SI
Siemens AG 6ES7155-6AU00-0HM0
Компонент системы автоматизации Siemens 6ES7155-6AU00-0HM0, серия ET200SP. Подбор по артикулу, поставка под заказ: цену и срок уточняйте через запрос на поставку.
Категории:
Технические характеристики
| Data sheet designation | SIMATIC ET 200SP, PROFINET, 2-port interface module IM 155-6 PN R1, 1 slot for BusAdapter, max. 64 I/O modules R1 redundancy, multi hot swap, 1 ms, PN security class 1 |
|---|---|
| General information / Product type designation | IM 155-6 PN R1 |
| General information / HW functional status | From FS03 |
| General information / Firmware version | V6.1 |
| General information / FW update possible | Yes |
| General information / Product function / I&M data | Yes; I&M0 to I&M4 |
| General information / Product function / Module swapping during operation (hot swapping) | Yes; Multi-hot swapping |
| General information / Product function / Isochronous mode | No |
| General information / Engineering with / STEP 7 TIA Portal configurable/integrated from version | V19 |
| General information / Engineering with / STEP 7 configurable/integrated from version | use GSD file |
| General information / Engineering with / PROFINET from GSD version/GSD revision | GSDML V2.45 |
| Configuration control / via dataset | No |
| CiR - Configuration in RUN / Reparameterization possible in RUN | Yes |
| CiR - Configuration in RUN / reconfiguration possible in RUN | Yes |
| Напряжение питания | 24 V |
| Напряжение питания | 19.2 V |
| Напряжение питания | 28.8 V |
| Напряжение питания | Yes |
| Напряжение питания | Yes |
| Напряжение питания | 10 ms |
| Input current / Current consumption, max. | 700 mA |
| Input current / Inrush current, max. | 5 A |
| Power loss / Power loss, typ. | 2.4 W |
| Address area / Address space per module / Address space per module, max. | 288 byte; For input and output data respectively |
| Address area / Address space per station / Address space per station, max. | 1 440 byte |
| Hardware configuration / Rack / Quantity of operable ET 200SP modules, max. | 64 |
| Hardware configuration / Rack / Quantity of operable ET 200AL modules, max. | 0 |
| Hardware configuration / Submodules / Number of submodules per station, max. | 256 |
| Interfaces / Transmission procedure | 100BASE-TX |
| Interfaces / Number of PROFINET interfaces | 1; 2 ports (switch) |
| 1. Interface / Interface types / RJ 45 (Ethernet) | Yes; with BusAdapter |
| 1. Interface / Interface types / Number of ports | 2; with BusAdapter |
| 1. Interface / Services / Dynamic Frame Packing (DFP) | No |
| 1. Interface / Services / PROFIenergy | No |
| 1. Interface / Services / Prioritized startup | No |
| 1. Interface / Services / Shared device | No |
| Interface types / RJ 45 (Ethernet) / Transmission procedure | PROFINET with 100 Mbit/s full duplex (100BASE-TX) |
| Interface types / RJ 45 (Ethernet) / 100 Mbps | Yes |
| Interface types / RJ 45 (Ethernet) / Autonegotiation | Yes |
| Interface types / RJ 45 (Ethernet) / Autocrossing | Yes |
| Protocols / Supports protocol for PROFINET IO | Yes |
| Protocols / PROFIsafe | Yes |
| Protocols / PROFIBUS | No |
| Protocols / EtherNet/IP | No |
| Protocols / Modbus TCP | No |
| Protocols / Redundancy mode / PROFINET system redundancy (S2) | No |
| Protocols / Redundancy mode / PROFINET system redundancy (R1) | Yes |
| Protocols / Redundancy mode / H-Sync forwarding | Yes |
| Protocols / Redundancy mode / Media redundancy / MRPD | No |
| Protocols / Open IE communication / TCP/IP | Yes |
| Protocols / Open IE communication / SNMP | Yes |
| Protocols / Open IE communication / LLDP | Yes |
| Interrupts/diagnostics/status information / Status indicator | Yes |
| Interrupts/diagnostics/status information / Alarms | Yes |
| Interrupts/diagnostics/status information / Diagnostics function | Yes |
| Interrupts/diagnostics/status information / Diagnostics indication LED / RUN LED | Yes; green LED |
| Interrupts/diagnostics/status information / Diagnostics indication LED / ERROR LED | Yes; red LED |
| Interrupts/diagnostics/status information / Diagnostics indication LED / MAINT LED | Yes; Yellow LED |
| Interrupts/diagnostics/status information / Diagnostics indication LED / ACT LED | Yes; green LED |
| Напряжение питания | Yes; green PWR LED |
| Interrupts/diagnostics/status information / Diagnostics indication LED / Connection display LINK TX/RX | Yes; 2x green link LEDs on BusAdapter |
| Potential separation / between backplane bus and electronics | No |
| Potential separation / between PROFINET and all other circuits | Yes; 1500 V AC (type test) |
| Potential separation / between supply and all other circuits | Yes |
| Permissible potential difference / between different circuits | Safety extra low voltage SELV |
| Isolation / Isolation tested with | 707 V DC (type test) |
| Сертификация | 3 |
| Сертификация | Yes |
| Сертификация | 105 kg |
| Сертификация | 13.7 kg |
| Сертификация | 91.9 kg |
| Security / signed firmware update | Yes |
| Security / Secure Boot | No |
| Security / securely removing data | No |
| Security / data integrity | Yes |
| Рабочая температура | -30 °C; No condensation |
| Рабочая температура | 60 °C |
| Рабочая температура | -30 °C; No condensation |
| Рабочая температура | 50 °C |
| Ambient conditions / Altitude during operation relating to sea level / Installation altitude above sea level, max. | 2 000 m |
| Connection method / ET-Connection / via BU/BA Send | No |
| Dimensions / Width | 50 mm |
| Dimensions / Height | 138 mm |
| Dimensions / Depth | 89 mm |
| Сертификация | tion Society) |
| Сертификация | 5/20/2026 |