ПЛК и системы автоматизации
SI

Siemens AG 6ES7531-7PF00-0AB0

Модуль ввода-вывода Siemens 6ES7531-7PF00-0AB0, серия S7-1500. Подбор по артикулу, поставка под заказ: цену и срок уточняйте через запрос на поставку.

  • Бренд: Siemens AG
  • Артикул (MPN): 6ES7531-7PF00-0AB0
  • Серия: S7-1500 Series
  • Статус производства: Не определён

Категории:

Технические характеристики

Data sheet designationSIMATIC S7-1500 analog input module AI 8xU/R/RTD/TC HF, 16 bit resolution, up to 21 bit Resolution at RT and TC, accuracy 0.1%, 8 channels in groups of 1; common mode voltage: 30 V AC/60 V DC, Diagnostics; Hardware interrupts Scalable temperature measuring range, thermocouple type C, Calibrate in RUN; Delivery including infeed element, shield bracket and shield terminal: Front connector (screw terminals or push-in) to be ordered separately
General information / Product type designationAI 8xU/R/RTD/TC HF
General information / HW functional statusfrom FS01
General information / Firmware versionV1.1.0
General information / FW update possibleYes
General information / Product function / I&M dataYes; I&M0 to I&M3
General information / Product function / Isochronous modeNo
General information / Product function / Prioritized startupYes
General information / Product function / Measuring range scalableYes
General information / Product function / Scalable measured valuesNo
General information / Product function / Adjustment of measuring rangeNo
General information / Engineering with / STEP 7 TIA Portal configurable/integrated from versionV14 / -
General information / Engineering with / STEP 7 configurable/integrated from versionV5.5 SP3 / -
General information / Engineering with / PROFIBUS from GSD version/GSD revisionV1.0 / V5.1
General information / Engineering with / PROFINET from GSD version/GSD revisionV2.3 / -
General information / Operating mode / OversamplingNo
CiR - Configuration in RUN / Reparameterization possible in RUNYes
CiR - Configuration in RUN / Calibration possible in RUNYes
Напряжение питания24 V
Напряжение питания19.2 V
Напряжение питания28.8 V
Напряжение питанияYes
Input current / Current consumption, max.55 mA; with 19.2 V supply
Power / Power consumption from the backplane bus0.85 W
Power loss / Power loss, typ.1.9 W
Address area / Address space per module / Inputs18 byte; typical, maximum 80 bytes, see manual for details
Address area / Address space per module / Outputs0 byte
Analog inputs / Number of analog inputs8; Plus one additional RTD (reference) channel
Напряжение питания8; Plus one additional RTD (reference) channel
Analog inputs / For resistance/resistance thermometer measurement8; Plus one additional RTD (reference) channel
Analog inputs / Standardization of measured valuesYes; See manual for details
Напряжение питанияNo
Напряжение питанияNo
Напряжение питанияNo
Напряжение питанияYes
Напряжение питания10 MΩ
Напряжение питанияNo
Напряжение питанияNo
Напряжение питанияYes
Напряжение питания10 MΩ
Напряжение питанияYes
Напряжение питания10 MΩ
Напряжение питанияNo
Напряжение питанияYes
Напряжение питания10 MΩ
Напряжение питанияYes
Напряжение питания10 MΩ
Напряжение питанияYes
Напряжение питания10 MΩ
Analog inputs / Input ranges (rated values), currents / 0 to 20 mANo
Analog inputs / Input ranges (rated values), currents / -20 mA to +20 mANo
Analog inputs / Input ranges (rated values), currents / 4 mA to 20 mANo
Analog inputs / Input ranges (rated values), thermocouples / type BYes
Analog inputs / Input ranges (rated values), thermocouples / Input resistance (Type B)10 MΩ
Analog inputs / Input ranges (rated values), thermocouples / type CYes
Analog inputs / Input ranges (rated values), thermocouples / Input resistance (Type C)10 MΩ
Analog inputs / Input ranges (rated values), thermocouples / Type EYes
Analog inputs / Input ranges (rated values), thermocouples / Input resistance (Type E)10 MΩ
Analog inputs / Input ranges (rated values), thermocouples / Type JYes
Analog inputs / Input ranges (rated values), thermocouples / Input resistance (type J)10 MΩ
Analog inputs / Input ranges (rated values), thermocouples / Type KYes
Analog inputs / Input ranges (rated values), thermocouples / Input resistance (Type K)10 MΩ
Analog inputs / Input ranges (rated values), thermocouples / Type LNo
Analog inputs / Input ranges (rated values), thermocouples / Type NYes
Analog inputs / Input ranges (rated values), thermocouples / Input resistance (Type N)10 MΩ
Analog inputs / Input ranges (rated values), thermocouples / Type RYes
Analog inputs / Input ranges (rated values), thermocouples / Input resistance (Type R)10 MΩ
Analog inputs / Input ranges (rated values), thermocouples / Type SYes
Analog inputs / Input ranges (rated values), thermocouples / Input resistance (Type S)10 MΩ
Analog inputs / Input ranges (rated values), thermocouples / Type TYes
Analog inputs / Input ranges (rated values), thermocouples / Input resistance (Type T)10 MΩ
Analog inputs / Input ranges (rated values), thermocouples / Type TXK/TXK(L) to GOSTYes
Analog inputs / Input ranges (rated values), thermocouples / Input resistance (Type TXK/TXK(L) to GOST)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Cu 10Yes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Cu 10)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Cu 10 according to GOSTYes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Cu 10 according to GOST)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Cu 50Yes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Cu 50)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Cu 50 according to GOSTYes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Cu 50 according to GOST)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Cu 100Yes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Cu 100)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Cu 100 according to GOSTYes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Cu 100 according to GOST)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Ni 10Yes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Ni 10)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Ni 10 according to GOSTYes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Ni 10 according to GOST)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Ni 100Yes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Ni 100)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Ni 100 according to GOSTYes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Ni 100 according to GOST)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Ni 1000Yes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Ni 1000)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Ni 1000 according to GOSTYes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Ni 1000 according to GOST)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / LG-Ni 1000Yes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (LG-Ni 1000)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Ni 120Yes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Ni 120)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Ni 120 according to GOSTYes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Ni 120 according to GOST)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Ni 200Yes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Ni 200)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Ni 200 according to GOSTYes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Ni 200 according to GOST)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Ni 500Yes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Ni 500)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Ni 500 according to GOSTYes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Ni 500 according to GOST)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Pt 10Yes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Pt 10)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Pt 10 according to GOSTYes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Pt 10 according to GOST)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Pt 50Yes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Pt 50)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Pt 50 according to GOSTYes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Pt 50 according to GOST)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Pt 100Yes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Pt 100)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Pt 100 according to GOSTYes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Pt 100 according to GOST)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Pt 1000Yes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Pt 1000)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Pt 1000 according to GOSTYes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Pt 1000 according to GOST)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Pt 200Yes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Pt 200)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Pt 200 according to GOSTYes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Pt 200 according to GOST)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Pt 500Yes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Pt 500)10 MΩ
Analog inputs / Input ranges (rated values), resistance thermometer / Pt 500 according to GOSTYes; Standard/climate
Analog inputs / Input ranges (rated values), resistance thermometer / Input resistance (Pt 500 according to GOST)10 MΩ
Analog inputs / Input ranges (rated values), resistors / 0 to 150 ohmsYes
Analog inputs / Input ranges (rated values), resistors / Input resistance (0 to 150 ohms)10 MΩ
Analog inputs / Input ranges (rated values), resistors / 0 to 300 ohmsYes
Analog inputs / Input ranges (rated values), resistors / Input resistance (0 to 300 ohms)10 MΩ
Analog inputs / Input ranges (rated values), resistors / 0 to 600 ohmsYes
Analog inputs / Input ranges (rated values), resistors / Input resistance (0 to 600 ohms)10 MΩ
Analog inputs / Input ranges (rated values), resistors / 0 to 3000 ohmsNo
Analog inputs / Input ranges (rated values), resistors / 0 to 6000 ohmsYes
Analog inputs / Input ranges (rated values), resistors / Input resistance (0 to 6000 ohms)10 MΩ
Analog inputs / Temperature compensation / internal temperature compensationYes
Analog inputs / Temperature compensation / external temperature compensation via RTDYes
Analog value generation for the inputs / Measurement principleintegrating
Analog value generation for the inputs / Smoothing of measured values / ParameterizableYes
Analog value generation for the inputs / Smoothing of measured values / Step: NoneYes
Analog value generation for the inputs / Smoothing of measured values / Step: lowYes
Analog value generation for the inputs / Smoothing of measured values / Step: MediumYes
Analog value generation for the inputs / Smoothing of measured values / Step: HighYes
Напряжение питанияYes
Encoder / Connection of signal encoders / for current measurement as 2-wire transducerNo
Encoder / Connection of signal encoders / for current measurement as 4-wire transducerNo
Errors/accuracies / Linearity error (relative to input range), (+/-)0.02 %
Errors/accuracies / Temperature error (relative to input range), (+/-)0.005 %/K
Напряжение питания0.1 %
Напряжение питания60 V DC/30 V AC
Errors/accuracies / Common mode interference, min.80 dB
Interrupts/diagnostics/status information / Diagnostics functionYes
Interrupts/diagnostics/status information / Alarms / Diagnostic alarmYes
Interrupts/diagnostics/status information / Alarms / Limit value alarmYes; two upper and two lower limit values in each case
Напряжение питанияYes
Interrupts/diagnostics/status information / Diagnoses / Wire breakYes; Only with TC, R, RTD
Interrupts/diagnostics/status information / Diagnoses / short-circuitNo
Interrupts/diagnostics/status information / Diagnoses / Group errorNo
Interrupts/diagnostics/status information / Diagnoses / Overflow/UnderflowYes
Interrupts/diagnostics/status information / Diagnostics indication LED / RUN LEDYes; green LED
Interrupts/diagnostics/status information / Diagnostics indication LED / ERROR LEDYes; red LED
Interrupts/diagnostics/status information / Diagnostics indication LED / MAINT LEDNo
Напряжение питанияYes; green LED
Interrupts/diagnostics/status information / Diagnostics indication LED / Channel status displayYes; green LED
Interrupts/diagnostics/status information / Diagnostics indication LED / for channel diagnosticsYes; red LED
Interrupts/diagnostics/status information / Diagnostics indication LED / for module diagnosticsYes; red LED
Potential separation / Potential separation channels / between the channelsYes
Potential separation / Potential separation channels / between the channels, in groups of1
СертификацияYes; Declaration of Conformity, see online support entry 109757262
СертификацияYes; Based on AMS 2750 E
СертификацияYes
Сертификация38.6 kg
Сертификация14.4 kg
Сертификация24.6 kg
Security / safely removing dataNo
Security / data integrityNo
Рабочая температура-30 °C; From FS02
Рабочая температура60 °C
Рабочая температура-30 °C; From FS02
Рабочая температура40 °C
Ambient conditions / Altitude during operation relating to sea level / Installation altitude above sea level, max.2 000 m
Ambient conditions / Absolute humidity / dew point, min.-60 °C; suitable for dry room applications
Dimensions / Width35 mm
Dimensions / Height147 mm
Dimensions / Depth129 mm
Масса290 g
Получить предложение по этой позиции