Устройства плавного пуска
SI

Siemens AG 3RW5217-1AC05

Устройство плавного пуска Siemens 3RW5217-1AC05, серия 3RW. Подбор по артикулу, поставка под заказ: цену и срок уточняйте через запрос на поставку.

  • Бренд: Siemens AG
  • Артикул (MPN): 3RW5217-1AC05
  • Серия: 3RW Series
  • Статус производства: Не определён

Категории:

Технические характеристики

Data sheet designationSIRIUS soft starter 200-600 V 38 A, 24 V AC/DC Screw terminals Analog output
product brand nameSIRIUS
product categoryHybrid switching devices
product designationSoft starter
product type designation3RW52
manufacturer's article number / of standard HMI module usable3RW5980-0HS00
manufacturer's article number / of high feature HMI module usable3RW5980-0HF00
manufacturer's article number / of communication module PROFINET standard usable3RW5980-0CS00
manufacturer's article number / of communication module PROFIBUS usable3RW5980-0CP00
manufacturer's article number / of communication module Modbus TCP usable3RW5980-0CT00
manufacturer's article number / of communication module Modbus RTU usable3RW5980-0CR00
manufacturer's article number / of communication module Ethernet/IP3RW5980-0CE00
manufacturer's article number / of circuit breaker usable at 400 V3RV2032-4WA10; Type of coordination 1, Iq = 65 kA, CLASS 10
manufacturer's article number / of circuit breaker usable at 500 V3RV2032-4WA10; Type of coordination 1, Iq = 10 kA, CLASS 10
manufacturer's article number / of circuit breaker usable at 400 V at inside-delta circuit3RV2032-4RA10; Type of coordination 1, Iq = 65 kA, CLASS 10
manufacturer's article number / of circuit breaker usable at 500 V at inside-delta circuit3RV2032-4RA10; Type of coordination 1, Iq = 10 kA, CLASS 10
manufacturer's article number / of the gG fuse usable up to 690 V3NA3824-6; Type of coordination 1, Iq = 65 kA
manufacturer's article number / of the gG fuse usable at inside-delta circuit up to 500 V3NA3824-6; Type of coordination 1, Iq = 65 kA
manufacturer's article number / of full range R fuse link for semiconductor protection3NE1820-0; Type of coordination 2, Iq = 65 kA
Напряжение питания50 %; non-adjustable
General technical data / start-up ramp time of soft starter0 ... 20 s
General technical data / current limiting value [%] adjustable130 ... 700 %
СертификацияYes
СертификацияYes
СертификацияYes
General technical data / product component / HMI-High FeatureNo
General technical data / product component / is supported HMI-StandardYes
General technical data / product component / is supported HMI-High FeatureYes
General technical data / product feature integrated bypass contact systemYes
General technical data / buffering time in the event of power failure / for main current circuit100 ms
General technical data / buffering time in the event of power failure / for control circuit100 ms
Напряжение питания600 V
General technical data / degree of pollution3, acc. to IEC 60947-4-2
Напряжение питания6 kV
Напряжение питания1 600 V
General technical data / service factor1
Напряжение питания6 kV
Напряжение питания600 V
General technical data / shock resistance15 g / 11 ms, from 12 g / 11 ms with potential contact lifting
General technical data / vibration resistance15 mm to 6 Hz; 2 g to 500 Hz
General technical data / utilization category according to IEC 60947-4-2AC 53a
General technical data / reference code according to IEC 81346-2Q
General technical data / product function / ramp-up (soft starting)Yes
General technical data / product function / soft stoppingYes
General technical data / product function / Soft TorqueYes
General technical data / product function / adjustable current limitationYes
General technical data / product function / pump stopYes
General technical data / product function / intrinsic device protectionYes
General technical data / product function / motor overload protectionYes; Electronic motor overload protection
General technical data / product function / evaluation of thermistor motor protectionNo
General technical data / product function / inside-delta circuitYes
General technical data / product function / auto-RESETYes
General technical data / product function / manual RESETYes
General technical data / product function / remote resetYes; By turning off the control supply voltage
General technical data / product function / communication functionYes
General technical data / product function / operating measured value displayYes; Only in conjunction with special accessories
General technical data / product function / error logbookYes; Only in conjunction with special accessories
General technical data / product function / via software parameterizableNo
General technical data / product function / via software configurableYes
General technical data / product function / PROFIenergyYes; in connection with the PROFINET Standard communication module
General technical data / product function / firmware updateYes
General technical data / product function / removable terminal for control circuitYes
General technical data / product function / torque controlNo
General technical data / product function / analog outputYes; 4 ... 20 mA (default) / 0 ... 10 V (parameterizable with High Feature HMI)
Power Electronics / operational current / at 40 °C rated value38 A
Power Electronics / operational current / at 50 °C rated value33.5 A
Power Electronics / operational current / at 60 °C rated value30.5 A
Power Electronics / operational current at inside-delta circuit / at 40 °C rated value65.8 A
Power Electronics / operational current at inside-delta circuit / at 50 °C rated value58 A
Power Electronics / operational current at inside-delta circuit / at 60 °C rated value52.8 A
Напряжение питания200 ... 600 V
Напряжение питания200 ... 600 V
Напряжение питания-15 %
Power Electronics / operating power for 3-phase motors / at 230 V at inside-delta circuit at 40 °C rated value18.5 kW
Power Electronics / operating power for 3-phase motors / at 400 V at 40 °C rated value18.5 kW
Power Electronics / operating power for 3-phase motors / at 400 V at inside-delta circuit at 40 °C rated value30 kW
Power Electronics / operating power for 3-phase motors / at 500 V at 40 °C rated value22 kW
Power Electronics / operating power for 3-phase motors / at 500 V at inside-delta circuit at 40 °C rated value37 kW
Power Electronics / Operating frequency 1 rated value50 Hz
Power Electronics / Operating frequency 2 rated value60 Hz
Power Electronics / relative negative tolerance of the operating frequency-10 %
Power Electronics / relative positive tolerance of the operating frequency10 %
Power Electronics / adjustable motor current / at rotary coding switch on switch position 115.5 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 217 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 318.5 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 420 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 521.5 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 623 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 724.5 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 826 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 927.5 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 1029 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 1130.5 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 1232 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 1333.5 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 1435 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 1536.5 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 1638 A
Power Electronics / adjustable motor current / minimum15.5 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch26.8 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #229.4 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #332 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #434.6 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #537.2 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #639.8 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #742.4 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #845 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #947.6 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #1050.2 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #1152.8 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #1255.4 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #1358 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #1460.6 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #1563.2 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #1665.8 A
Power Electronics / adjustable motor current / at inside-delta circuit minimum26.8 A
Power Electronics / minimum load [%]15 %; Relative to smallest settable Ie
Power Electronics / power loss [W] for rated value of the current at AC / at 40 °C after startup23 W
Power Electronics / power loss [W] for rated value of the current at AC / at 50 °C after startup22 W
Power Electronics / power loss [W] for rated value of the current at AC / at 60 °C after startup21 W
Power Electronics / power loss [W] at AC at current limitation 350% / at 40 °C during startup628 W
Power Electronics / power loss [W] at AC at current limitation 350% / at 50 °C during startup526 W
Power Electronics / power loss [W] at AC at current limitation 350% / at 60 °C during startup464 W
Напряжение питанияAC/DC
Напряжение питания24 V
Inputs/ Outputs / number of digital outputs3
Inputs/ Outputs / not parameterizable2
Inputs/ Outputs / digital output version2 normally-open contacts (NO) / 1 changeover contact (CO)
Inputs/ Outputs / number of analog outputs1
Inputs/ Outputs / switching capacity current of the relay outputs / at AC-15 at 250 V rated value3 A
Inputs/ Outputs / switching capacity current of the relay outputs / at DC-13 at 24 V rated value1 A
Installation/ mounting/ dimensions / width170 mm
Installation/ mounting/ dimensions / depth152 mm
Installation/ mounting/ dimensions / required spacing with side-by-side mounting / forwards10 mm
Installation/ mounting/ dimensions / required spacing with side-by-side mounting / backwards0 mm
Installation/ mounting/ dimensions / required spacing with side-by-side mounting / upwards100 mm
Installation/ mounting/ dimensions / required spacing with side-by-side mounting / downwards75 mm
Installation/ mounting/ dimensions / required spacing with side-by-side mounting / at the side5 mm
Масса2.3 kg
Connections/ Terminals / type of electrical connection / for main current circuitscrew-type terminals
Connections/ Terminals / type of electrical connection / for control circuitscrew-type terminals
Connections/ Terminals / type of connectable conductor cross-sections / for main contacts / solid2x (1.0 ... 2.5 mm²), 2x (2.5 ... 10 mm²)
Connections/ Terminals / type of connectable conductor cross-sections / for main contacts / finely stranded with core end processing2x (1.0 ... 2.5 mm²), 2x (2.5 ... 6.0 mm²)
Connections/ Terminals / type of connectable conductor cross-sections / for AWG cables for main current circuit solid2x (16 ... 12), 2x (14 ... 8)
Connections/ Terminals / type of connectable conductor cross-sections / for control circuit solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
Connections/ Terminals / type of connectable conductor cross-sections / for control circuit finely stranded with core end processing1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Connections/ Terminals / type of connectable conductor cross-sections / for AWG cables for control circuit solid1x (20 ... 12), 2x (20 ... 14)
Connections/ Terminals / wire length / between soft starter and motor maximum800 m
Connections/ Terminals / wire length / at the digital inputs at AC maximum100 m
Connections/ Terminals / wire length / at the digital inputs at DC maximum1 000 m
Рабочая температура-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Ambient conditions / ambient temperature / during storage and transport-40 ... +80 °C
Electromagnetic compatibility / EMC emitted interferenceacc. to IEC 60947-4-2: Class A
Communication/ Protocol / communication module is supported / PROFINET standardYes
Communication/ Protocol / communication module is supported / EtherNet/IPYes
Communication/ Protocol / communication module is supported / Modbus RTUYes
Communication/ Protocol / communication module is supported / Modbus TCPYes
Communication/ Protocol / communication module is supported / PROFIBUSYes
UL/CSA ratings / manufacturer's article number / of circuit breaker usable for Standard Faults / at 460/480 V according to ULSiemens type: 3RV2742, max. 70 A or 3VA51, max. 125 A; Iq = 5 kA
UL/CSA ratings / manufacturer's article number / of circuit breaker usable for Standard Faults / 60/480 V according to ULSiemens type: 3RV2742, max.40 A or 3VA51, max. 60 A; Iq max = 65 kA
UL/CSA ratings / manufacturer's article number / of circuit breaker usable for Standard Faults / at 460/480 V at inside-delta circuit according to ULSiemens type: 3RV2742, max. 70 A or 3VA51, max. 125 A; Iq = 5 kA
UL/CSA ratings / manufacturer's article number / of circuit breaker usable for Standard Faults / 60/480 V at inside-delta circuit according to ULSiemens type: 3VA51, max. 60 A; Iq max = 65 kA
UL/CSA ratings / manufacturer's article number / of circuit breaker usable for Standard Faults / at 575/600 V according to ULSiemens type: 3RV2742, max. 70 A or 3VA51, max. 125 A; Iq = 5 kA
UL/CSA ratings / manufacturer's article number / of circuit breaker usable for Standard Faults / at 575/600 V at inside-delta circuit according to ULSiemens type: 3RV2742, max. 70 A or 3VA51, max. 125 A; Iq = 5 kA
UL/CSA ratings / manufacturer's article number / of the fuse / usable for Standard Faults up to 575/600 VType: Class RK5 / K5, max. 150 A; Iq = 5 kA
UL/CSA ratings / manufacturer's article number / of the fuse / usable for High Faults up to 575/600 V according toType: Class J / L, max. 150 A; Iq = 100 kA
UL/CSA ratings / manufacturer's article number / of the fuse / usable for Standard Faults at inside-delta circuit upType: Class RK5 / K5, max. 150 A; Iq = 5 kA
UL/CSA ratings / operating power [hp] for 3-phase motors / at 220/230 V at 50 °C rated value10 hp
UL/CSA ratings / operating power [hp] for 3-phase motors / at 460/480 V at 50 °C rated value20 hp
UL/CSA ratings / operating power [hp] for 3-phase motors / at 575/600 V at 50 °C rated value30 hp
UL/CSA ratings / operating power [hp] for 3-phase motors / at 200/208 V at inside-delta circuit at 50 °C rated value15 hp
UL/CSA ratings / operating power [hp] for 3-phase motors / at 220/230 V at inside-delta circuit at 50 °C rated value20 hp
UL/CSA ratings / operating power [hp] for 3-phase motors / at 460/480 V at inside-delta circuit at 50 °C rated value40 hp
Сертификация37.2 kg
Сертификация0.66 kg
Сертификация152 kg
Сертификация-4.19 kg
Получить предложение по этой позиции