Технические характеристики

Data sheet designationpower contactor, AC-3e/AC-3, 7 A, 3 kW / 400 V, 3-pole, 380 V AC, 50/60 Hz, auxiliary contacts: 1 NO, screw terminal, size: S00
product brand nameSIRIUS
product designationPower contactor
product type designation3RT2
General technical data / size of contactorS00
General technical data / product extension / function module for communicationNo
General technical data / product extension / auxiliary switchYes
General technical data / power loss [W] for rated value of the current / at AC in hot operating state0.6 W
General technical data / power loss [W] for rated value of the current / at AC in hot operating state per pole0.2 W
General technical data / power loss [W] for rated value of the current / without load current share typical1.1 W
General technical data / type of calculation of power loss current-dependentquadratic
Напряжение питания690 V
Напряжение питания690 V
Напряжение питания6 kV
General technical data / shock resistance with sine pulse / at AC10,5 g / 5 ms, 6,6 g / 10 ms
General technical data / mechanical service life (operating cycles) / of contactor typical30 000 000
General technical data / mechanical service life (operating cycles) / of the contactor with added electronically optimized5 000 000
General technical data / mechanical service life (operating cycles) / of the contactor with added auxiliary switch block typical10 000 000
General technical data / reference code according to IEC 81346-2Q
General technical data / Substance Prohibitance (day/month/year)10/01/2009
Масса0.218 kg
Ambient conditions / installation altitude at height above sea level maximum2 000 m
Рабочая температура-25 ... +60 °C
Main circuit / number of NO contacts for main contacts3
Main circuit / number of NC contacts for main contacts0
Напряжение питания690 V
Напряжение питания690 V
Рабочая температура18 A
Рабочая температура18 A
Main circuit / operational current / at AC-3 / at 500 V rated value6 A
Main circuit / operational current / at AC-3 / at 690 V rated value4.9 A
Main circuit / operational current / at AC-3e / at 400 V rated value7 A
Main circuit / operational current / at AC-3e / at 500 V rated value6 A
Main circuit / operational current / at AC-3e / at 690 V rated value4.9 A
Main circuit / operational current / at AC-4 at 400 V rated value6.5 A
Main circuit / operational current / at AC-5a up to 690 V rated value15.8 A
Main circuit / operational current / at AC-5b up to 400 V rated value5.8 A
Main circuit / operational current / at AC-6a / up to 230 V for current peak value n=20 rated value4 A
Main circuit / operational current / at AC-6a / up to 400 V for current peak value n=20 rated value4 A
Main circuit / operational current / at AC-6a / up to 500 V for current peak value n=20 rated value3.8 A
Main circuit / operational current / at AC-6a / up to 690 V for current peak value n=20 rated value3.6 A
Main circuit / operational current / at AC-6a / up to 230 V for current peak value n=30 rated value2.7 A
Main circuit / operational current / at AC-6a / up to 400 V for current peak value n=30 rated value2.7 A
Main circuit / operational current / at AC-6a / up to 500 V for current peak value n=30 rated value2.5 A
Main circuit / AC-4 / at 690 V rated value1.8 A
Main circuit / operational current / at 1 current path at DC-1 / at 24 V rated value15 A
Main circuit / operational current / at 1 current path at DC-1 / at 60 V rated value15 A
Main circuit / operational current / at 1 current path at DC-1 / at 110 V rated value1.5 A
Main circuit / operational current / at 1 current path at DC-1 / at 220 V rated value0.6 A
Main circuit / operational current / at 1 current path at DC-1 / at 440 V rated value0.42 A
Main circuit / operational current / at 1 current path at DC-1 / at 600 V rated value0.42 A
Main circuit / operational current / with 2 current paths in series at DC-1 / at 24 V rated value15 A
Main circuit / operational current / with 2 current paths in series at DC-1 / at 60 V rated value15 A
Main circuit / operational current / with 2 current paths in series at DC-1 / at 110 V rated value8.4 A
Main circuit / operational current / with 2 current paths in series at DC-1 / at 220 V rated value1.2 A
Main circuit / operational current / with 2 current paths in series at DC-1 / at 440 V rated value0.6 A
Main circuit / operational current / with 2 current paths in series at DC-1 / at 600 V rated value0.5 A
Main circuit / operational current / with 3 current paths in series at DC-1 / at 24 V rated value15 A
Main circuit / operational current / with 3 current paths in series at DC-1 / at 60 V rated value15 A
Main circuit / operational current / with 3 current paths in series at DC-1 / at 110 V rated value15 A
Main circuit / operational current / with 3 current paths in series at DC-1 / at 220 V rated value15 A
Main circuit / operational current / with 3 current paths in series at DC-1 / at 440 V rated value0.9 A
Main circuit / operational current / with 3 current paths in series at DC-1 / at 600 V rated value0.7 A
Main circuit / operational current / at 1 current path at DC-3 at DC-5 / at 24 V rated value15 A
Main circuit / operational current / at 1 current path at DC-3 at DC-5 / at 60 V rated value0.35 A
Main circuit / operational current / at 1 current path at DC-3 at DC-5 / at 110 V rated value0.1 A
Main circuit / operational current / with 2 current paths in series at DC-3 at DC-5 / at 24 V rated value15 A
Main circuit / operational current / with 2 current paths in series at DC-3 at DC-5 / at 60 V rated value3.5 A
Main circuit / operational current / with 2 current paths in series at DC-3 at DC-5 / at 110 V rated value0.25 A
Main circuit / operational current / with 3 current paths in series at DC-3 at DC-5 / at 24 V rated value15 A
Main circuit / operational current / with 3 current paths in series at DC-3 at DC-5 / at 60 V rated value15 A
Main circuit / operational current / with 3 current paths in series at DC-3 at DC-5 / at 110 V rated value15 A
Main circuit / operational current / with 3 current paths in series at DC-3 at DC-5 / at 220 V rated value1.2 A
Main circuit / operational current / with 3 current paths in series at DC-3 at DC-5 / at 440 V rated value0.14 A
Main circuit / operational current / with 3 current paths in series at DC-3 at DC-5 / at 600 V rated value0.14 A
Main circuit / operating power / at AC-2 at 400 V rated value3 kW
Main circuit / operating power / at AC-3 / at 230 V rated value1.5 kW
Main circuit / operating power / at AC-3 / at 400 V rated value3 kW
Main circuit / operating power / at AC-3 / at 500 V rated value3 kW
Main circuit / operating power / at AC-3 / at 690 V rated value4 kW
Main circuit / operating power / at AC-3e / at 230 V rated value1.5 kW
Main circuit / operating power / at AC-3e / at 400 V rated value3 kW
Main circuit / operating apparent power at AC-6a / up to 230 V for current peak value n=20 rated value1.5 kVA
Main circuit / operating apparent power at AC-6a / up to 400 V for current peak value n=20 rated value2.7 kVA
Main circuit / operating apparent power at AC-6a / up to 500 V for current peak value n=20 rated value3.3 kVA
Main circuit / operating apparent power at AC-6a / up to 690 V for current peak value n=20 rated value4.3 kVA
Main circuit / operating apparent power at AC-6a / up to 230 V for current peak value n=30 rated value1 kVA
Main circuit / operating apparent power at AC-6a / up to 400 V for current peak value n=30 rated value1.8 kVA
Main circuit / 40 °C / limited to 5 s switching at zero current maximum86 A; Use minimum cross-section acc. to AC-1 rated value
Main circuit / 40 °C / limited to 10 s switching at zero current maximum67 A; Use minimum cross-section acc. to AC-1 rated value
Main circuit / 40 °C / limited to 30 s switching at zero current maximum52 A; Use minimum cross-section acc. to AC-1 rated value
Main circuit / 40 °C / limited to 60 s switching at zero current maximum43 A; Use minimum cross-section acc. to AC-1 rated value
Main circuit / no-load switching frequency / at AC10 000 1/h
Main circuit / operating frequency / at AC-1 maximum1 000 1/h
Main circuit / operating frequency / at AC-2 maximum750 1/h
Main circuit / operating frequency / at AC-3 maximum750 1/h
Main circuit / operating frequency / at AC-3e / maximum750 1/h
Main circuit / operating frequency / at AC-4 maximum250 1/h
Напряжение питанияAC
Control circuit/ Control / magnet coil at AC / at 60 Hz0.85 ... 1.1
Control circuit/ Control / apparent pick-up power of magnet coil at AC / at 50 Hz27 V·A
Control circuit/ Control / apparent pick-up power of magnet coil at AC / at 60 Hz24.3 V·A
Control circuit/ Control / inductive power factor with closing power of the coil / at 50 Hz0.8
Control circuit/ Control / inductive power factor with closing power of the coil / at 60 Hz0.75
Control circuit/ Control / apparent holding power of magnet coil at AC / at 50 Hz4.2 V·A
Control circuit/ Control / apparent holding power of magnet coil at AC / at 60 Hz3.3 V·A
Control circuit/ Control / inductive power factor with the holding power of the coil / at 50 Hz0.25
Control circuit/ Control / inductive power factor with the holding power of the coil / at 60 Hz0.25
Control circuit/ Control / closing delay / at AC9 ... 35 ms
Control circuit/ Control / opening delay / at AC4 ... 15 ms
Control circuit/ Control / arcing time10 ... 15 ms
Control circuit/ Control / control version of the switch operating mechanismStandard A1 - A2
Auxiliary circuit / operational current at AC-15 / at 230 V rated value10 A
Auxiliary circuit / operational current at AC-15 / at 400 V rated value3 A
Auxiliary circuit / operational current at AC-15 / at 500 V rated value2 A
Auxiliary circuit / operational current at AC-15 / at 690 V rated value1 A
Auxiliary circuit / operational current at DC-12 / at 24 V rated value10 A
Auxiliary circuit / operational current at DC-12 / at 48 V rated value6 A
Auxiliary circuit / operational current at DC-12 / at 60 V rated value6 A
Auxiliary circuit / operational current at DC-12 / at 110 V rated value3 A
Auxiliary circuit / operational current at DC-12 / at 125 V rated value2 A
Auxiliary circuit / operational current at DC-12 / at 220 V rated value1 A
Auxiliary circuit / operational current at DC-12 / at 600 V rated value0.15 A
Auxiliary circuit / operational current at DC-13 / at 24 V rated value10 A
Auxiliary circuit / operational current at DC-13 / at 48 V rated value2 A
Auxiliary circuit / operational current at DC-13 / at 60 V rated value2 A
Auxiliary circuit / operational current at DC-13 / at 110 V rated value1 A
Auxiliary circuit / operational current at DC-13 / at 125 V rated value0.9 A
Auxiliary circuit / operational current at DC-13 / at 220 V rated value0.3 A
Auxiliary circuit / operational current at DC-13 / at 600 V rated value0.1 A
Auxiliary circuit / contact reliability of auxiliary contacts1 faulty switching per 100 million (17 V, 1 mA)
UL/CSA ratings / at 480 V rated value4.8 A
UL/CSA ratings / at 600 V rated value6.1 A
UL/CSA ratings / yielded mechanical performance [hp] / for single-phase AC motor / at 110/120 V rated value0.25 hp
UL/CSA ratings / yielded mechanical performance [hp] / for single-phase AC motor / at 230 V rated value0.75 hp
UL/CSA ratings / yielded mechanical performance [hp] / for 3-phase AC motor / at 200/208 V rated value1.5 hp
UL/CSA ratings / yielded mechanical performance [hp] / for 3-phase AC motor / at 220/230 V rated value2 hp
UL/CSA ratings / yielded mechanical performance [hp] / for 3-phase AC motor / at 460/480 V rated value3 hp
UL/CSA ratings / yielded mechanical performance [hp] / for 3-phase AC motor / at 575/600 V rated value5 hp
UL/CSA ratings / contact rating of auxiliary contacts according to ULA600 / Q600
Short-circuit protection / design of the fuse link / for short-circuit protection of the main circuit / with type of coordination 1 requiredgG: 35 A (690 V,100 kA), aM: 20 A (690 V,100 kA), BS88: 35 A (415 V,80 kA)
Short-circuit protection / design of the fuse link / for short-circuit protection of the main circuit / with type of coordination 2 requiredgG: 20 A (690 V, 100 kA), aM: 16 A (690 V, 100 kA), BS88: 20 A (415 V, 80 kA)
Short-circuit protection / design of the fuse link / for short-circuit protection of the auxiliary switch requiredgG: 10 A (500 V, 1 kA)
Installation/ mounting/ dimensions / height58 mm
Installation/ mounting/ dimensions / width45 mm
Installation/ mounting/ dimensions / depth73 mm
Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / forwards10 mm
Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / upwards10 mm
Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / downwards10 mm
Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / at the side0 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts / forwards10 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts / upwards10 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts / at the side6 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts / downwards10 mm
Installation/ mounting/ dimensions / required spacing / for live parts / forwards10 mm
Installation/ mounting/ dimensions / required spacing / for live parts / upwards10 mm
Installation/ mounting/ dimensions / required spacing / for live parts / downwards10 mm
Installation/ mounting/ dimensions / required spacing / for live parts / at the side6 mm
Connections/ Terminals / type of electrical connection / for main current circuitscrew-type terminals
Connections/ Terminals / type of electrical connection / for auxiliary and control circuitscrew-type terminals
Connections/ Terminals / type of electrical connection / at contactor for auxiliary contactsScrew-type terminals
Connections/ Terminals / type of electrical connection / of magnet coilscrew terminal
Connections/ Terminals / type of connectable conductor cross-sections / for main contacts / solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Connections/ Terminals / type of connectable conductor cross-sections / for main contacts / solid or stranded2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), 2x 4 mm²
Connections/ Terminals / type of connectable conductor cross-sections / for main contacts / finely stranded with core end processing2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Connections/ Terminals / type of connectable conductor cross-sections / for AWG cables for main contacts2x (20 ... 16), 2x (18 ... 14), 2x 12
Connections/ Terminals / connectable conductor cross-section for main contacts / solid0.5 ... 4 mm²
Connections/ Terminals / connectable conductor cross-section for main contacts / stranded0.5 ... 4 mm²
Connections/ Terminals / connectable conductor cross-section for main contacts / finely stranded with core end processing0.5 ... 2.5 mm²
Connections/ Terminals / connectable conductor cross-section for auxiliary contacts / solid or stranded0.5 ... 4 mm²
Connections/ Terminals / connectable conductor cross-section for auxiliary contacts / finely stranded with core end processing0.5 ... 2.5 mm²
Connections/ Terminals / type of connectable conductor cross-sections / for auxiliary contacts / solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Connections/ Terminals / type of connectable conductor cross-sections / for auxiliary contacts / finely stranded with core end processing2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Safety related data / product function / mirror contact according to IEC 60947-4-1Yes; with 3RH29
Safety related data / product function / positively driven operation according to IEC 60947-5-No
Safety related data / product function / suitable for safety functionYes
Safety related data / suitability for use safety-related switching OFFYes
Safety related data / service life maximum20 a
Safety related data / test wear-related service life necessaryYes
Safety related data / proportion of dangerous failures / with low demand rate according to SN 3192040 %
Safety related data / proportion of dangerous failures / with high demand rate according to SN 3192073 %
Сертификация1.18 kg
Сертификация38.5 kg
Сертификация-0.155 kg