Технические характеристики

Data sheet designationSIMATIC S7-1500, digital output module DQ 16x 230V AC/2A ST; relay 16 channels in groups of 2; 4 A per group; switching cycle counter for integrated relay, diagnostics; substitute value: the module supports the safety-oriented shutdown of load groups up to SIL1 according to EN IEC 62061:2021 and Category 2 / PL c according to EN ISO 13849-1:2015. front connector (screw terminals or push-in) to be ordered separately
General information / Product type designationDQ 16x 230 V AC/2 A ST (relay)
General information / HW functional statusFS01
General information / Firmware versionV1.1.0
General information / FW update possibleYes
General information / Product function / I&M dataYes; I&M0 to I&M3
General information / Product function / Isochronous modeNo
General information / Product function / Prioritized startupYes
General information / Engineering with / STEP 7 TIA Portal configurable/integrated from versionV13 SP1 / -
General information / Engineering with / STEP 7 configurable/integrated from versionV5.5 SP3 / -
General information / Engineering with / PROFIBUS from GSD version/GSD revisionV1.0 / V5.1
General information / Engineering with / PROFINET from GSD version/GSD revisionV2.3 / -
General information / Operating mode / DQ with energy-saving functionNo
General information / Operating mode / Cam control (switching at comparison values)No
General information / Operating mode / OversamplingNo
General information / Operating mode / Integrated operating cycle counterYes; FW V1.1.0 or higher
Напряжение питания24 V
Напряжение питания19.2 V
Напряжение питания28.8 V
Напряжение питанияYes
Input current / Current consumption, max.185 mA
Напряжение питания230 V; 24 V DC to 120 V DC / 24 V AC to 230 V AC
Power / Power consumption from the backplane bus0.8 W
Power loss / Power loss, typ.5 W
Address area / Address space per module / Inputs0 byte; typical, maximum 14 bytes, see manual for details
Address area / Address space per module / Outputs2 byte
Digital outputs / Type of digital outputRelays
Digital outputs / Number of digital outputs16
Digital outputs / Current-sinkingYes
Digital outputs / Current-sourcingYes
Digital outputs / Digital outputs, parameterizableYes
Digital outputs / Short-circuit protectionNo
Digital outputs / Controlling a digital inputYes
Digital outputs / Size of motor starters according to NEMA, max.5
Digital outputs / Digital output functions, parameterizable / Switching tripped by comparison valuesNo
Digital outputs / Digital output functions, parameterizable / Freely usable digital outputNo
Digital outputs / Digital output functions, parameterizable / PWM outputNo
Digital outputs / Digital output functions, parameterizable / Digital output with oversamplingNo
Digital outputs / Switching capacity of the outputs / with resistive load, max.2 A
Digital outputs / Switching capacity of the outputs / on lamp load, max.50 W (230 V AC), 5 W (24 V DC)
Digital outputs / Output current / for signal "1" rated value2 A
Digital outputs / Output current / for signal "1" permissible range, min.10 mA; 10 V
Digital outputs / Output current / for signal "1" permissible range, max.2 A; thermal continuous current
Digital outputs / Output current / for signal "0" residual current, max.0 A
Digital outputs / Parallel switching of two outputs / for logic linksYes
Digital outputs / Parallel switching of two outputs / for upratingNo
Digital outputs / Parallel switching of two outputs / for redundant control of a loadYes
Digital outputs / Switching frequency / with resistive load, max.1 Hz
Digital outputs / Switching frequency / with inductive load, max.0.5 Hz
Digital outputs / Switching frequency / on lamp load, max.1 Hz
Digital outputs / Total current of the outputs / Current per channel, max.2 A; see additional description in the manual
Digital outputs / Total current of the outputs / Current per group, max.4 A; see additional description in the manual
Digital outputs / Total current of the outputs / Current per module, max.32 A; see additional description in the manual
Digital outputs / Relay outputs / Number of relay outputs16
Напряжение питания24 V
Digital outputs / Relay outputs / Current consumption of relays (coil current of all relays),150 mA
Digital outputs / Relay outputs / external protection for relay outputsMiniature circuit breaker B10 / B16
Digital outputs / Relay outputs / Contact connection (internal)No
Digital outputs / Relay outputs / Number of operating cycles, max.see additional description in the manual
Digital outputs / Relay outputs / Switching capacity of contacts / with inductive load, max.2 A; see additional description in the manual
Digital outputs / Relay outputs / Switching capacity of contacts / with resistive load, max.2 A; see additional description in the manual
Digital outputs / Cable length / shielded, max.1 000 m
Digital outputs / Cable length / unshielded, max.600 m
Interrupts/diagnostics/status information / Diagnostics functionNo
Interrupts/diagnostics/status information / Substitute values connectableYes
Interrupts/diagnostics/status information / Alarms / Diagnostic alarmYes
Interrupts/diagnostics/status information / Alarms / Maintenance interruptYes; maintenance alarm for switching cycle counter
Напряжение питанияYes
Interrupts/diagnostics/status information / Diagnoses / Wire breakNo
Interrupts/diagnostics/status information / Diagnoses / Short-circuitNo
Interrupts/diagnostics/status information / Diagnoses / Group errorNo
Interrupts/diagnostics/status information / Diagnostics indication LED / RUN LEDYes; green LED
Interrupts/diagnostics/status information / Diagnostics indication LED / ERROR LEDYes; red LED
Interrupts/diagnostics/status information / Diagnostics indication LED / MAINT LEDYes; Yellow LED
Напряжение питанияYes; green LED
Interrupts/diagnostics/status information / Diagnostics indication LED / Channel status displayYes; green LED
Interrupts/diagnostics/status information / Diagnostics indication LED / for channel diagnosticsNo
Interrupts/diagnostics/status information / Diagnostics indication LED / for module diagnosticsYes; red LED
Potential separation / Potential separation channels / between the channelsNo
Potential separation / Potential separation channels / between the channels, in groups of2
Potential separation / Potential separation channels / between the channels and backplane busYes
Напряжение питанияYes
СертификацияNo
СертификацияYes; From FS02
СертификацияYes
Сертификация43.8 kg
Сертификация9.5 kg
Сертификация34.5 kg
СертификацияCat. 2
СертификацияSIL 1
Сертификацияhttps://support.industry.siemens.com/cs/de/en/view/39198632
Security / signed firmware updateYes; Firmware V3.0.0 or higher
Security / securely removing dataNo
Security / data integrityYes; Firmware V3.0.0 or higher
Рабочая температура-25 °C; From FS02
Рабочая температура60 °C
Рабочая температура-25 °C; From FS02
Рабочая температура40 °C
Ambient conditions / Altitude during operation relating to sea level / Installation altitude above sea level, max.2 000 m
Dimensions / Width35 mm
Dimensions / Height147 mm
Dimensions / Depth129 mm