Автоматические выключатели защиты электродвигателей
SI

Siemens AG 3RV2011-0KA10

Автоматический выключатель защиты двигателя Siemens 3RV2011-0KA10, серия 3RV2. Подбор по артикулу, поставка под заказ: цену и срок уточняйте через запрос на поставку.

  • Бренд: Siemens AG
  • Артикул (MPN): 3RV2011-0KA10
  • Серия: 3RV2 Series
  • Статус производства: Не определён
  • Возможная замена для модели (требуется проверка совместимости): 3RV1011-0KA10

Категории:

Технические характеристики

Data sheet designationCircuit breaker size S00 for motor protection, CLASS 10 A-release 0.9...1.25 A N- release 16 A screw terminal Standard switching capacity
product brand nameSIRIUS
product designationCircuit breaker
design of the productFor motor protection
product type designation3RV2
General technical data / product function disconnector functionalityYes
General technical data / product extension auxiliary switchYes
General technical data / power loss [W] for rated value of the current / at AC in hot operating state7.25 W
General technical data / power loss [W] for rated value of the current / at AC in hot operating state per pole2.4 W
General technical data / type of calculation of power loss current-dependentquadratic
Напряжение питания690 V
Напряжение питания6 kV
Напряжение питания400 V
General technical data / protection class IP / on the frontIP20
General technical data / protection class IP / of the terminalIP20
General technical data / shock resistance according to IEC 60068-2-2725g / 11 ms
General technical data / mechanical service life (operating cycles) / of the main contacts typical100 000
General technical data / mechanical service life (operating cycles) / of auxiliary contacts typical100 000
General technical data / electrical endurance (operating cycles) typical100 000
General technical data / reference code according to IEC 81346-2Q
General technical data / continuous current rated value1.25 A
General technical data / Substance Prohibitance (day/month/year)10/01/2009
Масса319.6 g
Ambient conditions / installation altitude at height above sea level maximum2 000 m
Рабочая температура-20 ... +60 °C
Ambient conditions / ambient temperature / during storage-50 ... +80 °C
Рабочая температура-50 ... +80 °C
Ambient conditions / temperature compensation-20 ... +60 °C
Ambient conditions / relative humidity during operation10 ... 95 %
Напряжение питания690 V
Напряжение питания20 ... 690 V
Напряжение питания690 V
Напряжение питания690 V
Main circuit / operating frequency rated value50 ... 60 Hz
Main circuit / operational current rated value1.25 A
Main circuit / operational current / at AC-3 at 400 V rated value1.25 A
Main circuit / operational current / at AC-3e at 400 V rated value1.25 A
Main circuit / operating power / at AC-3 / at 230 V rated value0.2 kW
Main circuit / operating power / at AC-3 / at 400 V rated value0.37 kW
Main circuit / operating power / at AC-3 / at 500 V rated value0.4 kW
Main circuit / operating power / at AC-3 / at 690 V rated value0.8 kW
Main circuit / operating power / at AC-3e / at 230 V rated value0.2 kW
Main circuit / operating power / at AC-3e / at 400 V rated value0.37 kW
Main circuit / operating power / at AC-3e / at 500 V rated value0.4 kW
Main circuit / operating power / at AC-3e / at 690 V rated value0.8 kW
Main circuit / operating frequency / at AC-3 maximum15 1/h
Main circuit / operating frequency / at AC-3e maximum15 1/h
Напряжение питанияAC/DC
Auxiliary circuit / number of NC contacts for auxiliary contacts0
Auxiliary circuit / number of NO contacts for auxiliary contacts0
Auxiliary circuit / number of CO contacts for auxiliary contacts0
Protective and monitoring functions / product function / ground fault detectionNo
Protective and monitoring functions / product function / phase failure detectionYes
Protective and monitoring functions / trip classCLASS 10
Protective and monitoring functions / design of the overload releasethermal
Protective and monitoring functions / protection function thermal overload protection (ANSI 49)Yes
Protective and monitoring functions / maximum short-circuit current breaking capacity (Icu) / at AC at 240 V rated value100 kA
Protective and monitoring functions / maximum short-circuit current breaking capacity (Icu) / at AC at 400 V rated value100 kA
Protective and monitoring functions / maximum short-circuit current breaking capacity (Icu) / at AC at 500 V rated value100 kA
Protective and monitoring functions / maximum short-circuit current breaking capacity (Icu) / at AC at 690 V rated value100 kA
Protective and monitoring functions / operating short-circuit current breaking capacity (Ics) at AC / at 240 V rated value100 kA
Protective and monitoring functions / operating short-circuit current breaking capacity (Ics) at AC / at 400 V rated value100 kA
Protective and monitoring functions / operating short-circuit current breaking capacity (Ics) at AC / at 500 V rated value100 kA
Protective and monitoring functions / operating short-circuit current breaking capacity (Ics) at AC / at 690 V rated value100 kA
Protective and monitoring functions / response value current of instantaneous short-circuit trip unit16 A
UL/CSA ratings / full-load current (FLA) for 3-phase AC motor / at 480 V rated value1.25 A
UL/CSA ratings / full-load current (FLA) for 3-phase AC motor / at 600 V rated value1.25 A
UL/CSA ratings / yielded mechanical performance [hp] / for 3-phase AC motor / at 460/480 V rated value1 hp
UL/CSA ratings / yielded mechanical performance [hp] / for 3-phase AC motor / at 575/600 V rated value0.5 hp
UL/CSA ratings / UL File Number (CCN)E47705 (NLRV, NLRV7), E156943 (NKJH, NKJH7)
Short-circuit protection / protection of the main circuit / at 690 VgL/gG 16 A
СертификацияDMT 02 ATEX F 001
Short-circuit protection / type of protection according to ATEX directive 2014/34/EUEx II (2) GD
Installation/ mounting/ dimensions / mounting positionany
Installation/ mounting/ dimensions / depth97 mm
Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / forwards0 mm
Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / backwards0 mm
Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / upwards50 mm
Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / downwards50 mm
Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / at the side0 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts / forwards0 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts / backwards0 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts / upwards50 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts / at the side30 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts / downwards50 mm
Installation/ mounting/ dimensions / required spacing / for live parts / forwards0 mm
Installation/ mounting/ dimensions / required spacing / for live parts / backwards0 mm
Installation/ mounting/ dimensions / required spacing / for live parts / upwards50 mm
Installation/ mounting/ dimensions / required spacing / for live parts / downwards50 mm
Installation/ mounting/ dimensions / required spacing / for live parts / at the side30 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts at 400 V / downwards30 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts at 400 V / upwards30 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts at 400 V / at the side9 mm
Installation/ mounting/ dimensions / required spacing / for live parts at 400 V / downwards30 mm
Installation/ mounting/ dimensions / required spacing / for live parts at 400 V / upwards30 mm
Installation/ mounting/ dimensions / required spacing / for live parts at 400 V / at the side9 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts at 500 V / downwards30 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts at 500 V / upwards30 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts at 500 V / at the side9 mm
Installation/ mounting/ dimensions / required spacing / for live parts at 500 V / downwards30 mm
Installation/ mounting/ dimensions / required spacing / for live parts at 500 V / upwards30 mm
Installation/ mounting/ dimensions / required spacing / for live parts at 500 V / at the side9 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts at 690 V / downwards50 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts at 690 V / upwards50 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts at 690 V / backwards0 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts at 690 V / at the side30 mm
Installation/ mounting/ dimensions / required spacing / for grounded parts at 690 V / forwards0 mm
Installation/ mounting/ dimensions / required spacing / for live parts at 690 V / downwards50 mm
Installation/ mounting/ dimensions / required spacing / for live parts at 690 V / upwards50 mm
Installation/ mounting/ dimensions / required spacing / for live parts at 690 V / backwards0 mm
Installation/ mounting/ dimensions / required spacing / for live parts at 690 V / at the side30 mm
Installation/ mounting/ dimensions / required spacing / for live parts at 690 V / forwards0 mm
Connections/ Terminals / type of connectable conductor cross-sections / for main contacts / solid or stranded2x (0,75 ... 2,5 mm²), 2x 4 mm²
Connections/ Terminals / type of connectable conductor cross-sections / for main contacts / finely stranded with core end processing2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Connections/ Terminals / type of connectable conductor cross-sections / for AWG cables for main contacts2x (18 ... 14), 2x 12
Connections/ Terminals / connectable conductor cross-section for main contacts / solid or stranded0.75 ... 4 mm²
Connections/ Terminals / design of screwdriver shaftDiameter 5 to 6 mm
Connections/ Terminals / size of the screwdriver tipPozidriv size 2
Connections/ Terminals / design of the thread of the connection screw / for main contactsM3
Safety related data / product function suitable for safety functionYes
Safety related data / suitability for use / safety-related switching onNo
Safety related data / suitability for use / safety-related switching OFFYes
Safety related data / service life maximum10 a
Safety related data / test wear-related service life necessaryYes
Safety related data / proportion of dangerous failures / with low demand rate according to SN 3192040 %
Safety related data / proportion of dangerous failures / with high demand rate according to SN 3192050 %
Display / display version for switching statusHandle
Сертификация1.98 kg
Сертификация0.134 kg
Сертификация72.7 kg
Сертификация-0.116 kg
Further information / last modified:5/5/2026