ПЛК и системы автоматизации
SI

Siemens AG 6ES7132-6FD00-0CU0

Модуль ввода-вывода Siemens 6ES7132-6FD00-0CU0, серия ET200SP. Подбор по артикулу, поставка под заказ: цену и срок уточняйте через запрос на поставку.

  • Бренд: Siemens AG
  • Артикул (MPN): 6ES7132-6FD00-0CU0
  • Серия: ET200SP Series
  • Статус производства: Не определён

Категории:

Технические характеристики

Data sheet designationSIMATIC ET 200SP, digital output module DQ 4x 24..230V AC/2A HF packaging unit: 1 piece, two alternative modes: DQ and power control, fits to BU-Type U0, color code CC20, channel diagnosis
General information / Product type designationDQ 4x24 ... 230 V AC/2 A HF
General information / HW functional statusFrom FS03
General information / Firmware version / FW update possibleYes
General information / usable BaseUnitsBU type U0
General information / Color code for module-specific color-coded labelCC20
General information / Product function / I&M dataYes; I&M0 to I&M3
General information / Product function / Isochronous modeNo
General information / Engineering with / STEP 7 TIA Portal configurable/integrated from versionV14
General information / Engineering with / STEP 7 configurable/integrated from versionSTEP 7 V5.5 or higher
General information / Engineering with / PROFIBUS from GSD version/GSD revisionGSD as of Revision 5
General information / Engineering with / PROFINET from GSD version/GSD revisionGSDML V2.3
General information / Operating mode / DQ with energy-saving functionYes
General information / Operating mode / OversamplingNo
General information / Operating mode / Phase controlYes; Control area: 8.5 ... 100% of the phase angle
General information / Operating mode / Trailing-edge phaseNo
General information / Operating mode / Half-waveYes
General information / Operating mode / Full-waveYes
Напряжение питания230 V; 47 ... 63 Hz, max. rate of change of frequency 1 mHz/s
Напряжение питания20.4 V
Напряжение питания264 V
Input current / Current consumption (rated value)8 mA; without load
Напряжение питания230 V; 24V AC to 230V AC
Power loss / Power loss, typ.9 W; Active power, load voltage 230 V, all outputs loaded with 2 A, 50 Hz
Address area / Address space per module / Inputs+ 1 byte for QI information
Address area / Address space per module / Outputs8 byte
Hardware configuration / Automatic encodingYes
Hardware configuration / Mechanical coding elementYes
Hardware configuration / Type of mechanical coding elementtype C
Hardware configuration / Selection of BaseUnit for connection variants / 1-wire connectionBU type U0
Hardware configuration / Selection of BaseUnit for connection variants / 2-wire connectionBU type U0
Hardware configuration / Selection of BaseUnit for connection variants / 3-wire connectionBU type U0 + Potential distributor module
Digital outputs / Type of digital outputTriac
Digital outputs / Number of digital outputs4
Digital outputs / Current-sinkingNo
Digital outputs / Current-sourcingYes
Digital outputs / Digital outputs, parameterizableYes
Digital outputs / Short-circuit protectionNo; external fusing necessary
Digital outputs / Open-circuit detectionYes; channel by channel
Digital outputs / Switching capacity of the outputs / with resistive load, max.2 A; Max. 4 A, see additional description in manual
Digital outputs / Output current / for signal "1" rated value2 A
Digital outputs / Output current / for signal "1" permissible range, min.10 mA
Digital outputs / Output current / for signal "1" permissible range, max.4 A; note derating data in the manual
Digital outputs / Output current / for signal "0" residual current, max.3 mA
Digital outputs / Output delay with resistive load / "0" to "1", max.40 ms; 2 AC cycles
Digital outputs / Output delay with resistive load / "1" to "0", max.20 ms; 1 AC cycle
Digital outputs / Parallel switching of two outputs / for logic linksNo
Digital outputs / Parallel switching of two outputs / for upratingNo
Digital outputs / Parallel switching of two outputs / for redundant control of a loadYes
Digital outputs / Switching frequency / with resistive load, max.10 Hz; Applies to DQ mode; limited by line frequency in PC mode
Digital outputs / Switching frequency / with inductive load (acc. to IEC 60947-5-1, AC15), max.10 Hz; Applies to DQ mode; limited by line frequency in PC mode
Digital outputs / Switching frequency / on lamp load, max.1 Hz; Applies to DQ mode; limited by line frequency in PC mode
Digital outputs / horizontal installation / up to 50 °C, max.6 A
Digital outputs / horizontal installation / up to 60 °C, max.4 A
Digital outputs / vertical installation / up to 30 °C, max.8 A
Digital outputs / vertical installation / up to 40 °C, max.6 A
Digital outputs / vertical installation / up to 50 °C, max.4 A
Digital outputs / Cable length / shielded, max.1 000 m
Digital outputs / Cable length / unshielded, max.600 m
Interrupts/diagnostics/status information / Diagnostics functionYes
Interrupts/diagnostics/status information / Substitute values connectableYes
Interrupts/diagnostics/status information / Alarms / Diagnostic alarmYes
Interrupts/diagnostics/status information / Diagnoses / Diagnostic information readableYes
Напряжение питанияYes
Interrupts/diagnostics/status information / Diagnoses / Wire breakYes; channel by channel
Interrupts/diagnostics/status information / Diagnoses / Short-circuitNo
Interrupts/diagnostics/status information / Diagnoses / Group errorYes
Напряжение питанияYes; green PWR LED
Interrupts/diagnostics/status information / Diagnostics indication LED / Channel status displayYes; green LED
Interrupts/diagnostics/status information / Diagnostics indication LED / for channel diagnosticsYes; red Fn LED
Interrupts/diagnostics/status information / Diagnostics indication LED / for module diagnosticsYes; green/red DIAG LED
Potential separation / Potential separation channels / between the channelsNo
СертификацияNo
СертификацияYes
Сертификация13.9 kg
Сертификация5.53 kg
Сертификация8.71 kg
Рабочая температура-30 °C
Рабочая температура60 °C
Рабочая температура-30 °C
Рабочая температура50 °C
Ambient conditions / Altitude during operation relating to sea level / Installation altitude above sea level, max.2 000 m; On request: Installation altitudes greater than 2 000 m
Ambient conditions / Absolute humidity / dew point, min.-60 °C; suitable for dry room applications
Dimensions / Width20 mm
Dimensions / Height73 mm
Dimensions / Depth58 mm
Сертификацияof Shipping)
Сертификация2/1/2026
Получить предложение по этой позиции