Технические характеристики

Data sheet designationSIRIUS soft starter 200-480 V 47 A, 110-250 V AC Screw terminals Thermistor input
product brand nameSIRIUS
product categoryHybrid switching devices
product designationSoft starter
product type designation3RW52
manufacturer's article number / of standard HMI module usable3RW5980-0HS00
manufacturer's article number / of high feature HMI module usable3RW5980-0HF00
manufacturer's article number / of communication module PROFINET standard usable3RW5980-0CS00
manufacturer's article number / of communication module PROFIBUS usable3RW5980-0CP00
manufacturer's article number / of communication module Modbus TCP usable3RW5980-0CT00
manufacturer's article number / of communication module Modbus RTU usable3RW5980-0CR00
manufacturer's article number / of communication module Ethernet/IP3RW5980-0CE00
manufacturer's article number / of circuit breaker usable at 400 V3RV2032-4JA10; Type of coordination 1, Iq = 65 kA, CLASS 10
manufacturer's article number / of circuit breaker usable at 500 V3RV2032-4JA10; Type of coordination 1, Iq = 10 kA, CLASS 10
manufacturer's article number / of circuit breaker usable at 400 V at inside-delta circuit3RV2032-4RA10; Type of coordination 1, Iq = 65 kA, CLASS 10
manufacturer's article number / of circuit breaker usable at 500 V at inside-delta circuit3RV2032-4RA10; Type of coordination 1, Iq = 10 kA, CLASS 10
manufacturer's article number / of the gG fuse usable up to 690 V3NA3824-6; Type of coordination 1, Iq = 65 kA
manufacturer's article number / of the gG fuse usable at inside-delta circuit up to 500 V3NA3824-6; Type of coordination 1, Iq = 65 kA
manufacturer's article number / of full range R fuse link for semiconductor protection3NE1021-2; Type of coordination 2, Iq = 65 kA
Напряжение питания50 %; non-adjustable
General technical data / start-up ramp time of soft starter0 ... 20 s
General technical data / current limiting value [%] adjustable130 ... 700 %
СертификацияYes
СертификацияYes
СертификацияYes
General technical data / product component / HMI-High FeatureNo
General technical data / product component / is supported HMI-StandardYes
General technical data / product component / is supported HMI-High FeatureYes
General technical data / product feature integrated bypass contact systemYes
General technical data / buffering time in the event of power failure / for main current circuit100 ms
General technical data / buffering time in the event of power failure / for control circuit100 ms
Напряжение питания600 V
General technical data / degree of pollution3, acc. to IEC 60947-4-2
Напряжение питания6 kV
Напряжение питания1 400 V
General technical data / service factor1
Напряжение питания6 kV
Напряжение питания600 V
General technical data / shock resistance15 g / 11 ms, from 12 g / 11 ms with potential contact lifting
General technical data / vibration resistance15 mm to 6 Hz; 2 g to 500 Hz
General technical data / utilization category according to IEC 60947-4-2AC 53a
General technical data / reference code according to IEC 81346-2Q
General technical data / product function / ramp-up (soft starting)Yes
General technical data / product function / soft stoppingYes
General technical data / product function / Soft TorqueYes
General technical data / product function / adjustable current limitationYes
General technical data / product function / pump stopYes
General technical data / product function / auto-RESETYes
General technical data / product function / manual RESETYes
General technical data / product function / remote resetYes; By turning off the control supply voltage
General technical data / product function / communication functionYes
General technical data / product function / operating measured value displayYes; Only in conjunction with special accessories
General technical data / product function / error logbookYes; Only in conjunction with special accessories
General technical data / product function / via software parameterizableNo
General technical data / product function / via software configurableYes
General technical data / product function / PROFIenergyYes; in connection with the PROFINET Standard communication module
General technical data / product function / firmware updateYes
General technical data / product function / removable terminal for control circuitYes
General technical data / product function / torque controlNo
General technical data / product function / analog outputNo
Power Electronics / operational current / at 40 °C rated value47 A
Power Electronics / operational current / at 50 °C rated value41.6 A
Power Electronics / operational current / at 60 °C rated value36.2 A
Power Electronics / operational current at inside-delta circuit / at 40 °C rated value81.4 A
Power Electronics / operational current at inside-delta circuit / at 50 °C rated value72 A
Power Electronics / operational current at inside-delta circuit / at 60 °C rated value62.7 A
Напряжение питания200 ... 480 V
Напряжение питания200 ... 480 V
Напряжение питания-15 %
Power Electronics / operating power for 3-phase motors / at 230 V at inside-delta circuit at 40 °C rated value22 kW
Power Electronics / operating power for 3-phase motors / at 400 V at 40 °C rated value22 kW
Power Electronics / operating power for 3-phase motors / at 400 V at inside-delta circuit at 40 °C rated value45 kW
Power Electronics / Operating frequency 1 rated value50 Hz
Power Electronics / Operating frequency 2 rated value60 Hz
Power Electronics / relative negative tolerance of the operating frequency-10 %
Power Electronics / relative positive tolerance of the operating frequency10 %
Power Electronics / adjustable motor current / at rotary coding switch on switch position 120 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 221.8 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 323.6 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 425.4 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 527.2 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 629 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 730.8 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 832.6 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 934.4 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 1036.2 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 1138 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 1239.8 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 1341.6 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 1443.4 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 1545.2 A
Power Electronics / adjustable motor current / at rotary coding switch on switch position 1647 A
Power Electronics / adjustable motor current / minimum20 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch34.6 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #237.8 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #340.9 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #444 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #547.1 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #650.2 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #753.3 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #856.5 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #959.6 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #1062.7 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #1165.8 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #1268.9 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #1372.1 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #1475.2 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #1578.3 A
Power Electronics / adjustable motor current / for inside-delta circuit at rotary coding switch on switch #1681.4 A
Power Electronics / adjustable motor current / at inside-delta circuit minimum34.6 A
Power Electronics / minimum load [%]15 %; Relative to smallest settable Ie
Power Electronics / power loss [W] for rated value of the current at AC / at 40 °C after startup26 W
Power Electronics / power loss [W] for rated value of the current at AC / at 50 °C after startup24 W
Power Electronics / power loss [W] for rated value of the current at AC / at 60 °C after startup23 W
Power Electronics / power loss [W] at AC at current limitation 350% / at 40 °C during startup606 W
Power Electronics / power loss [W] at AC at current limitation 350% / at 50 °C during startup522 W
Power Electronics / power loss [W] at AC at current limitation 350% / at 60 °C during startup438 W
Напряжение питанияAC
Напряжение питания110 ... 250 V
Inputs/ Outputs / number of digital outputs3
Inputs/ Outputs / not parameterizable2
Inputs/ Outputs / digital output version2 normally-open contacts (NO) / 1 changeover contact (CO)
Inputs/ Outputs / number of analog outputs0
Inputs/ Outputs / switching capacity current of the relay outputs / at AC-15 at 250 V rated value3 A
Inputs/ Outputs / switching capacity current of the relay outputs / at DC-13 at 24 V rated value1 A
Installation/ mounting/ dimensions / width185 mm
Installation/ mounting/ dimensions / depth203 mm
Installation/ mounting/ dimensions / required spacing with side-by-side mounting / forwards10 mm
Installation/ mounting/ dimensions / required spacing with side-by-side mounting / backwards0 mm
Installation/ mounting/ dimensions / required spacing with side-by-side mounting / upwards100 mm
Installation/ mounting/ dimensions / required spacing with side-by-side mounting / downwards75 mm
Installation/ mounting/ dimensions / required spacing with side-by-side mounting / at the side5 mm
Масса5.2 kg
Connections/ Terminals / type of electrical connection / for main current circuitbox terminal
Connections/ Terminals / type of electrical connection / for control circuitscrew-type terminals
Connections/ Terminals / width of connection bar maximum25 mm
Connections/ Terminals / wire length for thermistor connection / with conductor cross-section = 0.5 mm² maximum50 m
Connections/ Terminals / contacts for box terminal / using the front clamping point finely stranded with core1x (2.5 ... 50 mm²)
Connections/ Terminals / contacts for box terminal / using the front clamping point stranded1x (10 ... 70 mm²)
Connections/ Terminals / contacts for box terminal / using the back clamping point solid1x (2.5 ... 16 mm²)
Connections/ Terminals / contacts for box terminal / r box terminal using the back clamping point1x (10 ... 2/0)
Connections/ Terminals / contacts for box terminal / using both clamping points solid2x (2.5 ... 16 mm²)
Connections/ Terminals / contacts for box terminal / using both clamping points finely stranded with core end2x (2.5 ... 35 mm²)
Connections/ Terminals / contacts for box terminal / using both clamping points stranded2x (6 ... 16 mm²), 2x (10 ... 50 mm²)
Connections/ Terminals / contacts for box terminal / using the back clamping point finely stranded with core1x (2.5 ... 50 mm²)
Connections/ Terminals / contacts for box terminal / using the back clamping point stranded1x (10 ... 70 mm²)
Connections/ Terminals / type of connectable conductor cross-sections / for control circuit solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
Connections/ Terminals / type of connectable conductor cross-sections / for control circuit finely stranded with core end processing1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Connections/ Terminals / type of connectable conductor cross-sections / for AWG cables for control circuit solid1x (20 ... 12), 2x (20 ... 14)
Connections/ Terminals / wire length / between soft starter and motor maximum800 m
Connections/ Terminals / wire length / at the digital inputs at AC maximum100 m
Рабочая температура-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Ambient conditions / ambient temperature / during storage and transport-40 ... +80 °C
Electromagnetic compatibility / EMC emitted interferenceacc. to IEC 60947-4-2: Class A
Communication/ Protocol / communication module is supported / PROFINET standardYes
Communication/ Protocol / communication module is supported / EtherNet/IPYes
Communication/ Protocol / communication module is supported / Modbus RTUYes
Communication/ Protocol / communication module is supported / Modbus TCPYes
Communication/ Protocol / communication module is supported / PROFIBUSYes
UL/CSA ratings / manufacturer's article number / of circuit breaker usable for Standard Faults / at 460/480 V according to ULSiemens type: 3RV2742, max. 70 A or 3VA51, max. 90 A; Iq = 5 kA
UL/CSA ratings / manufacturer's article number / of circuit breaker usable for Standard Faults / 60/480 V according to ULSiemens type: 3VA51, max. 60 A; Iq max = 65 kA
UL/CSA ratings / manufacturer's article number / of circuit breaker usable for Standard Faults / at 460/480 V at inside-delta circuit according to ULSiemens type: 3VA51, max. 90 A; Iq = 5 kA
UL/CSA ratings / manufacturer's article number / of circuit breaker usable for Standard Faults / 60/480 V at inside-delta circuit according to ULSiemens type: 3VA51, max. 60 A; Iq max = 65 kA
UL/CSA ratings / manufacturer's article number / of circuit breaker usable for Standard Faults / at 575/600 V according to ULSiemens type: 3RV2742, max. 70 A or 3VA51, max. 90 A; Iq = 5 kA
UL/CSA ratings / manufacturer's article number / of circuit breaker usable for Standard Faults / at 575/600 V at inside-delta circuit according to ULSiemens type: 3VA51, max. 90 A; Iq = 5 kA
UL/CSA ratings / manufacturer's article number / of the fuse / usable for Standard Faults up to 575/600 VType: Class RK5 / K5, max. 175 A; Iq = 5 kA
UL/CSA ratings / manufacturer's article number / of the fuse / usable for High Faults up to 575/600 V according toType: Class J / L, max. 175 A; Iq = 100 kA
UL/CSA ratings / manufacturer's article number / of the fuse / usable for Standard Faults at inside-delta circuit upType: Class RK5 / K5, max. 175 A; Iq = 5 kA
UL/CSA ratings / operating power [hp] for 3-phase motors / at 220/230 V at 50 °C rated value10 hp
UL/CSA ratings / operating power [hp] for 3-phase motors / at 460/480 V at 50 °C rated value30 hp
UL/CSA ratings / operating power [hp] for 3-phase motors / at 200/208 V at inside-delta circuit at 50 °C rated value20 hp
UL/CSA ratings / operating power [hp] for 3-phase motors / at 220/230 V at inside-delta circuit at 50 °C rated value25 hp
Сертификация67.7 kg
Сертификация1.84 kg
Сертификация242 kg
Сертификация-15.7 kg
Получить предложение по этой позиции