SI
Siemens AG 3RV2031-4DB10
Автоматический выключатель защиты двигателя Siemens 3RV2031-4DB10, серия 3RV2. Подбор по артикулу, поставка под заказ: цену и срок уточняйте через запрос на поставку.
Категории:
Технические характеристики
| Data sheet designation | Circuit breaker size S2 for motor protection, Class 20 A-release 18...25 A N- release 325 A Screw terminal Standard switching capacity |
|---|---|
| product brand name | SIRIUS |
| product designation | Circuit breaker |
| design of the product | For motor protection |
| product type designation | 3RV2 |
| General technical data / product function disconnector functionality | Yes |
| General technical data / product extension auxiliary switch | Yes |
| General technical data / power loss [W] for rated value of the current / at AC in hot operating state | 14.5 W |
| General technical data / power loss [W] for rated value of the current / at AC in hot operating state per pole | 4.8 W |
| General technical data / type of calculation of power loss current-dependent | quadratic |
| Напряжение питания | 690 V |
| Напряжение питания | 6 kV |
| Напряжение питания | 400 V |
| General technical data / protection class IP / on the front | IP20 |
| General technical data / protection class IP / of the terminal | IP00 |
| General technical data / shock resistance according to IEC 60068-2-27 | 25 g / 11 ms Sinus |
| General technical data / mechanical service life (operating cycles) / of the main contacts typical | 50 000 |
| General technical data / mechanical service life (operating cycles) / of auxiliary contacts typical | 50 000 |
| General technical data / electrical endurance (operating cycles) typical | 50 000 |
| General technical data / reference code according to IEC 81346-2 | Q |
| General technical data / continuous current rated value | 25 A |
| General technical data / Substance Prohibitance (day/month/year) | 10/15/2014 |
| General technical data / SVHC substance name | Lead CAS-No. 7439-92-1 |
| Масса | 1.074 kg |
| Ambient conditions / installation altitude at height above sea level maximum | 2 000 m |
| Рабочая температура | -20 ... +60 °C |
| Ambient conditions / ambient temperature / during storage | -50 ... +80 °C |
| Рабочая температура | -50 ... +80 °C |
| Ambient conditions / temperature compensation | -20 ... +60 °C |
| Ambient conditions / relative humidity during operation | 10 ... 95 % |
| Напряжение питания | 690 V |
| Напряжение питания | 20 ... 690 V |
| Напряжение питания | 690 V |
| Напряжение питания | 690 V |
| Main circuit / operating frequency rated value | 50 ... 60 Hz |
| Main circuit / operational current rated value | 25 A |
| Main circuit / operational current / at AC-3 at 400 V rated value | 25 A |
| Main circuit / operational current / at AC-3e at 400 V rated value | 25 A |
| Main circuit / operating power / at AC-3 / at 230 V rated value | 5.5 kW |
| Main circuit / operating power / at AC-3 / at 400 V rated value | 11 kW |
| Main circuit / operating power / at AC-3 / at 500 V rated value | 15 kW |
| Main circuit / operating power / at AC-3 / at 690 V rated value | 22 kW |
| Main circuit / operating power / at AC-3e / at 230 V rated value | 5.5 kW |
| Main circuit / operating power / at AC-3e / at 400 V rated value | 11 kW |
| Main circuit / operating power / at AC-3e / at 500 V rated value | 15 kW |
| Main circuit / operating power / at AC-3e / at 690 V rated value | 22 kW |
| Main circuit / operating frequency / at AC-3 maximum | 15 1/h |
| Main circuit / operating frequency / at AC-3e maximum | 15 1/h |
| Напряжение питания | AC/DC |
| Auxiliary circuit / number of NC contacts for auxiliary contacts | 0 |
| Auxiliary circuit / number of NO contacts for auxiliary contacts | 0 |
| Auxiliary circuit / number of CO contacts for auxiliary contacts | 0 |
| Protective and monitoring functions / product function / ground fault detection | No |
| Protective and monitoring functions / product function / phase failure detection | Yes |
| Protective and monitoring functions / trip class | CLASS 20 |
| Protective and monitoring functions / design of the overload release | thermal |
| Protective and monitoring functions / protection function thermal overload protection (ANSI 49) | Yes |
| Protective and monitoring functions / maximum short-circuit current breaking capacity (Icu) / at AC at 240 V rated value | 100 kA |
| Protective and monitoring functions / maximum short-circuit current breaking capacity (Icu) / at AC at 400 V rated value | 65 kA |
| Protective and monitoring functions / maximum short-circuit current breaking capacity (Icu) / at AC at 500 V rated value | 12 kA |
| Protective and monitoring functions / maximum short-circuit current breaking capacity (Icu) / at AC at 690 V rated value | 5 kA |
| Protective and monitoring functions / operating short-circuit current breaking capacity (Ics) at AC / at 240 V rated value | 100 kA |
| Protective and monitoring functions / operating short-circuit current breaking capacity (Ics) at AC / at 400 V rated value | 30 kA |
| Protective and monitoring functions / operating short-circuit current breaking capacity (Ics) at AC / at 500 V rated value | 6 kA |
| Protective and monitoring functions / operating short-circuit current breaking capacity (Ics) at AC / at 690 V rated value | 3 kA |
| Protective and monitoring functions / response value current of instantaneous short-circuit trip unit | 325 A |
| UL/CSA ratings / full-load current (FLA) for 3-phase AC motor / at 480 V rated value | 25 A |
| UL/CSA ratings / full-load current (FLA) for 3-phase AC motor / at 600 V rated value | 25 A |
| UL/CSA ratings / yielded mechanical performance [hp] / for single-phase AC motor / at 110/120 V rated value | 2 hp |
| UL/CSA ratings / yielded mechanical performance [hp] / for single-phase AC motor / at 230 V rated value | 5 hp |
| UL/CSA ratings / yielded mechanical performance [hp] / for 3-phase AC motor / at 200/208 V rated value | 7.5 hp |
| UL/CSA ratings / yielded mechanical performance [hp] / for 3-phase AC motor / at 220/230 V rated value | 10 hp |
| UL/CSA ratings / yielded mechanical performance [hp] / for 3-phase AC motor / at 460/480 V rated value | 20 hp |
| UL/CSA ratings / yielded mechanical performance [hp] / for 3-phase AC motor / at 575/600 V rated value | 25 hp |
| Short-circuit protection / protection of the main circuit / at 400 V | 100 |
| Short-circuit protection / protection of the main circuit / at 500 V | 80 |
| Short-circuit protection / protection of the main circuit / at 690 V | 63 |
| Installation/ mounting/ dimensions / mounting position | any |
| Installation/ mounting/ dimensions / depth | 149 mm |
| Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / forwards | 0 mm |
| Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / backwards | 0 mm |
| Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / upwards | 50 mm |
| Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / downwards | 50 mm |
| Installation/ mounting/ dimensions / required spacing / with side-by-side mounting / at the side | 0 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts / forwards | 0 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts / backwards | 0 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts / upwards | 50 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts / at the side | 10 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts / downwards | 50 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts / forwards | 0 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts / backwards | 0 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts / upwards | 50 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts / downwards | 50 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts / at the side | 10 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts at 400 V / downwards | 50 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts at 400 V / upwards | 50 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts at 400 V / at the side | 10 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts at 400 V / downwards | 50 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts at 400 V / upwards | 50 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts at 400 V / at the side | 10 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts at 500 V / upwards | 50 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts at 500 V / at the side | 10 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts at 500 V / downwards | 50 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts at 500 V / upwards | 50 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts at 500 V / at the side | 10 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts at 690 V / downwards | 50 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts at 690 V / upwards | 50 mm |
| Installation/ mounting/ dimensions / required spacing / for grounded parts at 690 V / at the side | 10 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts at 690 V / downwards | 50 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts at 690 V / upwards | 50 mm |
| Installation/ mounting/ dimensions / required spacing / for live parts at 690 V / at the side | 10 mm |
| Connections/ Terminals / type of connectable conductor cross-sections / for main contacts / solid or stranded | 2x (1 ... 25 mm²), 1x (1 ... 35 mm²) |
| Connections/ Terminals / type of connectable conductor cross-sections / for main contacts / finely stranded with core end processing | 2x (1 ... 16 mm²), 1x (1 ... 25 mm²) |
| Connections/ Terminals / type of connectable conductor cross-sections / for AWG cables for main contacts | 2x (18 ... 3), 1x (18 ... 2) |
| Connections/ Terminals / connectable conductor cross-section for main contacts / solid or stranded | 1 ... 35 mm² |
| Connections/ Terminals / design of screwdriver shaft | Diameter 5 to 6 mm |
| Connections/ Terminals / size of the screwdriver tip | Pozidriv size 2 |
| Connections/ Terminals / design of the thread of the connection screw / for main contacts | M6 |
| Safety related data / product function suitable for safety function | Yes |
| Safety related data / suitability for use / safety-related switching on | No |
| Safety related data / suitability for use / safety-related switching OFF | Yes |
| Safety related data / service life maximum | 10 a |
| Safety related data / test wear-related service life necessary | Yes |
| Safety related data / proportion of dangerous failures / with low demand rate according to SN 31920 | 40 % |
| Safety related data / proportion of dangerous failures / with high demand rate according to SN 31920 | 50 % |
| Display / display version for switching status | Handle |
| Сертификация | 12.8 kg |
| Сертификация | 0.477 kg |
| Сертификация | 230 kg |
| Сертификация | -3.4 kg |
| Further information / last modified: | 5/5/2026 |