SI
Siemens AG 3RV2021-4FA15
Автоматический выключатель защиты двигателя Siemens 3RV2021-4FA15, серия 3RV2. Подбор по артикулу, поставка под заказ: цену и срок уточняйте через запрос на поставку.
Категории:
Технические характеристики
| Data sheet designation | circuit breaker frame size S0 for motor protection, Class 10 thermal release 34...40 A short-circuit release 480 A screw terminal standard switching capacity with transverse auxiliary switch 1 NO+1 NC |
|---|---|
| product brand name | SIRIUS |
| product designation | Circuit breaker |
| design of the product | For motor protection |
| product type designation | 3RV2 |
| General technical data / product function disconnector functionality | Yes |
| General technical data / product extension auxiliary switch | Yes |
| General technical data / power loss [W] for rated value of the current / at AC in hot operating state | 16.25 W |
| General technical data / power loss [W] for rated value of the current / at AC in hot operating state per pole | 5.4 W |
| General technical data / type of calculation of power loss current-dependent | quadratic |
| Напряжение питания | 690 V |
| Напряжение питания | 6 kV |
| Напряжение питания | 400 V |
| General technical data / protection class IP / on the front | IP20 |
| General technical data / protection class IP / of the terminal | IP20 |
| General technical data / shock resistance according to IEC 60068-2-27 | 25g / 11 ms |
| General technical data / mechanical service life (operating cycles) / of the main contacts typical | 100 000 |
| General technical data / mechanical service life (operating cycles) / of auxiliary contacts typical | 100 000 |
| General technical data / electrical endurance (operating cycles) typical | 100 000 |
| General technical data / reference code according to IEC 81346-2 | Q |
| General technical data / continuous current rated value | 40 A |
| General technical data / Substance Prohibitance (day/month/year) | 10/01/2009 |
| Масса | 373.18 g |
| Ambient conditions / installation altitude at height above sea level maximum | 2 000 m |
| Рабочая температура | -20 ... +40 °C |
| Ambient conditions / ambient temperature / during storage | -50 ... +80 °C |
| Рабочая температура | -50 ... +80 °C |
| Ambient conditions / temperature compensation | -20 ... +60 °C |
| Ambient conditions / relative humidity during operation | 10 ... 95 % |
| Напряжение питания | 690 V |
| Напряжение питания | 20 ... 690 V |
| Напряжение питания | 690 V |
| Main circuit / operating frequency rated value | 50 ... 60 Hz |
| Main circuit / operational current rated value | 40 A |
| Main circuit / operational current / at AC-3 at 400 V rated value | 40 A |
| Main circuit / operating power / at AC-3 / at 230 V rated value | 11 kW |
| Main circuit / operating power / at AC-3 / at 400 V rated value | 18.5 kW |
| Main circuit / operating power / at AC-3 / at 500 V rated value | 22 kW |
| Main circuit / operating power / at AC-3 / at 690 V rated value | 39 kW |
| Main circuit / operating frequency / at AC-3 maximum | 15 1/h |
| Auxiliary circuit / design of the auxiliary switch | transverse |
| Напряжение питания | AC/DC |
| Auxiliary circuit / number of NC contacts for auxiliary contacts | 1 |
| Auxiliary circuit / number of NO contacts for auxiliary contacts | 1 |
| Auxiliary circuit / number of CO contacts for auxiliary contacts | 0 |
| Auxiliary circuit / operational current of auxiliary contacts at AC-15 / at 24 V | 2 A |
| Auxiliary circuit / operational current of auxiliary contacts at AC-15 / at 120 V | 0.5 A |
| Auxiliary circuit / operational current of auxiliary contacts at AC-15 / at 125 V | 0.5 A |
| Auxiliary circuit / operational current of auxiliary contacts at AC-15 / at 230 V | 0.5 A |
| Auxiliary circuit / operational current of auxiliary contacts at DC-13 / at 24 V | 1 A |
| Auxiliary circuit / operational current of auxiliary contacts at DC-13 / at 60 V | 0.15 A |
| Protective and monitoring functions / product function / ground fault detection | No |
| Protective and monitoring functions / product function / phase failure detection | Yes |
| Protective and monitoring functions / trip class | CLASS 10 |
| Protective and monitoring functions / design of the overload release | thermal |
| Protective and monitoring functions / protection function thermal overload protection (ANSI 49) | Yes |
| Protective and monitoring functions / maximum short-circuit current breaking capacity (Icu) / at AC at 240 V rated value | 100 kA |
| Protective and monitoring functions / maximum short-circuit current breaking capacity (Icu) / at AC at 400 V rated value | 20 kA |
| Protective and monitoring functions / maximum short-circuit current breaking capacity (Icu) / at AC at 500 V rated value | 6 kA |
| Protective and monitoring functions / maximum short-circuit current breaking capacity (Icu) / at AC at 690 V rated value | 3 kA |
| Protective and monitoring functions / operating short-circuit current breaking capacity (Ics) at AC / at 240 V rated value | 100 kA |
| Protective and monitoring functions / operating short-circuit current breaking capacity (Ics) at AC / at 400 V rated value | 10 kA |
| Protective and monitoring functions / operating short-circuit current breaking capacity (Ics) at AC / at 500 V rated value | 3 kA |
| Protective and monitoring functions / operating short-circuit current breaking capacity (Ics) at AC / at 690 V rated value | 2 kA |
| Protective and monitoring functions / response value current of instantaneous short-circuit trip unit | 480 A |
| UL/CSA ratings / full-load current (FLA) for 3-phase AC motor / at 480 V rated value | 40 A |
| UL/CSA ratings / full-load current (FLA) for 3-phase AC motor / at 600 V rated value | 40 A |
| UL/CSA ratings / yielded mechanical performance [hp] / for single-phase AC motor / at 110/120 V rated value | 3 hp |
| UL/CSA ratings / yielded mechanical performance [hp] / for single-phase AC motor / at 230 V rated value | 7.5 hp |
| UL/CSA ratings / yielded mechanical performance [hp] / for 3-phase AC motor / at 200/208 V rated value | 10 hp |
| UL/CSA ratings / yielded mechanical performance [hp] / for 3-phase AC motor / at 220/230 V rated value | 10 hp |
| UL/CSA ratings / yielded mechanical performance [hp] / for 3-phase AC motor / at 460/480 V rated value | 30 hp |
| UL/CSA ratings / contact rating of auxiliary contacts according to UL | C300 / R300 |
| UL/CSA ratings / UL File Number (CCN) | E47705 (NLRV, NLRV7) |
| Short-circuit protection / product function short circuit protection | Yes |
| Short-circuit protection / design of the short-circuit trip | magnetic |
| Short-circuit protection / protection of the main circuit / at 500 V | gG 63 A |
| Short-circuit protection / protection of the main circuit / at 690 V | gG 63 A |
| Сертификация | DMT 02 ATEX F 001 |
| Short-circuit protection / type of protection according to ATEX directive 2014/34/EU | Ex II (2) GD |
| Installation/ mounting/ dimensions / mounting position | any |
| Installation/ mounting/ dimensions / depth | 97 mm |
| Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / forwards | 0 mm |
| Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / backwards | 0 mm |
| Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / upwards | 70 mm |
| Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / downwards | 70 mm |
| Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / at the side | 9 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts / forwards | 0 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts / backwards | 0 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts / upwards | 70 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts / at the side | 30 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts / downwards | 70 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts / forwards | 0 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts / backwards | 0 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts / upwards | 70 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts / downwards | 70 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts / at the side | 30 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts at 400 V / downwards | 30 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts at 400 V / upwards | 30 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts at 400 V / at the side | 9 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts at 400 V / downwards | 30 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts at 400 V / upwards | 30 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts at 400 V / at the side | 9 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts at 500 V / downwards | 30 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts at 500 V / upwards | 30 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts at 500 V / at the side | 9 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts at 500 V / downwards | 30 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts at 500 V / upwards | 30 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts at 500 V / at the side | 9 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts at 690 V / downwards | 70 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts at 690 V / upwards | 70 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts at 690 V / backwards | 0 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts at 690 V / at the side | 30 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts at 690 V / forwards | 0 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts at 690 V / downwards | 70 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts at 690 V / upwards | 70 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts at 690 V / backwards | 0 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts at 690 V / at the side | 30 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts at 690 V / forwards | 0 mm |
| Connections/ Terminals / type of connectable conductor cross-sections / for main contacts / solid or stranded | 2x (1 ... 2.5 mm²), 2x (2.5 ... 10 mm²) |
| Connections/ Terminals / type of connectable conductor cross-sections / for main contacts / finely stranded with core end processing | 2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²), 1x 10 mm² |
| Connections/ Terminals / type of connectable conductor cross-sections / for AWG cables for main contacts | 2x (16 ... 12), 2x (14 ... 8) |
| Connections/ Terminals / connectable conductor cross-section for main contacts / solid or stranded | 1 ... 10 mm² |
| Connections/ Terminals / connectable conductor cross-section for main contacts / finely stranded with core end processing | 1 ... 10 mm² |
| Connections/ Terminals / connectable conductor cross-section for auxiliary contacts / solid or stranded | 0.5 ... 2.5 mm² |
| Connections/ Terminals / connectable conductor cross-section for auxiliary contacts / finely stranded with core end processing | 0.5 ... 2.5 mm² |
| Connections/ Terminals / type of connectable conductor cross-sections / for auxiliary contacts / solid or stranded | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
| Connections/ Terminals / type of connectable conductor cross-sections / for auxiliary contacts / finely stranded with core end processing | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
| Connections/ Terminals / tightening torque / for auxiliary contacts with screw-type terminals | 0.8 ... 1.2 N·m |
| Connections/ Terminals / design of screwdriver shaft | Diameter 5 to 6 mm |
| Connections/ Terminals / size of the screwdriver tip | Pozidriv size 2 |
| Connections/ Terminals / design of the thread of the connection screw / for main contacts | M4 |
| Connections/ Terminals / design of the thread of the connection screw / of the auxiliary and control contacts | M3 |
| Safety related data / product function suitable for safety function | Yes |
| Safety related data / suitability for use / safety-related switching on | No |
| Safety related data / suitability for use / safety-related switching OFF | Yes |
| Safety related data / service life maximum | 10 a |
| Safety related data / test wear-related service life necessary | Yes |
| Safety related data / proportion of dangerous failures / with low demand rate according to SN 31920 | 40 % |
| Safety related data / proportion of dangerous failures / with high demand rate according to SN 31920 | 50 % |
| Display / display version for switching status | Handle |
| Сертификация | 2.68 kg |
| Сертификация | 0.143 kg |
| Сертификация | 72.7 kg |
| Сертификация | -0.445 kg |