Модуль ввода-вывода Siemens 6ES7522-5HF00-0AB0, серия S7-1500. Подбор по артикулу, поставка под заказ: цену и срок уточняйте через запрос на поставку.

  • Бренд: Siemens AG
  • Артикул (MPN): 6ES7522-5HF00-0AB0
  • Серия: S7-1500 Series
  • Статус производства: Не определён

Категории:

Технические характеристики

Data sheet designationSIMATIC S7-1500, digital output module DQ 8xAC 230V/5A ST; relay; 8 channels in groups of 1; 5 A per group; diagnostics; substitute value: switching cycle counter for integrated relay, the module supports the safety-oriented shutdown of load groups up to SIL1 according to EN IEC 62061:2021 and Category 2 / PL c according to EN ISO 13849-1:2015. front connector (screw terminals or push-in) to be ordered separately
General information / Product type designationDQ 8x230 V AC/5 A ST (relay)
General information / HW functional statusFrom FS02
General information / Firmware versionV2.1.0
General information / FW update possibleYes
General information / Product function / I&M dataYes; I&M0 to I&M3
General information / Product function / Isochronous modeNo
General information / Product function / Prioritized startupYes
General information / Engineering with / STEP 7 TIA Portal configurable/integrated from versionV12 / V12
General information / Engineering with / STEP 7 configurable/integrated from versionV5.5 SP3 / -
General information / Engineering with / PROFIBUS from GSD version/GSD revisionV1.0 / V5.1
General information / Engineering with / PROFINET from GSD version/GSD revisionV2.3 / -
General information / Operating mode / DQ with energy-saving functionNo
General information / Operating mode / OversamplingNo
General information / Operating mode / Integrated operating cycle counterYes; FW V2.1.0 or higher
Напряжение питания24 V
Напряжение питания20.4 V
Напряжение питания28.8 V
Напряжение питанияYes
Input current / Current consumption, max.80 mA
Напряжение питания230 V; 24 V DC to 120 V DC / 24 V AC to 230 V AC
Power / Power consumption from the backplane bus0.8 W
Power loss / Power loss, typ.5 W
Digital outputs / Type of digital outputRelays
Digital outputs / Number of digital outputs8
Digital outputs / Current-sinkingYes
Digital outputs / Current-sourcingYes
Digital outputs / Digital outputs, parameterizableYes
Digital outputs / Short-circuit protectionNo
Digital outputs / Controlling a digital inputYes; possible
Digital outputs / Size of motor starters according to NEMA, max.5
Digital outputs / Switching capacity of the outputs / on lamp load, max.1 500 W; 10 000 operating cycles
Digital outputs / Output current / for signal "1" rated value5 A
Digital outputs / Output current / for signal "1" permissible range, min.5 mA; 10 V
Digital outputs / Output current / for signal "1" permissible range, max.8 A; thermal continuous current
Digital outputs / Output current / for signal "0" residual current, max.0 A
Digital outputs / Parallel switching of two outputs / for logic linksYes
Digital outputs / Parallel switching of two outputs / for upratingNo
Digital outputs / Parallel switching of two outputs / for redundant control of a loadYes
Digital outputs / Switching frequency / with resistive load, max.2 Hz
Digital outputs / Switching frequency / with inductive load, max.0.5 Hz
Digital outputs / Switching frequency / on lamp load, max.2 Hz
Digital outputs / Total current of the outputs / Current per channel, max.8 A; see additional description in the manual
Digital outputs / Total current of the outputs / Current per group, max.8 A; see additional description in the manual
Digital outputs / Total current of the outputs / Current per module, max.64 A; see additional description in the manual
Digital outputs / Relay outputs / Number of relay outputs8
Напряжение питания24 V
Digital outputs / Relay outputs / Current consumption of relays (coil current of all relays),80 mA
Digital outputs / Relay outputs / Relay approved acc. to UL 508Yes; 250 V AC/5 A g.p.; 120 V AC TV-4 tungsten; A300, R300
Digital outputs / Relay outputs / Switching capacity of contacts / with inductive load, max.see additional description in the manual
Digital outputs / Relay outputs / Switching capacity of contacts / with resistive load, max.see additional description in the manual
Digital outputs / Cable length / shielded, max.1 000 m
Digital outputs / Cable length / unshielded, max.600 m
Interrupts/diagnostics/status information / Diagnostics functionYes
Interrupts/diagnostics/status information / Substitute values connectableYes
Interrupts/diagnostics/status information / Alarms / Diagnostic alarmYes
Напряжение питанияYes
Interrupts/diagnostics/status information / Diagnoses / Wire breakNo
Interrupts/diagnostics/status information / Diagnoses / Short-circuitNo
Interrupts/diagnostics/status information / Diagnostics indication LED / RUN LEDYes; green LED
Interrupts/diagnostics/status information / Diagnostics indication LED / ERROR LEDYes; red LED
Interrupts/diagnostics/status information / Diagnostics indication LED / MAINT LEDYes; Yellow LED
Напряжение питанияYes; green LED
Interrupts/diagnostics/status information / Diagnostics indication LED / Channel status displayYes; green LED
Interrupts/diagnostics/status information / Diagnostics indication LED / for channel diagnosticsNo
Interrupts/diagnostics/status information / Diagnostics indication LED / for module diagnosticsYes; red LED
Potential separation / Potential separation channels / between the channelsYes; Switching of different phases permitted
Potential separation / Potential separation channels / between the channels, in groups of1
Potential separation / Potential separation channels / between the channels and backplane busYes
Напряжение питанияYes
Security / signed firmware updateNo
Security / data integrityNo
Рабочая температура-30 °C; From FS03
Рабочая температура60 °C
Рабочая температура-30 °C; From FS03
Рабочая температура40 °C
Dimensions / Width35 mm
Dimensions / Height147 mm
Dimensions / Depth129 mm
Сертификацияof Shipping)
Сертификация10/23/2025
Получить предложение по этой позиции