SI
Siemens AG 6ES7536-1MF00-0AB0
Модуль ввода-вывода Siemens 6ES7536-1MF00-0AB0, серия S7-1500. Подбор по артикулу, поставка под заказ: цену и срок уточняйте через запрос на поставку.
Категории:
Технические характеристики
| Data sheet designation | SIMATIC S7-1500, F-analog input module, F-AI 8xI 0(4)..20 mA PROFIsafe; 35 mm, overall width; up to PL e (ISO 13849-1)/ SIL 3 (IEC 61508) |
|---|---|
| General information / Product type designation | F-AI 8xI 0(4) ... 20 mA |
| General information / Firmware version / FW update possible | Yes |
| General information / Product function / I&M data | Yes; I&M0 to I&M3 |
| General information / Engineering with / STEP 7 TIA Portal configurable/integrated from version | V18 with HSP0394 (FW V1.0) / V19 with HSP0451 (FW V2.0) |
| CiR - Configuration in RUN / Reparameterization possible in RUN | No |
| CiR - Configuration in RUN / Calibration possible in RUN | No |
| Напряжение питания | 24 V |
| Напряжение питания | 19.2 V |
| Напряжение питания | 28.8 V |
| Напряжение питания | Yes |
| Input current / Current consumption (rated value) | 75 mA |
| Input current / Current consumption, max. | 2.5 A; All channels are supplied from the encoder supply |
| Encoder supply / Number of outputs | 8 |
| Encoder supply / Short-circuit protection | Yes |
| Encoder supply / 24 V encoder supply / 24 V | Yes; min. L+ (-1.5 V) |
| Encoder supply / 24 V encoder supply / Short-circuit protection | Yes |
| Encoder supply / 24 V encoder supply / Output current per channel, max. | 300 mA |
| Power / Power consumption from the backplane bus | 0.5 W |
| Power loss / Power loss, typ. | 2.5 W |
| Address area / Address space per module / Inputs | 23 byte |
| Address area / Address space per module / Outputs | 6 byte |
| Hardware configuration / Automatic encoding | Yes |
| Analog inputs / Input ranges (rated values), currents / Input resistance (0 to 20 mA) | 150 Ω |
| Analog inputs / Input ranges (rated values), currents / 4 mA to 20 mA | Yes |
| Analog inputs / Input ranges (rated values), currents / Input resistance (4 mA to 20 mA) | 150 Ω |
| Analog inputs / Cable length / shielded, max. | 1 000 m |
| Analog value generation for the inputs / Measurement principle | Sigma Delta |
| Analog value generation for the inputs / Integration and conversion time/resolution per channel / Resolution with overrange (bit including sign), max. | 16 bit |
| Analog value generation for the inputs / Integration and conversion time/resolution per channel / Integration time, parameterizable | Yes |
| Analog value generation for the inputs / Smoothing of measured values / parameterizable | Yes |
| Analog value generation for the inputs / Smoothing of measured values / Step: None | Yes; 1x conversion time |
| Analog value generation for the inputs / Smoothing of measured values / Step: low | Yes; 2x / 4x conversion cycle time |
| Analog value generation for the inputs / Smoothing of measured values / Step: Medium | Yes; 8x / 16x conversion cycle time |
| Analog value generation for the inputs / Smoothing of measured values / Step: High | Yes; 32x / 64x conversion cycle time |
| Encoder / Connection of signal encoders / for current measurement as 2-wire transducer | Yes |
| Encoder / Connection of signal encoders / Burden of 2-wire transmitter, max. | 650 Ω |
| Encoder / Connection of signal encoders / for current measurement as 4-wire transducer | Yes |
| Errors/accuracies / Linearity error (relative to input range), (+/-) | 0.05 % |
| Errors/accuracies / Temperature error (relative to input range), (+/-) | 0.005 %/K |
| Errors/accuracies / Basic error limit (operational limit at 25 °C) / Current, relative to input range, (+/-) | 0.05 %; without HART communication |
| Errors/accuracies / Influence of a HART signal modulated on the input signal in relation | to input range |
| Errors/accuracies / error occurred at interference frequency suppression: 60 | 0.12 % |
| Напряжение питания | 60 V DC/30 V AC |
| Errors/accuracies / Common mode interference, min. | 70 dB |
| Interrupts/diagnostics/status information / Diagnostics function | Yes |
| Interrupts/diagnostics/status information / Alarms / Diagnostic alarm | Yes |
| Interrupts/diagnostics/status information / Alarms / Limit value alarm | No |
| Напряжение питания | Yes |
| Interrupts/diagnostics/status information / Diagnoses / Wire break | Yes |
| Interrupts/diagnostics/status information / Diagnoses / Short-circuit | Yes |
| Interrupts/diagnostics/status information / Diagnoses / Overflow/Underflow | Yes |
| Interrupts/diagnostics/status information / Diagnostics indication LED / RUN LED | Yes; green LED |
| Interrupts/diagnostics/status information / Diagnostics indication LED / ERROR LED | Yes; red LED |
| Напряжение питания | Yes; green PWR LED |
| Interrupts/diagnostics/status information / Diagnostics indication LED / Channel status display | Yes; green LED |
| Interrupts/diagnostics/status information / Diagnostics indication LED / for channel diagnostics | Yes; red LED |
| Potential separation / Potential separation analog inputs / between the channels | No |
| Potential separation / Potential separation analog inputs / between the channels, in groups of | 4 |
| Isolation / Isolation tested with | 707 V DC (type test) |
| Сертификация | PLe |
| Сертификация | Cat. 4 |
| Сертификация | SIL 3 |
| Сертификация | of 100 hours) |
| Сертификация | < 4.00E-05 |
| Рабочая температура | 0 °C |
| Рабочая температура | 60 °C |
| Рабочая температура | 0 °C |
| Рабочая температура | 40 °C |
| Dimensions / Width | 35 mm |
| Dimensions / Height | 147 mm |
| Dimensions / Depth | 129 mm |
| Сертификация | of Shipping) |
| Сертификация | 10/23/2025 |