ПЛК и системы автоматизации
SI

Siemens AG 6ES7514-2WN03-0AB0

Компонент системы автоматизации Siemens 6ES7514-2WN03-0AB0, серия S7-1500. Подбор по артикулу, поставка под заказ: цену и срок уточняйте через запрос на поставку.

  • Бренд: Siemens AG
  • Артикул (MPN): 6ES7514-2WN03-0AB0
  • Серия: S7-1500 Series
  • Статус производства: Не определён

Категории:

Технические характеристики

Data sheet designationSIMATIC DP, CPU 1514SP TF-2 PN for ET 200SP, central processing unit with 900 KB work memory for program and 3.5 MB for data, 1st interface: PROFINET IRT with 2-port switch, 2nd interface: PROFINET RT 6 ns bit performance, including server module (6ES7193-6PA00-0AA0); SIMATIC Memory Card required, BusAdapter required for 1st interface
General information / Product type designationCPU 1514SP TF-2 PN
General information / HW functional statusFS06
General information / Firmware versionV4.1
General information / FW update possibleYes
General information / Product function / I&M dataYes; I&M0 to I&M3
General information / Product function / Module swapping during operation (hot swapping)Yes; Multi-hot swapping
General information / Product function / Isochronous modeYes; only with PROFINET; with minimum OB 6x cycle of 375 µs
General information / Product function / SysLogYes
General information / Engineering with / STEP 7 TIA Portal configurable/integrated from versionV21 (FW V4.1) / V18 (FW V3.0) or higher
Configuration control / via datasetYes
Control elements / Mode selector switch1
Напряжение питания24 V
Напряжение питания19.2 V
Напряжение питания28.8 V
Напряжение питанияYes
Напряжение питания10 ms
Input current / Current consumption (rated value)0.48 A
Input current / Current consumption, max.0.7 A
Input current / Inrush current, max.1.34 A; Rated value
Power / Infeed power to the backplane bus8.05 W
Power loss / Power loss, typ.3.4 W
Storage / Number of slots for SIMATIC memory card1
Storage / SIMATIC memory card requiredYes
Storage / integrated (for program)900 kbyte
Storage / integrated (for data)3.5 Mbyte
Storage / Load memory / Plug-in (SIMATIC Memory Card), max.32 Gbyte
Storage / Backup / maintenance-freeYes
CPU processing times / for bit operations, typ.6 ns
CPU processing times / for word operations, typ.7 ns
CPU processing times / for fixed point arithmetic, typ.9 ns
CPU processing times / for floating point arithmetic, typ.37 ns
CPU-blocks / Number of elements (total)8 000; Blocks (OB, FB, FC, DB) and UDTs
CPU-blocks / Nesting depth / per priority class24; Up to 8 possible for F-blocks
Counters, timers and their retentivity / S7 counter / Number2 048
Counters, timers and their retentivity / S7 counter / Retentivity / adjustableYes
Counters, timers and their retentivity / IEC counter / NumberAny (only limited by the main memory)
Counters, timers and their retentivity / IEC counter / Retentivity / adjustableYes
Counters, timers and their retentivity / S7 timer / Number2 048
Counters, timers and their retentivity / S7 timer / Retentivity / adjustableYes
Counters, timers and their retentivity / IEC timer / NumberAny (only limited by the main memory)
Counters, timers and their retentivity / IEC timer / Retentivity / adjustableYes
Data areas and their retentivity / Flag / Number of clock memories8; 8 clock memory bit, grouped into one clock memory byte
Data areas and their retentivity / Data blocks / Retentivity adjustableYes
Data areas and their retentivity / Data blocks / Retentivity presetNo
Data areas and their retentivity / Local data / per priority class, max.64 kbyte; max. 16 KB per block
Address area / Number of IO modules8 192; max. number of modules / submodules
Address area / I/O address area / Inputs32 kbyte; All inputs are in the process image
Address area / I/O address area / Outputs32 kbyte; All outputs are in the process image
Address area / I/O address area / per integrated IO subsystem / Inputs (volume)8 kbyte
Address area / I/O address area / per integrated IO subsystem / Outputs (volume)8 kbyte
Address area / I/O address area / per CM/CP / Inputs (volume)8 kbyte
Address area / I/O address area / per CM/CP / Outputs (volume)8 kbyte
Address area / Subprocess images / Number of subprocess images, max.32
Address area / Address space per module / Address space per module, max.288 byte; For input and output data respectively
Hardware configuration / Number of IO Controllers / Integrated2
Hardware configuration / Number of IO Controllers / via CM0
Hardware configuration / Rack / Number of lines, max.1
Time of day / Clock / TypeHardware clock
Time of day / Clock / Backup time6 wk; At 40 °C ambient temperature, typically
Time of day / Clock / Deviation per day, max.10 s; Typ.: 2 s
Time of day / Operating hours counter / Number64
Time of day / Clock synchronization / supportedYes
Time of day / Clock synchronization / to DP, masterYes; Via CM DP module
Time of day / Clock synchronization / on DP, deviceYes; Via CM DP module
Time of day / Clock synchronization / in AS, masterYes
Time of day / Clock synchronization / in AS, deviceYes
Time of day / Clock synchronization / on Ethernet via NTPYes
Interfaces / Number of PROFINET interfaces2
Interfaces / Number of PROFIBUS interfaces1; Via CM DP module
Interfaces / Optical interfaceYes; Via SIMATIC BusAdapter
1. Interface / Interface types / RJ 45 (Ethernet)Yes; X1 P1 and X1 P2 via BusAdapter BA 2x RJ45
1. Interface / Interface types / Number of ports2; via BusAdapter
1. Interface / Protocols / PROFINET IO ControllerYes
1. Interface / Protocols / PROFINET IO DeviceYes
1. Interface / Protocols / SIMATIC communicationYes
1. Interface / Protocols / Open IE communicationYes; Optionally also encrypted
1. Interface / Services / Direct data exchangeYes; Requirement: IRT and isochronous mode (MRPD optional)
1. Interface / Services / Dynamic Frame Packing (DFP)Yes
1. Interface / Services / PROFIenergyYes; per user program
1. Interface / Services / of which in line, max.256
1. Interface / Services / Number of IO Devices that can be simultaneously8; in total across all interfaces
1. Interface / Update time for IRT / for send cycle of 2 ms2 ms to 32 ms
1. Interface / Update time for RT / for send cycle of 500 µs500 µs to 256 ms
1. Interface / Update time for RT / for send cycle of 1 ms1 ms to 512 ms
1. Interface / Services / Dynamic Frame Packing (DFP) #2No
1. Interface / Services / Prioritized startupYes
1. Interface / Services / Shared deviceYes
1. Interface / Services / Number of IO Controllers with shared device, max.4
1. Interface / Services / activation/deactivation of I-devicesYes; per user program
1. Interface / Services / Asset management recordYes; per user program
2. Interface / Interface types / RJ 45 (Ethernet)Yes; X2
2. Interface / Interface types / Number of ports1
2. Interface / Interface types / integrated switchNo
2. Interface / Protocols / IP protocolYes; IPv4
2. Interface / Protocols / PROFINET IO ControllerYes
2. Interface / Protocols / PROFINET IO DeviceYes
2. Interface / Protocols / SIMATIC communicationYes
2. Interface / Protocols / Open IE communicationYes; Optionally also encrypted
2. Interface / Services / Direct data exchangeNo
2. Interface / Services / Dynamic Frame Packing (DFP)No
2. Interface / Services / PROFIenergyYes; per user program
2. Interface / Services / Number of IO Devices that can be simultaneously8; in total across all interfaces
2. Interface / Services / IO Devices changing during operation (partnerYes
2. Interface / Services / Prioritized startupNo
2. Interface / Services / Shared deviceYes
2. Interface / Services / Number of IO Controllers with shared device, max.4
2. Interface / Services / activation/deactivation of I-devicesYes; per user program
2. Interface / Services / Asset management recordYes; per user program
3. Interface / Interface types / RS 485Yes; Via CM DP module
3. Interface / Interface types / Number of ports1
3. Interface / Protocols / PROFIBUS DP masterYes
3. Interface / Protocols / PROFIBUS DP deviceYes
3. Interface / Protocols / SIMATIC communicationYes
3. Interface / PROFIBUS DP master / Services / activation/deactivation of DP devicesYes
Interface types / RJ 45 (Ethernet) / 100 MbpsYes
Interface types / RJ 45 (Ethernet) / AutonegotiationYes
Interface types / RJ 45 (Ethernet) / AutocrossingYes
Interface types / RJ 45 (Ethernet) / Industrial Ethernet status LEDYes
Interface types / RS 485 / Transmission rate, max.12 Mbit/s
Protocols / PROFIsafeYes; V2.4 / V2.6
Protocols / Number of connections / Number of connections, max.192; via integrated interfaces of the CPU and connected CPs / CMs
Protocols / Number of connections / Number of connections reserved for ES/HMI/web10
Protocols / Number of connections / Number of connections via integrated interfaces128
Protocols / Number of connections / Number of connections per CP/CM32
Protocols / Number of connections / Number of S7 routing paths16
Protocols / Redundancy mode / PROFINET system redundancy (S2)No
Protocols / Redundancy mode / PROFINET system redundancy (R1)No
Protocols / Redundancy mode / H-Sync forwardingYes
Protocols / Redundancy mode / Media redundancy / Switchover time on line break, typ.200 ms; For MRP, bumpless for MRPD
Protocols / Redundancy mode / Media redundancy / Number of stations in the ring, max.50
Protocols / SIMATIC communication / PG/OP communicationYes; encryption with TLS V1.3 pre-selected
Protocols / SIMATIC communication / S7 routingYes
Protocols / SIMATIC communication / Data record routingYes
Protocols / SIMATIC communication / S7 communication, as serverYes
Protocols / SIMATIC communication / S7 communication, as clientYes
Protocols / SIMATIC communication / User data per job, max.See online help (S7 communication, user data size)
Protocols / Open IE communication / TCP/IPYes
Protocols / Open IE communication / Data length, max.64 kbyte
Protocols / Open IE communication / several passive connections per port, supportedYes
Protocols / Open IE communication / ISO-on-TCP (RFC1006)Yes
Protocols / Open IE communication / Data length, max. #22 kbyte; 1 472 bytes for UDP broadcast
Protocols / Open IE communication / UDP multicastYes; max. 118 multicast circuits
Protocols / Open IE communication / DHCPYes
Protocols / Open IE communication / SNMPYes
Protocols / Open IE communication / LLDPYes
Protocols / Open IE communication / EncryptionYes; Optional
Protocols / Web server / HTTPYes; Standard and user pages
Protocols / Web server / HTTPSYes; Standard and user pages
Protocols / Web server / web API / Number of sessions, max.100
Protocols / Web server / web API / number of simultaneous HTTP calls, max.4
Protocols / Web server / web API / HTTP request body, max.131 072 byte
Protocols / OPC UA / Runtime license requiredYes; "Medium" license required
Protocols / OPC UA / OPC UA ClientYes; Data Access (registered Read/Write), Method Call
Protocols / OPC UA / Number of nodes of the client interfaces,2 000
Protocols / OPC UA / Number of elements for one call of100
Protocols / OPC UA / Number of registerable nodes, max.5 000
Protocols / OPC UA / Number of registerable method calls of100
Protocols / OPC UA / Number of sessions, max.48
Protocols / OPC UA / Number of accessible variables, max.100 000
Protocols / OPC UA / Number of registerable nodes, max. #220 000
Protocols / OPC UA / Number of subscriptions per session, max.50
Protocols / OPC UA / Sampling interval, min.100 ms
Protocols / OPC UA / Number of alarms for system diagnostics100
Protocols / Further protocols / MODBUSYes; MODBUS TCP
S7 message functions / Number of login stations for message functions, max.64
S7 message functions / number of subscriptions, max.500
S7 message functions / number of tags/attributes for subscriptions, max.8 000
S7 message functions / Number of simultaneously active program alarms / Number of program alarms1 000
S7 message functions / Number of simultaneously active program alarms / Number of alarms for system diagnostics200
S7 message functions / Number of simultaneously active program alarms / Number of alarms for motion technology objects160
Test commissioning functions / Joint commission (Team Engineering)Yes; Parallel online access possible for up to 8 engineering systems
Test commissioning functions / Status blockYes; Up to 8 simultaneously (in total across all ES clients)
Test commissioning functions / Single stepYes
Test commissioning functions / Number of breakpoints8
Test commissioning functions / ProfilingYes
Test commissioning functions / Status/control / Number of variables, max. / of which control variables, max.200; per job
Test commissioning functions / Forcing / ForcingYes; without fail-safe
Test commissioning functions / Forcing / Forcing, variablesperipheral inputs/outputs (without fail-safe)
Test commissioning functions / Forcing / Number of variables, max.200
Test commissioning functions / Diagnostic buffer / presentYes
Test commissioning functions / Diagnostic buffer / Number of entries, max.3 200
Test commissioning functions / Diagnostic buffer / of which powerfail-proof500
Test commissioning functions / Traces / Number of configurable Traces4
Test commissioning functions / Traces / Memory size per trace, max.512 kbyte
Interrupts/diagnostics/status information / Diagnostics indication LED / RUN/STOP LEDYes
Interrupts/diagnostics/status information / Diagnostics indication LED / ERROR LEDYes
Interrupts/diagnostics/status information / Diagnostics indication LED / MAINT LEDYes
Напряжение питанияYes
Interrupts/diagnostics/status information / Diagnostics indication LED / Connection display LINK TX/RXYes
Supported technology objects / Required Motion Control resources / per speed-controlled axis40
Supported technology objects / Required Motion Control resources / per positioning axis80
Supported technology objects / Required Motion Control resources / per synchronous axis160
Supported technology objects / Required Motion Control resources / per external encoder80
Supported technology objects / Required Motion Control resources / per output cam20
Supported technology objects / Required Motion Control resources / per cam track160
Supported technology objects / Required Motion Control resources / per probe40
Supported technology objects / Number of available Extended Motion Control resources120
Supported technology objects / Required Extended Motion Control resources / per cam (1 000 points and 50 segments)2
Supported technology objects / Required Extended Motion Control resources / per cam (10 000 points and 50 segments)20
Supported technology objects / Required Extended Motion Control resources / per cam (50 points and 600 segments)2
Supported technology objects / Required Extended Motion Control resources / per cam (50 points and 6 000 segments)20
Supported technology objects / Required Extended Motion Control resources / for each set of kinematics30
Supported technology objects / Required Extended Motion Control resources / per Interpreter60
Supported technology objects / Required Extended Motion Control resources / Per leading axis proxy3
Supported technology objects / kinematics functions / kinematics with up to 4 interpolating axesYes; max. 3D + orientation
Supported technology objects / kinematics functions / kinematics with 5 or more interpolating axesNo
Supported technology objects / kinematics functions / user-defined kinematicsNo
Supported technology objects / kinematics functions / SIMATIC Safe KinematicsNo
Supported technology objects / Positioning axis / Number of positioning axes at motion control cycle11
Supported technology objects / Controller / PID_3StepYes; PID controller with integrated optimization for valves
Supported technology objects / Controller / PID-TempYes; PID controller with integrated optimization for temperature
Supported technology objects / Counting and measuring / High-speed counterYes
СертификацияSiemens EcoTech
СертификацияYes
СертификацияYes
Сертификация83.2 kg
Сертификация22.3 kg
Сертификация61.8 kg
СертификацияSIL 3
Сертификацияof 100 hours)
Сертификация< 2.00E-05
Security / signed firmware updateYes
Security / Secure BootYes
Security / safely removing dataYes
Рабочая температура-30 °C; No condensation
Рабочая температура60 °C
Рабочая температура-30 °C; No condensation
Рабочая температура50 °C
Configuration / Programming language / GRAPHYes
Configuration / Know-how protection / User program protection/password protectionYes
Configuration / Know-how protection / Copy protectionYes
Configuration / Know-how protection / Block protectionYes
Configuration / Access protection / protection of confidential configuration dataYes
Configuration / Access protection / Protection level: Write protectionYes
Configuration / Access protection / Protection level: Read/write protectionYes
Configuration / Access protection / Protection level: Write protection for FailsafeYes
Configuration / Access protection / Protection level: Complete protectionYes
Configuration / Access protection / User administrationYes; device-wide and centralized
Configuration / Access protection / Number of users100
Configuration / Access protection / Number of groups100
Configuration / Access protection / Number of roles50
Configuration / Cycle time monitoring / lower limitadjustable minimum cycle time
Configuration / Cycle time monitoring / upper limitadjustable maximum cycle time
Dimensions / Width100 mm
Dimensions / Height117 mm
Dimensions / Depth75 mm
Получить предложение по этой позиции