V
Control circuit/ Control – ● initial value0.7
Control circuit/ Control – ● full-scale value1.25
Control circuit/ Control – consumed current at PLC-control input according to IEC 60947-1 maximum2 mA
Напряжение питания24 ... 110 V
Control circuit/ Control – design of the surge suppressorwith varistor
Control circuit/ Control – closing power of magnet coil at DC800 W
Control circuit/ Control – holding power of magnet coil at DC3.6 W
Control circuit/ Control – ● at DC60 ... 90 ms
Control circuit/ Control – ● at DC (2)80 ... 100 ms
Control circuit/ Control – arcing time10 ... 15 ms
Control circuit/ Control – control version of the switch operating mechanismPLC-IN or Standard A1 - A2 (adjustable)
Auxiliary circuit – number of NC contacts for auxiliary contacts2
Auxiliary circuit – ● instantaneous contact2
Auxiliary circuit – number of NO contacts for auxiliary contacts2
Auxiliary circuit – ● instantaneous contact (2)2
Auxiliary circuit – operational current at AC-12 maximum10 A
Auxiliary circuit – ● at 230 V rated value6 A
Auxiliary circuit – ● at 400 V rated value3 A
Auxiliary circuit – ● at 500 V rated value2 A
Auxiliary circuit – ● at 24 V rated value10 A
Auxiliary circuit – ● at 48 V rated value6 A
Auxiliary circuit – ● at 60 V rated value6 A
Auxiliary circuit – ● at 110 V rated value3 A
Auxiliary circuit – ● at 125 V rated value2 A
Auxiliary circuit – ● at 220 V rated value1 A
Auxiliary circuit – ● at 600 V rated value0.15 A
Auxiliary circuit – ● at 24 V rated value (2)6 A
Auxiliary circuit – ● at 48 V rated value (2)2 A
Auxiliary circuit – ● at 60 V rated value (2)2 A
Auxiliary circuit – ● at 110 V rated value (2)1 A
Auxiliary circuit – ● at 125 V rated value (2)0.9 A
Auxiliary circuit – ● at 220 V rated value (2)0.3 A
Auxiliary circuit – ● at 600 V rated value (2)0.1 A
UL/CSA ratings – ● at 480 V rated value180 A
UL/CSA ratings – ● at 600 V rated value192 A
UL/CSA ratings – — at 220/230 V rated value75 hp
UL/CSA ratings – — at 460/480 V rated value150 hp
UL/CSA ratings – — at 575/600 V rated value200 hp
UL/CSA ratings – contact rating of auxiliary contacts according to ULA600 / Q600
Short-circuit protection – design of the miniature circuit breaker for short-circuit protection of the auxiliary circuit up to 230 VC characteristic: 10 A; 0.4 kA
Short-circuit protection – — with type of coordination 1 requiredgG: 800 A (690 V, 50 kA)
Short-circuit protection – — with type of coordination 2 requiredgR: 710 A (690 V, 100 kA)
Short-circuit protection – ● for short-circuit protection of the auxiliary switch requiredgG: 10 A (500 V, 1 kA)
Installation/ mounting/ dimensions – mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Installation/ mounting/ dimensions – fastening method side-by-side mountingYes
Installation/ mounting/ dimensions – fastening methodscrew fixing
Installation/ mounting/ dimensions – height214 mm
Installation/ mounting/ dimensions – width160 mm
Installation/ mounting/ dimensions – depth225 mm
Installation/ mounting/ dimensions – — forwards20 mm
Installation/ mounting/ dimensions – — upwards10 mm
Installation/ mounting/ dimensions – — downwards10 mm
Installation/ mounting/ dimensions – — at the side10 mm
Installation/ mounting/ dimensions – — forwards (2)20 mm
Installation/ mounting/ dimensions – — upwards (2)10 mm
Installation/ mounting/ dimensions – — at the side (2)10 mm
Installation/ mounting/ dimensions – — downwards (2)10 mm
Installation/ mounting/ dimensions – — forwards (3)20 mm
Installation/ mounting/ dimensions – — upwards (3)10 mm
Installation/ mounting/ dimensions – — downwards (3)10 mm
Installation/ mounting/ dimensions – — at the side (3)10 mm
Connections/ Terminals – ● for main current circuitscrew-type terminals
Connections/ Terminals – ● for auxiliary and control circuitspring-loaded terminals
Connections/ Terminals – width of connection bar25 mm
Connections/ Terminals – thickness of connection bar6 mm
Connections/ Terminals – diameter of holes11 mm
Connections/ Terminals – number of holes1
Connections/ Terminals – — solid or stranded2x (70 ... 240 mm²)
Connections/ Terminals – ● for AWG cables for main contacts2/0 ... 500 kcmil
Connections/ Terminals – — solid2x (0.25 ... 2.5 mm²)
Connections/ Terminals – — solid or stranded (2)2x (0,25 ... 2,5 mm²)
Connections/ Terminals – — finely stranded with core end processing2x (0.25 ... 1.5 mm²)
Connections/ Terminals – — finely stranded without core end processing2x (0.25 ... 2.5 mm²)
Connections/ Terminals – ● for AWG cables for auxiliary contacts2x (24 ... 14)
Connections/ Terminals – AWG number as coded connectable conductor cross section for auxiliary contacts24 ... 14
Safety related data – ● mirror contact according to IEC 60947-4-1Yes
Safety related data – ● positively driven operation according to IEC 60947-5-1No
Safety related data – protection class IP on the front according to IEC 60529IP00; IP20 with box terminal/cover
Safety related data – touch protection on the front according to IEC 60529finger-safe, for vertical contact from the front with box terminal/cover
Communication/ Protocol – product function bus communicationNo