ПЛК и системы автоматизации
SI

Siemens AG 6ES7138-6AA01-0BA0

Модуль ввода-вывода Siemens 6ES7138-6AA01-0BA0, серия ET200SP. Подбор по артикулу, поставка под заказ: цену и срок уточняйте через запрос на поставку.

  • Бренд: Siemens AG
  • Артикул (MPN): 6ES7138-6AA01-0BA0
  • Серия: ET200SP Series
  • Статус производства: Не определён

Категории:

Технические характеристики

Data sheet designationSIMATIC ET 200SP, TM count 1x 24 V Counter module, 1 channel for 24 V incremental encoder or pulse encoder, 3 DI, 2 DQ Suitable for BU type A0, packing quantity: 1 unit,
General information / Product type designationTM Count 1x24V
General information / Firmware versionV2.0
General information / FW update possibleYes
General information / usable BaseUnitsBU type A0
General information / Color code for module-specific color-coded labelCC00
General information / Product function / I&M dataYes; I&M0 to I&M3
General information / Product function / Isochronous modeYes
General information / Engineering with / STEP 7 TIA Portal configurable/integrated from versionSTEP 7 V15 SP1 or higher
General information / Engineering with / STEP 7 configurable/integrated from versionV5.6 and higher
General information / Engineering with / PROFIBUS from GSD version/GSD revisionOne GSD file each, Revision 3 and 5 and higher
General information / Engineering with / PROFINET from GSD version/GSD revisionGSDML V2.34
Напряжение питания24 V
Напряжение питания24 V
Напряжение питания19.2 V
Напряжение питания28.8 V
Напряжение питанияYes
Input current / Current consumption, max.60 mA; without load
Encoder supply / Number of outputs1
Encoder supply / 24 V encoder supply / 24 VYes; L+ (-0.8 V)
Encoder supply / 24 V encoder supply / Short-circuit protectionYes; electronic/thermal
Encoder supply / 24 V encoder supply / Output current, max.300 mA
Power loss / Power loss, typ.1 W
Address area / Address space per module / Inputs16 byte; 4 bytes in Fast mode
Address area / Address space per module / Outputs12 byte; 4 bytes for Motion Control, 0 bytes for Fast mode
Hardware configuration / Automatic encodingYes
Hardware configuration / Mechanical coding elementYes
Hardware configuration / Type of mechanical coding elementtype B
Digital inputs / Number of digital inputs3
Digital inputs / Digital inputs, parameterizableYes
Digital inputs / Input characteristic curve in accordance with IEC 61131, type 3Yes
Digital inputs / Digital input functions, parameterizable / Gate start/stopYes
Digital inputs / Digital input functions, parameterizable / CaptureYes
Digital inputs / Digital input functions, parameterizable / SynchronizationYes
Digital inputs / Digital input functions, parameterizable / Freely usable digital inputYes
Digital inputs / Digital input functions, parameterizable / ProbeYes
Напряжение питания24 V
Напряжение питания-5 ... +5 V
Напряжение питания+11 to +30V
Напряжение питания-30 V; -5 V continuous, -30 V brief reverse polarity protection
Напряжение питания30 V
Digital inputs / for technological functions / ParameterizableYes
Digital inputs / Cable length / shielded, max.1 000 m
Digital inputs / Cable length / unshielded, max.600 m
Digital outputs / Type of digital outputTransistor
Digital outputs / Number of digital outputs2
Digital outputs / Digital outputs, parameterizableYes
Digital outputs / Short-circuit protectionYes; electronic/thermal
Digital outputs / Response threshold, typ.1 A
Напряжение питанияL+ (-53 V)
Digital outputs / Controlling a digital inputYes
Digital outputs / Digital output functions, parameterizable / Switching tripped by comparison valuesYes
Digital outputs / Digital output functions, parameterizable / Freely usable digital outputYes
Digital outputs / Switching capacity of the outputs / with resistive load, max.0.5 A; Per digital output
Digital outputs / Switching capacity of the outputs / on lamp load, max.5 W
Digital outputs / Load resistance range / lower limit48 Ω
Digital outputs / Load resistance range / upper limit12 kΩ
Напряжение питания23.2 V; L+ (-0.8 V)
Digital outputs / Output current / for signal "1" rated value0.5 A; Per digital output
Digital outputs / Output current / for signal "1" permissible range, max.0.6 A; Per digital output
Digital outputs / Output current / for signal "1" minimum load current2 mA
Digital outputs / Output current / for signal "0" residual current, max.0.5 mA
Digital outputs / Output delay with resistive load / "0" to "1", max.50 µs
Digital outputs / Output delay with resistive load / "1" to "0", max.50 µs
Digital outputs / Switching frequency / with resistive load, max.10 kHz
Digital outputs / Switching frequency / with inductive load, max.0.5 Hz; Acc. to IEC 60947-5-1, DC-13; observe derating curve
Digital outputs / Switching frequency / on lamp load, max.10 Hz
Digital outputs / Total current of the outputs / Current per module, max.1 A
Digital outputs / Cable length / shielded, max.1 000 m
Digital outputs / Cable length / unshielded, max.600 m
Encoder / Connectable encoders / 2-wire sensorYes
Encoder / Connectable encoders / permissible quiescent current (2-wire sensor), max.1.5 mA
Напряжение питания24 V
Encoder / Encoder signals, incremental encoder (asymmetrical) / Input frequency, max.200 kHz
Encoder / Encoder signals, incremental encoder (asymmetrical) / Incremental encoder with A/B tracks, 90° phase offsetYes
Encoder / Encoder signals, incremental encoder (asymmetrical) / pulse encoderYes
Encoder / Encoder signals, incremental encoder (asymmetrical) / pulse encoder with directionYes
Encoder / Encoder signals, incremental encoder (asymmetrical) / pulse encoder with one impulse signal per count directionYes
Interrupts/diagnostics/status information / Substitute values connectableYes; Parameterizable
Interrupts/diagnostics/status information / Alarms / Diagnostic alarmYes
Interrupts/diagnostics/status information / Alarms / Hardware interruptYes
Напряжение питанияYes
Interrupts/diagnostics/status information / Diagnoses / Wire breakYes
Interrupts/diagnostics/status information / Diagnoses / Short-circuitYes
Interrupts/diagnostics/status information / Diagnoses / A/B transition error at incremental encoderYes
Interrupts/diagnostics/status information / Diagnoses / Group errorYes
Напряжение питанияYes; green PWR LED
Interrupts/diagnostics/status information / Diagnostics indication LED / Channel status displayYes; green LED
Interrupts/diagnostics/status information / Diagnostics indication LED / for module diagnosticsYes; green/red DIAG LED
Interrupts/diagnostics/status information / Diagnostics indication LED / Status indicator forward counting (green)Yes
Interrupts/diagnostics/status information / Diagnostics indication LED / Status indicator backward counting (green)Yes
Integrated Functions / CounterYes
Integrated Functions / Number of counters1
Integrated Functions / Counting frequency, max.800 kHz; with quadruple evaluation
Integrated Functions / Fast modeYes
Integrated Functions / Counting functions / Can be used with TO High_Speed_CounterYes
Integrated Functions / Counting functions / Continuous countingYes
Integrated Functions / Counting functions / Counter response parameterizableYes
Integrated Functions / Counting functions / Hardware gate via digital inputYes
Integrated Functions / Counting functions / Software gateYes
Integrated Functions / Counting functions / Event-controlled stopYes
Integrated Functions / Counting functions / Synchronization via digital inputYes
Integrated Functions / Counting functions / Counting range, parameterizableYes
Integrated Functions / Counting functions / Comparator / Number of comparators2
Integrated Functions / Counting functions / Comparator / Can be changed from user programYes
Integrated Functions / Position detection / Incremental acquisitionYes
Integrated Functions / Position detection / Suitable for S7-1500 Motion ControlYes
Integrated Functions / Measuring functions / Measuring time, parameterizableYes
Integrated Functions / Measuring functions / Dynamic measurement period adjustmentYes
Integrated Functions / Measuring functions / Number of thresholds, parameterizable2
Integrated Functions / Measuring functions / Measuring range / Frequency measurement, min.0.04 Hz
Integrated Functions / Measuring functions / Measuring range / Frequency measurement, max.800 kHz
Integrated Functions / Measuring functions / Measuring range / Cycle duration measurement, min.1.25 µs
Integrated Functions / Measuring functions / Measuring range / Cycle duration measurement, max.25 s
Integrated Functions / Measuring functions / Accuracy / Frequency measurement100 ppm; depending on measuring interval and signal evaluation
Integrated Functions / Measuring functions / Accuracy / Cycle duration measurement100 ppm; depending on measuring interval and signal evaluation
Integrated Functions / Measuring functions / Accuracy / Velocity measurement100 ppm; depending on measuring interval and signal evaluation
Potential separation / Potential separation channels / between the channels and backplane busYes
Isolation / Isolation tested with707 V DC (type test)
СертификацияNo
Рабочая температура-30 °C
Рабочая температура60 °C; Observe derating
Рабочая температура-30 °C
Рабочая температура50 °C; Observe derating
Ambient conditions / Altitude during operation relating to sea level / Installation altitude above sea level, max.5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Ambient conditions / Absolute humidity / dew point, min.-60 °C; suitable for dry room applications
Decentralized operation / to SIMATIC S7-300Yes
Decentralized operation / to SIMATIC S7-400Yes
Decentralized operation / to SIMATIC S7-1200Yes
Decentralized operation / to SIMATIC S7-1500Yes
Decentralized operation / to standard PROFIBUS masterYes
Decentralized operation / to standard PROFINET controllerYes
Dimensions / Width15 mm
Dimensions / Height73 mm
Dimensions / Depth58 mm
Получить предложение по этой позиции