Siemens AG 3RT2015-1AF01
Контактор Siemens 3RT2015-1AF01, серия 3RT2. Подбор по артикулу, поставка под заказ: цену и срок уточняйте через запрос на поставку.
Категории:
Технические характеристики
| Data sheet designation | power contactor, AC-3e/AC-3, 7 A, 3 kW / 400 V, 3-pole, 110 V AC, 50/60 Hz, auxiliary contacts: 1 NO, screw terminal, size: S00 |
|---|---|
| product brand name | SIRIUS |
| product designation | Power contactor |
| product type designation | 3RT2 |
| General technical data / size of contactor | S00 |
| General technical data / product extension / function module for communication | No |
| General technical data / product extension / auxiliary switch | Yes |
| General technical data / power loss [W] for rated value of the current / at AC in hot operating state | 0.6 W |
| General technical data / power loss [W] for rated value of the current / at AC in hot operating state per pole | 0.2 W |
| General technical data / power loss [W] for rated value of the current / without load current share typical | 1.1 W |
| General technical data / type of calculation of power loss current-dependent | quadratic |
| Напряжение питания | 690 V |
| Напряжение питания | 690 V |
| Напряжение питания | 6 kV |
| General technical data / shock resistance with sine pulse / at AC | 10,5 g / 5 ms, 6,6 g / 10 ms |
| General technical data / mechanical service life (operating cycles) / of contactor typical | 30 000 000 |
| General technical data / mechanical service life (operating cycles) / of the contactor with added electronically optimized | 5 000 000 |
| General technical data / mechanical service life (operating cycles) / of the contactor with added auxiliary switch block typical | 10 000 000 |
| General technical data / reference code according to IEC 81346-2 | Q |
| General technical data / Substance Prohibitance (day/month/year) | 10/01/2009 |
| Масса | 217.8 g |
| Ambient conditions / installation altitude at height above sea level maximum | 2 000 m |
| Рабочая температура | -25 ... +60 °C |
| Main circuit / number of NO contacts for main contacts | 3 |
| Main circuit / number of NC contacts for main contacts | 0 |
| Напряжение питания | 690 V |
| Напряжение питания | 690 V |
| Рабочая температура | 18 A |
| Рабочая температура | 18 A |
| Main circuit / operational current / at AC-3 / at 500 V rated value | 6 A |
| Main circuit / operational current / at AC-3 / at 690 V rated value | 4.9 A |
| Main circuit / operational current / at AC-3e / at 400 V rated value | 7 A |
| Main circuit / operational current / at AC-3e / at 500 V rated value | 6 A |
| Main circuit / operational current / at AC-3e / at 690 V rated value | 4.9 A |
| Main circuit / operational current / at AC-4 at 400 V rated value | 6.5 A |
| Main circuit / operational current / at AC-5a up to 690 V rated value | 15.8 A |
| Main circuit / operational current / at AC-5b up to 400 V rated value | 5.8 A |
| Main circuit / operational current / at AC-6a / up to 230 V for current peak value n=20 rated value | 4 A |
| Main circuit / operational current / at AC-6a / up to 400 V for current peak value n=20 rated value | 4 A |
| Main circuit / operational current / at AC-6a / up to 500 V for current peak value n=20 rated value | 3.8 A |
| Main circuit / operational current / at AC-6a / up to 690 V for current peak value n=20 rated value | 3.6 A |
| Main circuit / operational current / at AC-6a / up to 230 V for current peak value n=30 rated value | 2.7 A |
| Main circuit / operational current / at AC-6a / up to 400 V for current peak value n=30 rated value | 2.7 A |
| Main circuit / operational current / at AC-6a / up to 500 V for current peak value n=30 rated value | 2.5 A |
| Main circuit / AC-4 / at 690 V rated value | 1.8 A |
| Main circuit / operational current / at 1 current path at DC-1 / at 24 V rated value | 15 A |
| Main circuit / operational current / at 1 current path at DC-1 / at 60 V rated value | 15 A |
| Main circuit / operational current / at 1 current path at DC-1 / at 110 V rated value | 1.5 A |
| Main circuit / operational current / at 1 current path at DC-1 / at 220 V rated value | 0.6 A |
| Main circuit / operational current / at 1 current path at DC-1 / at 440 V rated value | 0.42 A |
| Main circuit / operational current / at 1 current path at DC-1 / at 600 V rated value | 0.42 A |
| Main circuit / operational current / with 2 current paths in series at DC-1 / at 24 V rated value | 15 A |
| Main circuit / operational current / with 2 current paths in series at DC-1 / at 60 V rated value | 15 A |
| Main circuit / operational current / with 2 current paths in series at DC-1 / at 110 V rated value | 8.4 A |
| Main circuit / operational current / with 2 current paths in series at DC-1 / at 220 V rated value | 1.2 A |
| Main circuit / operational current / with 2 current paths in series at DC-1 / at 440 V rated value | 0.6 A |
| Main circuit / operational current / with 2 current paths in series at DC-1 / at 600 V rated value | 0.5 A |
| Main circuit / operational current / with 3 current paths in series at DC-1 / at 24 V rated value | 15 A |
| Main circuit / operational current / with 3 current paths in series at DC-1 / at 60 V rated value | 15 A |
| Main circuit / operational current / with 3 current paths in series at DC-1 / at 110 V rated value | 15 A |
| Main circuit / operational current / with 3 current paths in series at DC-1 / at 220 V rated value | 15 A |
| Main circuit / operational current / with 3 current paths in series at DC-1 / at 440 V rated value | 0.9 A |
| Main circuit / operational current / with 3 current paths in series at DC-1 / at 600 V rated value | 0.7 A |
| Main circuit / operational current / at 1 current path at DC-3 at DC-5 / at 24 V rated value | 15 A |
| Main circuit / operational current / at 1 current path at DC-3 at DC-5 / at 60 V rated value | 0.35 A |
| Main circuit / operational current / at 1 current path at DC-3 at DC-5 / at 110 V rated value | 0.1 A |
| Main circuit / operational current / with 2 current paths in series at DC-3 at DC-5 / at 24 V rated value | 15 A |
| Main circuit / operational current / with 2 current paths in series at DC-3 at DC-5 / at 60 V rated value | 3.5 A |
| Main circuit / operational current / with 2 current paths in series at DC-3 at DC-5 / at 110 V rated value | 0.25 A |
| Main circuit / operational current / with 3 current paths in series at DC-3 at DC-5 / at 24 V rated value | 15 A |
| Main circuit / operational current / with 3 current paths in series at DC-3 at DC-5 / at 60 V rated value | 15 A |
| Main circuit / operational current / with 3 current paths in series at DC-3 at DC-5 / at 110 V rated value | 15 A |
| Main circuit / operational current / with 3 current paths in series at DC-3 at DC-5 / at 220 V rated value | 1.2 A |
| Main circuit / operational current / with 3 current paths in series at DC-3 at DC-5 / at 440 V rated value | 0.14 A |
| Main circuit / operational current / with 3 current paths in series at DC-3 at DC-5 / at 600 V rated value | 0.14 A |
| Main circuit / operating power / at AC-3 / at 230 V rated value | 1.5 kW |
| Main circuit / operating power / at AC-3 / at 400 V rated value | 3 kW |
| Main circuit / operating power / at AC-3 / at 500 V rated value | 3 kW |
| Main circuit / operating power / at AC-3 / at 690 V rated value | 4 kW |
| Main circuit / operating power / at AC-3e / at 230 V rated value | 1.5 kW |
| Main circuit / operating power / at AC-3e / at 400 V rated value | 3 kW |
| Main circuit / operating apparent power at AC-6a / up to 230 V for current peak value n=20 rated value | 1.5 kVA |
| Main circuit / operating apparent power at AC-6a / up to 400 V for current peak value n=20 rated value | 2.7 kVA |
| Main circuit / operating apparent power at AC-6a / up to 500 V for current peak value n=20 rated value | 3.3 kVA |
| Main circuit / operating apparent power at AC-6a / up to 690 V for current peak value n=20 rated value | 4.3 kVA |
| Main circuit / operating apparent power at AC-6a / up to 230 V for current peak value n=30 rated value | 1 kVA |
| Main circuit / operating apparent power at AC-6a / up to 400 V for current peak value n=30 rated value | 1.8 kVA |
| Main circuit / 40 °C / limited to 5 s switching at zero current maximum | 86 A; Use minimum cross-section acc. to AC-1 rated value |
| Main circuit / 40 °C / limited to 10 s switching at zero current maximum | 67 A; Use minimum cross-section acc. to AC-1 rated value |
| Main circuit / 40 °C / limited to 30 s switching at zero current maximum | 52 A; Use minimum cross-section acc. to AC-1 rated value |
| Main circuit / 40 °C / limited to 60 s switching at zero current maximum | 43 A; Use minimum cross-section acc. to AC-1 rated value |
| Main circuit / no-load switching frequency / at AC | 10 000 1/h |
| Main circuit / operating frequency / at AC-1 maximum | 1 000 1/h |
| Main circuit / operating frequency / at AC-2 maximum | 750 1/h |
| Main circuit / operating frequency / at AC-3 maximum | 750 1/h |
| Main circuit / operating frequency / at AC-3e / maximum | 750 1/h |
| Main circuit / operating frequency / at AC-4 maximum | 250 1/h |
| Напряжение питания | AC |
| Control circuit/ Control / magnet coil at AC / at 60 Hz | 0.85 ... 1.1 |
| Control circuit/ Control / apparent pick-up power of magnet coil at AC / at 50 Hz | 27 V·A |
| Control circuit/ Control / apparent pick-up power of magnet coil at AC / at 60 Hz | 24.3 V·A |
| Control circuit/ Control / inductive power factor with closing power of the coil / at 50 Hz | 0.8 |
| Control circuit/ Control / inductive power factor with closing power of the coil / at 60 Hz | 0.75 |
| Control circuit/ Control / apparent holding power of magnet coil at AC / at 50 Hz | 4.2 V·A |
| Control circuit/ Control / apparent holding power of magnet coil at AC / at 60 Hz | 3.3 V·A |
| Control circuit/ Control / inductive power factor with the holding power of the coil / at 50 Hz | 0.25 |
| Control circuit/ Control / inductive power factor with the holding power of the coil / at 60 Hz | 0.25 |
| Control circuit/ Control / closing delay / at AC | 9 ... 35 ms |
| Control circuit/ Control / opening delay / at AC | 4 ... 15 ms |
| Control circuit/ Control / arcing time | 10 ... 15 ms |
| Control circuit/ Control / control version of the switch operating mechanism | Standard A1 - A2 |
| Auxiliary circuit / operational current at AC-15 / at 230 V rated value | 10 A |
| Auxiliary circuit / operational current at AC-15 / at 400 V rated value | 3 A |
| Auxiliary circuit / operational current at AC-15 / at 500 V rated value | 2 A |
| Auxiliary circuit / operational current at AC-15 / at 690 V rated value | 1 A |
| Auxiliary circuit / operational current at DC-12 / at 24 V rated value | 10 A |
| Auxiliary circuit / operational current at DC-12 / at 48 V rated value | 6 A |
| Auxiliary circuit / operational current at DC-12 / at 60 V rated value | 6 A |
| Auxiliary circuit / operational current at DC-12 / at 110 V rated value | 3 A |
| Auxiliary circuit / operational current at DC-12 / at 125 V rated value | 2 A |
| Auxiliary circuit / operational current at DC-12 / at 220 V rated value | 1 A |
| Auxiliary circuit / operational current at DC-12 / at 600 V rated value | 0.15 A |
| Auxiliary circuit / operational current at DC-13 / at 24 V rated value | 10 A |
| Auxiliary circuit / operational current at DC-13 / at 48 V rated value | 2 A |
| Auxiliary circuit / operational current at DC-13 / at 60 V rated value | 2 A |
| Auxiliary circuit / operational current at DC-13 / at 110 V rated value | 1 A |
| Auxiliary circuit / operational current at DC-13 / at 125 V rated value | 0.9 A |
| Auxiliary circuit / operational current at DC-13 / at 220 V rated value | 0.3 A |
| Auxiliary circuit / operational current at DC-13 / at 600 V rated value | 0.1 A |
| Auxiliary circuit / contact reliability of auxiliary contacts | 1 faulty switching per 100 million (17 V, 1 mA) |
| UL/CSA ratings / full-load current (FLA) for 3-phase AC motor / at 600 V rated value | 6.1 A |
| UL/CSA ratings / yielded mechanical performance [hp] / for single-phase AC motor / at 110/120 V rated value | 0.25 hp |
| UL/CSA ratings / yielded mechanical performance [hp] / for single-phase AC motor / at 230 V rated value | 0.75 hp |
| UL/CSA ratings / yielded mechanical performance [hp] / for 3-phase AC motor / at 200/208 V rated value | 1.5 hp |
| UL/CSA ratings / yielded mechanical performance [hp] / for 3-phase AC motor / at 220/230 V rated value | 2 hp |
| UL/CSA ratings / yielded mechanical performance [hp] / for 3-phase AC motor / at 460/480 V rated value | 3 hp |
| UL/CSA ratings / yielded mechanical performance [hp] / for 3-phase AC motor / at 575/600 V rated value | 5 hp |
| UL/CSA ratings / contact rating of auxiliary contacts according to UL | A600 / Q600 |
| Short-circuit protection / design of the fuse link / for short-circuit protection of the main circuit / with type of coordination 1 required | gG: 35 A (690 V,100 kA), aM: 20 A (690 V,100 kA), BS88: 35 A (415 V,80 kA) |
| Short-circuit protection / design of the fuse link / for short-circuit protection of the main circuit / with type of coordination 2 required | gG: 20 A (690 V, 100 kA), aM: 16 A (690 V, 100 kA), BS88: 20 A (415 V, 80 kA) |
| Short-circuit protection / design of the fuse link / for short-circuit protection of the auxiliary switch required | gG: 10 A (500 V, 1 kA) |
| Installation/ mounting/ dimensions / height | 58 mm |
| Installation/ mounting/ dimensions / width | 45 mm |
| Installation/ mounting/ dimensions / depth | 73 mm |
| Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / forwards | 10 mm |
| Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / upwards | 10 mm |
| Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / downwards | 10 mm |
| Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / at the side | 0 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts / forwards | 10 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts / upwards | 10 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts / at the side | 6 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts / downwards | 10 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts / forwards | 10 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts / upwards | 10 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts / downwards | 10 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts / at the side | 6 mm |
| Connections/ Terminals / type of electrical connection / for main current circuit | screw-type terminals |
| Connections/ Terminals / type of electrical connection / for auxiliary and control circuit | screw-type terminals |
| Connections/ Terminals / type of electrical connection / at contactor for auxiliary contacts | Screw-type terminals |
| Connections/ Terminals / type of electrical connection / of magnet coil | screw terminal |
| Connections/ Terminals / type of connectable conductor cross-sections / for main contacts / solid | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm² |
| Connections/ Terminals / type of connectable conductor cross-sections / for main contacts / solid or stranded | 2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), 2x 4 mm² |
| Connections/ Terminals / type of connectable conductor cross-sections / for main contacts / finely stranded with core end processing | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
| Connections/ Terminals / type of connectable conductor cross-sections / for AWG cables for main contacts | 2x (20 ... 16), 2x (18 ... 14), 2x 12 |
| Connections/ Terminals / connectable conductor cross-section for main contacts / solid | 0.5 ... 4 mm² |
| Connections/ Terminals / connectable conductor cross-section for main contacts / stranded | 0.5 ... 4 mm² |
| Connections/ Terminals / connectable conductor cross-section for main contacts / finely stranded with core end processing | 0.5 ... 2.5 mm² |
| Connections/ Terminals / connectable conductor cross-section for auxiliary contacts / solid or stranded | 0.5 ... 4 mm² |
| Connections/ Terminals / connectable conductor cross-section for auxiliary contacts / finely stranded with core end processing | 0.5 ... 2.5 mm² |
| Connections/ Terminals / type of connectable conductor cross-sections / for auxiliary contacts / solid or stranded | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm² |
| Connections/ Terminals / type of connectable conductor cross-sections / for auxiliary contacts / finely stranded with core end processing | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
| Safety related data / product function / mirror contact according to IEC 60947-4-1 | Yes; with 3RH29 |
| Safety related data / product function / positively driven operation according to IEC 60947-5- | No |
| Safety related data / product function / suitable for safety function | Yes |
| Safety related data / suitability for use safety-related switching OFF | Yes |
| Safety related data / service life maximum | 20 a |
| Safety related data / test wear-related service life necessary | Yes |
| Safety related data / proportion of dangerous failures / with low demand rate according to SN 31920 | 40 % |
| Safety related data / proportion of dangerous failures / with high demand rate according to SN 31920 | 73 % |
| Сертификация | 1.18 kg |
| Сертификация | 38.5 kg |
| Сертификация | -0.155 kg |