| Data sheet designation | SIMATIC S7-1500, digital output module DQ 32x24V DC/0.5A HF; 32 channels in groups of 8; 4 A per group; single-channel diagnostics; substitute value, switching cycle counter for connected actuators. the module supports the safety-oriented shutdown of load groups up to SIL2 according to EN IEC 62061:2021 and Category 3 / PL d according to EN ISO 13849-1:2015. front connector (screw terminals or push-in) to be ordered separately |
|---|---|
| General information / Product type designation | DQ 32x24VDC/0.5A HF |
| General information / HW functional status | From FS02 |
| General information / Firmware version | V1.1.0 |
| General information / Product function / I&M data | Yes; I&M0 to I&M3 |
| General information / Product function / Isochronous mode | Yes |
| General information / Product function / Prioritized startup | Yes |
| General information / Engineering with / STEP 7 TIA Portal configurable/integrated from version | V13 SP1 / - |
| General information / Engineering with / STEP 7 configurable/integrated from version | V5.5 SP3 / - |
| General information / Engineering with / PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 |
| General information / Engineering with / PROFINET from GSD version/GSD revision | V2.3 / - |
| General information / Operating mode / DQ with energy-saving function | No |
| General information / Operating mode / Cam control (switching at comparison values) | No |
| General information / Operating mode / Oversampling | No |
| General information / Operating mode / Integrated operating cycle counter | Yes |
| Напряжение питания | 24 V |
| Напряжение питания | 19.2 V |
| Напряжение питания | 28.8 V |
| Напряжение питания | Yes; through internal protection with 7 A per group |
| Input current / Current consumption, max. | 60 mA |
| Напряжение питания | 24 V |
| Power / Power consumption from the backplane bus | 1.1 W |
| Power loss / Power loss, typ. | 3.5 W |
| Address area / Address space per module / Inputs | 0 byte; typical, maximum 28 bytes, see manual for details |
| Address area / Address space per module / Outputs | 4 byte |
| Digital outputs / Type of digital output | Transistor |
| Digital outputs / Number of digital outputs | 32 |
| Digital outputs / Current-sinking | No |
| Digital outputs / Current-sourcing | Yes |
| Digital outputs / Digital outputs, parameterizable | Yes |
| Digital outputs / output type acc. to IEC 61131, type 0.5 | Yes |
| Digital outputs / Short-circuit protection | Yes; Clocked electronically |
| Digital outputs / Response threshold, typ. | 1 A |
| Напряжение питания | L+ (-53 V) |
| Digital outputs / Controlling a digital input | Yes |
| Digital outputs / Digital output functions, parameterizable / Switching tripped by comparison values | No |
| Digital outputs / Digital output functions, parameterizable / Digital output with oversampling | No |
| Digital outputs / Switching capacity of the outputs / with resistive load, max. | 0.5 A |
| Digital outputs / Switching capacity of the outputs / on lamp load, max. | 5 W |
| Digital outputs / Load resistance range / lower limit | 48 Ω |
| Digital outputs / Load resistance range / upper limit | 12 kΩ |
| Напряжение питания | L+ (-0.8 V) |
| Digital outputs / Output current / for signal "1" rated value | 0.5 A |
| Digital outputs / Output current / for signal "1" permissible range, max. | 0.5 A |
| Digital outputs / Output current / for signal "0" residual current, max. | 0.5 mA |
| Digital outputs / Output delay with resistive load / "0" to "1", max. | 100 µs |
| Digital outputs / Output delay with resistive load / "1" to "0", max. | 500 µs |
| Digital outputs / Parallel switching of two outputs / for logic links | Yes |
| Digital outputs / Parallel switching of two outputs / for uprating | No |
| Digital outputs / Parallel switching of two outputs / for redundant control of a load | Yes |
| Digital outputs / Switching frequency / with resistive load, max. | 100 Hz |
| Digital outputs / Switching frequency / with inductive load, max. | 0.5 Hz; According to IEC 60947-5-1, DC-13 |
| Digital outputs / Switching frequency / on lamp load, max. | 10 Hz |
| Digital outputs / Total current of the outputs / Current per channel, max. | 0.5 A; see additional description in the manual |
| Digital outputs / Total current of the outputs / Current per group, max. | 4 A; see additional description in the manual |
| Digital outputs / Total current of the outputs / Current per module, max. | 16 A; see additional description in the manual |
| Digital outputs / Cable length / shielded, max. | 1 000 m |
| Digital outputs / Cable length / unshielded, max. | 600 m |
| Isochronous mode / Execution and activation time (TCO), min. | 70 µs |
| Isochronous mode / Bus cycle time (TDP), min. | 250 µs |
| Interrupts/diagnostics/status information / Diagnostics function | Yes |
| Interrupts/diagnostics/status information / Substitute values connectable | Yes |
| Interrupts/diagnostics/status information / Alarms / Diagnostic alarm | Yes |
| Interrupts/diagnostics/status information / Alarms / Maintenance interrupt | Yes; maintenance alarm for switching cycle counter |
| Напряжение питания | Yes |
| Interrupts/diagnostics/status information / Diagnoses / Wire break | Yes |
| Interrupts/diagnostics/status information / Diagnoses / Short-circuit | Yes |
| Interrupts/diagnostics/status information / Diagnoses / Group error | Yes |
| Interrupts/diagnostics/status information / Diagnostics indication LED / RUN LED | Yes; green LED |
| Interrupts/diagnostics/status information / Diagnostics indication LED / ERROR LED | Yes; red LED |
| Interrupts/diagnostics/status information / Diagnostics indication LED / MAINT LED | Yes; Yellow LED |
| Напряжение питания | Yes; green LED |
| Interrupts/diagnostics/status information / Diagnostics indication LED / Channel status display | Yes; green LED |
| Interrupts/diagnostics/status information / Diagnostics indication LED / for channel diagnostics | Yes; red LED |
| Interrupts/diagnostics/status information / Diagnostics indication LED / for module diagnostics | Yes; red LED |
| Potential separation / Potential separation channels / between the channels | No |
| Potential separation / Potential separation channels / between the channels, in groups of | 8 |
| Potential separation / Potential separation channels / between the channels and backplane bus | Yes |
| Isolation / Isolation tested with | 707 V DC (type test) |
| Сертификация | Siemens EcoTech |
| Сертификация | No |
| Сертификация | Yes; From FS02 |
| Сертификация | Yes |
| Сертификация | 43.8 kg |
| Сертификация | 9.5 kg |
| Сертификация | 34.5 kg |
| Сертификация | Cat. 3 |
| Сертификация | SIL 2 |
| Сертификация | https://support.industry.siemens.com/cs/de/en/view/39198632 |
| Security / signed firmware update | Yes; Firmware V3.0.0 or higher |
| Security / securely removing data | No |
| Security / data integrity | Yes; Firmware V3.0.0 or higher |
| Рабочая температура | -30 °C; From FS03 |
| Рабочая температура | 60 °C |
| Рабочая температура | -30 °C; From FS03 |
| Рабочая температура | 40 °C |
| Ambient conditions / Altitude during operation relating to sea level / Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| Ambient conditions / Absolute humidity / dew point, min. | -60 °C; suitable for dry room applications |
| Dimensions / Width | 35 mm |
| Dimensions / Height | 147 mm |
| Dimensions / Depth | 129 mm |
| Сертификация | of Shipping) |
| Сертификация | 8/27/2026 |